| Parameter | Value |
|---|---|
| GTIN | 4017918904739 |
| Orderkey | 2964005 |
| Catalog page | Page 263 (C-6-2017) |
| Depth (Note) | 114.5 mm |
| Packing unit | 1 pc |
| Width (Note) | 35 mm |
| (Input data) | C6 (24 V AC/DC) automatic device |
| Height (Note) | 112 mm |
| (Output data) | IP54 |
| Country of origin | DE (Germany) |
| pluggable (General) | Yes |
| Custom tariff number | 85371098 |
| Net weight (Output data) | 270.18 g |
| Output fuse (Input data) | 6 A fast blow |
| Relay type (Output data) | Electromechanical relay with forcibly guided contacts in accordance with EN 50205 |
| Contact type (Input data) | 5 enabling current paths |
| Category (Connection data) | 4 (In conjunction with suitable evaluating device) |
| Stripping length (General) | 8 mm |
| Connection method (General) | Spring-cage connection |
| Housing color (Output data) | yellow |
| Mounting type (Output data) | DIN rail mounting |
| (Standards and Regulations) | No hazardous substances above threshold values |
| Contact material (Input data) | AgSnO2, + 0.2 µm Au |
| Designation (Connection data) | EN 62061 |
| Maximum altitude (Dimensions) | ≤ 2000 m (Above sea level) |
| Sq. Total current (Input data) | 72 A2(ITH2= I12+ I22+ ... + I52) |
| Mounting position (Output data) | any |
| Stop category (Connection data) | 0 |
| Degree of protection (Output data) | IP20 |
| Maximum inrush current (Input data) | 6 A |
| Status display (Ambient conditions) | Green LED |
| Inrush current, minimum (Input data) | 25 mA |
| Mechanical service life (Input data) | approx. 107cycles |
| Nominal operating mode (Output data) | 100% operating factor |
| Switching capacity min. (Input data) | 0.4 W |
| Weight per Piece (excluding packing) | 270.180 g |
| China RoHS (Standards and Regulations) | Environmentally friendly use period: unlimited = EFUP-e |
| Maximum switching voltage (Input data) | 250 V AC/DC |
| Minimum switching voltage (Input data) | 15 V AC/DC |
| Protective circuit (Ambient conditions) | Surge protection Suppressor diode |
| Limiting continuous current (Input data) | 6 A (N/O contact) |
| Performance level (PL) (Connection data) | e (In conjunction with suitable evaluating device) |
| Typical release time (Ambient conditions) | 20 ms |
| Concurrence input 1/2 (Ambient conditions) | ∞ |
| Conductor cross section AWG max. (General) | 16 |
| Conductor cross section AWG min. (General) | 24 |
| Shock (Safety-related characteristic data) | 15g |
| Typical response time (Ambient conditions) | 20 ms |
| Ambient temperature (operation) (Dimensions) | -20 °C ... 55 °C |
| Conductor cross section solid max. (General) | 1.5 mm² |
| Conductor cross section solid min. (General) | 0.2 mm² |
| Nominal input voltage UN (Ambient conditions) | 24 V AC/DC |
| Utilization restriction (Key Commercial Data) | EMC: class A product, see manufacturer's declaration in the download area |
| Safety Integrity Level (SIL) (Connection data) | 3 (In conjunction with suitable evaluating device) |
| Switching capacity (360/h cycles) (Input data) | 4 A (24 V DC) |
| Conductor cross section flexible max. (General) | 1.5 mm² |
| Conductor cross section flexible min. (General) | 0.2 mm² |
| Designation (Safety-related characteristic data) | Air clearances and creepage distances between the power circuits |
| Typical input current at UN (Ambient conditions) | 47 mA (per channel) |
| Interrupting rating (ohmic load) max. (Input data) | 144 W (24 V DC, τ = 0 ms, N/C contact 11/12: 72 W) |
| Ambient temperature (storage/transport) (Dimensions) | -40 °C ... 70 °C |
| Degree of pollution (Safety-related characteristic data) | 2 |
| Maximum interrupting rating (inductive load) (Input data) | 42 W (24 V DC, τ = 40 ms) |
| Min. degree of protection of inst. location (Output data) | IP54 |
| Overvoltage category (Safety-related characteristic data) | III |
| Max. permissible humidity (storage/transport) (Dimensions) | 75 % (on average, 85% infrequently, non-condensing) |
| Standards/regulations (Safety-related characteristic data) | DIN EN 50178/VDE 0160 |
| Vibration (operation) (Safety-related characteristic data) | 10 Hz ... 150 Hz, 2g |
| Input voltage range in reference to UN (Ambient conditions) | 0.8 ... 1.1 |
| Max. permissible relative humidity (operation) (Dimensions) | 75 % (on average, 85% infrequently, non-condensing) |
| Rated control circuit supply voltage US (Ambient conditions) | |
| Rated insulation voltage (Safety-related characteristic data) | 250 V |
| Safety Integrity Level Claim Limit (SIL CL) (Connection data) | 3 (In conjunction with suitable evaluating device) |
| Rated surge voltage/insulation (Safety-related characteristic data) | 4 kV / Basic isolation, (safe isolation, reinforced insulation and 6 kV between input circuit and enabling current paths(43/44, 53/54, 63/64, 71/72) and between 43/44, 53/54, 63/64, 71/72 themselves.) |
Technical specifications and performance data