| Parameter | Value |
|---|---|
| For power distribution applications, IEC 60364-4-43:2008, as amended + Corrigendum Ott. 2008 (DIN VDE 0100-430:2010-10) section 433.2 ff! | |
| note | The maximum load current of the individual connection points must not be exceeded. |
| Color | multicoloured |
| Depth | 21.7 mm |
| width | 56.5 mm |
| Result | Test passed |
| height | 28.6 mm |
| Feeding | Yes |
| Spectrum | Category 2 Electrical Life Check, Trolley Mounted |
| ASD Level | 6.12 (m/s²)²/Hz |
| Frequency | f1= 5 Hz up to f2= 250 Hz |
| Gauge Pad | A3 |
| Potential | 1 |
| Shock Form | Semi-sinusoidal |
| Acceleration | 3.12g |
| Product Type | Distribution terminal |
| Mounting type | Mounting on adapters for mounting on a support rail |
| Rated current | 24 A |
| Article review | 01 |
| Number of rows | 1 |
| Open side wall | no |
| Shock Duration | 18 ms |
| Nominal voltage | 450 V |
| Test Directions | X, Y, and Z axis |
| AWG Sizing Section | 14 |
| Note for Operation | The blocks can be bridged together over the conductor compartment, for suitable plug-in jumpers, see accessories |
| Test Specification | DIN EN 50155 (VDE 0115-200):2008-03 |
| Degree of pollution | 3 |
| Insulation material | PA |
| Maximum load current | 32 A (with a conductor cross-section of 4 mm²) |
| Overvoltage Category | Iii |
| Nominal cross-section | 2.5 mm² |
| Number of connections | 19 |
| Sizing Impulse Voltage | 6 kV |
| Test duration per axle | 5 h |
| Duration of application | 30 s |
| Insulation Material Group | The |
| Maximum cumulative current | 57 A (with a conductor cross-section of 10 mm²) |
| Conductor cross-section AWG | 26 ... 12 (converted according to IEC) |
| Support rail/fixing support | NS 35/NS 15 |
| Rigid conductor cross-section | 0.14 mm² ... 4 mm² |
| Standard-compliant connection | IEC 60998-2-2 |
| Ambient temperature (mounting) | -5 °C ... 70 °C |
| Number of connections per plan | 19 |
| Number of shocks per direction | 3 |
| Ambient temperature (operating) | -60 °C ... 110 °C (Operating temperature range including self-heating, short-term maximum operating temperature cf. RTI Elec.) |
| Ambient Temperature (Activation) | -5 °C ... 70 °C |
| Flexible conductor cross-section | 0.14 mm² ... 2.5 mm² |
| Permissible humidity (operation) | 20 % ... 90 % |
| NFPA 130 Fume Toxicity (SMP 800C) | Exceeded |
| Solid conductor cross-section [AWG] | 24 ... 12 (converted according to IEC) |
| Length of the section to be stripped | 8 mm ... 10 mm |
| Cold static insulation material insert | -60 °C |
| Flexible conductor cross-section [AWG] | 26 ... 14 (converted according to IEC) |
| Ambient temperature (storage/transport) | -25 °C ... 60 °C (for short duration, no longer than 24 h, -60 °C to +70 °C) |
| Combustibility class according to UL 94 | V0 |
| Permissible humidity (storage/transport) | 30 % ... 70 % |
| Surface Flammability NFPA 130 (ASTM E 162) | Exceeded |
| Maximum power dissipation under nominal conditions | 0.77 W |
| Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 - HL 3 |
| Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 - HL 3 |
| Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 - HL 3 |
| Fire protection for rail vehicles (DIN EN 45545-2) R26 | HL 1 - HL 3 |
| NFPA 130 (ASTM E 662) Specific Optical Density of Fumes | Exceeded |
| Flexible conductor cross-section (plastic lug and collar) | 0.14 mm² ... 2.5 mm² |
| Heat development calorimetric cone NFPA 130 (ASTM E 1354) | 28 MJ/kg |
| Insulation Material Relative Temperature Index (Elec., UL 746 B) | 130 °C |
| Flexible conductor cross-section (cable lug without insulation collar) | 0.14 mm² ... 2.5 mm² |
| Temperature index for insulation material (DIN EN 60216-1 (VDE 0304-21)) | 130 °C |
| 2 conductors of identical cross-section flexible with TWIN ferrule with plastic collar | 0.5 mm² ... 1.5 mm² |
| Flexible conductor cross-section (2 conductors of identical cross-section with TWIN ferrule with plastic collar) | 0.5 mm² ... 1.5 mm² |
Technical specifications and performance data