| Parameter | Value |
|---|---|
| 250 V | |
| Depth | 114.5 mm |
| Shock | 15g |
| Width | 35 mm |
| Height | 112 mm |
| Category | 4 (In conjunction with suitable evaluating device) |
| pluggable | yes |
| Relay type | Electromechanical relay with force-guided contacts in accordance with IEC/EN 61810-3 |
| Application | Extension module |
| Output fuse | 10 A gL/gG |
| Product type | Safety relays |
| Mounting type | DIN rail mounting |
| Recovery time | < 1 s |
| Stop category | 0 |
| Identification | CE-compliant |
| Inrush current | min. 10 mA |
| Product family | PSRclassic |
| Contact material | AgSnO2 |
| Housing material | Polyamide |
| Maximum altitude | ≤ 2000 m (Above sea level) |
| Number of inputs | 2 |
| Stripping length | 8 mm |
| Connection method | Push-in connection |
| Mounting position | vertical or horizontal |
| Number of outputs | 5 |
| Sq. Total current | 72 A2(observe derating) |
| Switching voltage | min. 10 V |
| Output description | 2 N/O contacts each in series, safety-related, floating |
| Protective circuit | Suppressor diode |
| Switching capacity | min. 100 mW |
| Current consumption | typ. 39 mA |
| Switching frequency | max. 1 Hz |
| Degree of protection | IP20 |
| Typical release time | < 20 ms (at Us / when controlled via A11/A12) |
| Assembly instructions | Observe derating |
| Standards/regulations | EN 60947-1 |
| Vibration (operation) | 10 Hz ... 150 Hz, amplitude 0.15 mm, 2g |
| Contact switching type | 5 enabling current paths |
| Nominal operating mode | 100% operating factor |
| Performance level (PL) | e (In conjunction with suitable evaluating device) |
| Mechanical service life | approx. 107cycles |
| Description of the input | safety-related |
| Rated insulation voltage | 250 V |
| Operating voltage display | 2 x green LED |
| Typ. starting time with Us | < 25 ms (at Us / when controlled via A11/A12) |
| Conductor cross-section AWG | 24 ... 16 |
| Limiting continuous current | 6 A (observe derating) |
| Maximum switching frequency | 1 Hz |
| Safety Integrity Level (SIL) | 3 (In conjunction with suitable evaluating device) |
| Conductor cross section rigid | 0.2 mm² ... 1.5 mm² |
| Input voltage range "1" signal | 19.2 V ... 26.4 V DC |
| Rated surge voltage/insulation | See section “Insulation coordination” |
| Ambient temperature (operation) | -20 °C ... 55 °C (observe derating) |
| Conductor cross section flexible | 0.2 mm² ... 1.5 mm² |
| Ambient temperature (storage/transport) | -40 °C ... 70 °C |
| Min. degree of protection of inst. location | IP54 |
| Max. permissible humidity (storage/transport) | 75 % (on average, 85% infrequently, non-condensing) |
| Max. permissible overall conductor resistance | 50 Ω |
| Max. permissible relative humidity (operation) | 75 % (on average, 85% infrequently, non-condensing) |
| Maximum power dissipation for nominal condition | 16.7 W (US= 26.4 V, IL² = 72 A², PTotal max= 1.4 W + 14.4 W) |
| Switching capacity in accordance with IEC 60947-5-1 | 3 A (AC15) |
| Conductor cross section, flexible, with ferrule, with plastic sleeve | 0.25 mm² ... 1.5 mm² (only together with CRIMPFOX 6) |
| Conductor cross section flexible, with ferrule without plastic sleeve | 0.25 mm² ... 1.5 mm² (only together with CRIMPFOX 6) |
Technical specifications and performance data
Installation and operation guide