Service time: Monday to Friday 9:00-18:00
PSR-SPP-24DC/URM4/5X1/2X2 - PSR-SPP-24DC/URM4/5X1/2X2 1442026 PHOENIX CONTACT Extension of 1 or 2 channel contacts, 5 normally open cont..
In Stock Hot Product

PSR-SPP-24DC/URM4/5X1/2X2

PSR-SPP-24DC/URM4/5X1/2X2 1442026 PHOENIX CONTACT Extension of 1 or 2 channel contacts, 5 normally open cont..

$282.54USD
73 in stock
Key Specifications
:250 V
Depth:114.5 mm
Shock:15g
Width:35 mm
Supplier Information
Products: 0
Usually ships within 2-3 business days
Quality Guaranteed
Fast Shipping
Technical Support

Technical Specifications

ParameterValue
250 V
Depth114.5 mm
Shock15g
Width35 mm
Height112 mm
Category4 (In conjunction with suitable evaluating device)
pluggableyes
Relay typeElectromechanical relay with force-guided contacts in accordance with IEC/EN 61810-3
ApplicationExtension module
Output fuse10 A gL/gG
Product typeSafety relays
Mounting typeDIN rail mounting
Recovery time< 1 s
Stop category0
IdentificationCE-compliant
Inrush currentmin. 10 mA
Product familyPSRclassic
Contact materialAgSnO2
Housing materialPolyamide
Maximum altitude≤ 2000 m (Above sea level)
Number of inputs2
Stripping length8 mm
Connection methodPush-in connection
Mounting positionvertical or horizontal
Number of outputs5
Sq. Total current72 A2(observe derating)
Switching voltagemin. 10 V
Output description2 N/O contacts each in series, safety-related, floating
Protective circuitSuppressor diode
Switching capacitymin. 100 mW
Current consumptiontyp. 39 mA
Switching frequencymax. 1 Hz
Degree of protectionIP20
Typical release time< 20 ms (at Us / when controlled via A11/A12)
Assembly instructionsObserve derating
Standards/regulationsEN 60947-1
Vibration (operation)10 Hz ... 150 Hz, amplitude 0.15 mm, 2g
Contact switching type5 enabling current paths
Nominal operating mode100% operating factor
Performance level (PL)e (In conjunction with suitable evaluating device)
Mechanical service lifeapprox. 107cycles
Description of the inputsafety-related
Rated insulation voltage250 V
Operating voltage display2 x green LED
Typ. starting time with Us< 25 ms (at Us / when controlled via A11/A12)
Conductor cross-section AWG24 ... 16
Limiting continuous current6 A (observe derating)
Maximum switching frequency1 Hz
Safety Integrity Level (SIL)3 (In conjunction with suitable evaluating device)
Conductor cross section rigid0.2 mm² ... 1.5 mm²
Input voltage range "1" signal19.2 V ... 26.4 V DC
Rated surge voltage/insulationSee section “Insulation coordination”
Ambient temperature (operation)-20 °C ... 55 °C (observe derating)
Conductor cross section flexible0.2 mm² ... 1.5 mm²
Ambient temperature (storage/transport)-40 °C ... 70 °C
Min. degree of protection of inst. locationIP54
Max. permissible humidity (storage/transport)75 % (on average, 85% infrequently, non-condensing)
Max. permissible overall conductor resistance50 Ω
Max. permissible relative humidity (operation)75 % (on average, 85% infrequently, non-condensing)
Maximum power dissipation for nominal condition16.7 W (US= 26.4 V, IL² = 72 A², PTotal max= 1.4 W + 14.4 W)
Switching capacity in accordance with IEC 60947-5-13 A (AC15)
Conductor cross section, flexible, with ferrule, with plastic sleeve0.25 mm² ... 1.5 mm² (only together with CRIMPFOX 6)
Conductor cross section flexible, with ferrule without plastic sleeve0.25 mm² ... 1.5 mm² (only together with CRIMPFOX 6)

Product Description

Single-channel or two-channel contact extension, 5 N/O contacts, 1 N/C contact, 1 confirmation current path, together with basic device up to Cat. 4 PL e in accordance with EN ISO 13849 safe isolation
Key Features
  • Industrial grade quality
  • RoHS compliant
  • CE certified
  • 1-year warranty

Product Documents

Datasheet

Technical specifications and performance data

User Manual

Installation and operation guide

Top