| Parameter | Value |
|---|---|
| Safety door | |
| Depth | 114.5 mm |
| Shock | 15g |
| Width | 22.5 mm |
| Height | 99 mm |
| Category | 4 |
| pluggable | yes |
| Relay type | Electromechanical relay with force-guided contacts in accordance with IEC/EN 61810-3 |
| Application | Emergency stop |
| Concurrence | ∞ |
| Filter time | 5 ms (at A1 in the event of voltage dips at Us) |
| Output fuse | 10 A gL/gG (Enabling current paths) |
| Product type | Safety relays |
| Screw thread | M3 |
| Assembly note | See derating curve |
| Mounting type | DIN rail mounting |
| Recovery time | 1 s (following demand of the safety function) |
| Stop category | 0 |
| Identification | CE-compliant |
| Inrush current | < 3.5 A (Δt = 3 ms at Us) |
| Product family | PSRclassic |
| Status display | LED (green) |
| Color (Housing) | yellow (RAL 1018) |
| Article revision | 06 |
| Contact material | AgSnO2, + 0.2 µm Au |
| Housing material | Polyamide |
| Maximum altitude | ≤ 2000 m (Above sea level) |
| Stripping length | 7 mm |
| Connection method | Screw connection |
| Mounting position | vertical or horizontal |
| Sq. Total current | 72 A2(Enabling current paths) |
| Protective circuit | Surge protection; Suppressor diode |
| Current consumption | typ. 38 mA (S12) |
| Note on application | Only for industrial use |
| Degree of protection | IP20 |
| Typical release time | 20 ms (on demand via the sensor circuit) |
| Standards/regulations | DIN EN 60947-1 |
| Typical response time | 100 ms (Monitored/manual start) |
| Vibration (operation) | 10 Hz ... 150 Hz, 2g |
| Contact switching type | 3 enabling current paths |
| Maximum inrush current | 6 A |
| Nominal operating mode | 100% operating factor |
| Performance level (PL) | e (5 A DC13; 5 A AC15; 8760 switching cycles/year) |
| Inrush current, minimum | 10 mA |
| Mechanical service life | approx. 107cycles |
| Power consumption at US | typ. 1.68 W (DC) |
| Switching capacity min. | 100 mW |
| Rated insulation voltage | 250 V |
| Maximum switching voltage | 250 V AC/DC |
| Minimum switching voltage | 10 V AC/DC |
| Operating voltage display | Green LED |
| Typ. starting time with Us | 250 ms (when controlled via A1) |
| Conductor cross-section AWG | 24 ... 12 |
| Limiting continuous current | 6 A (Observe derating and load limit curve) |
| Typical input current at UN | 70 mA DC (at Us) |
| Safety Integrity Level (SIL) | 3 |
| Conductor cross section rigid | 0.2 mm² ... 2.5 mm² |
| Rated surge voltage/insulation | See section “Insulation coordination” |
| Ambient temperature (operation) | -20 °C ... 55 °C (observe derating) |
| Rated control supply current IS | typ. 70 mA |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Interrupting rating (ohmic load) max. | see load limit curve |
| Input voltage range in reference to UN | 0.85 ... 1.1 |
| Ambient temperature (storage/transport) | -40 °C ... 70 °C |
| Rated control circuit supply voltage US | 24 V DC -15 % / +10 % |
| Min. degree of protection of inst. location | IP54 |
| Voltage at input/start and feedback circuit | approx. 24 V DC |
| Max. permissible humidity (storage/transport) | 75 % (on average, 85% infrequently, non-condensing) |
| Max. permissible overall conductor resistance | approx. 50 Ω (Input and start circuits at US) |
| Max. permissible relative humidity (operation) | 75 % (on average, 85% infrequently, non-condensing) |
| Maximum power dissipation for nominal condition | 16.44 W (US= 26.4 V, IL² = 72 A², PTotal max= 2.04 W + 14.4 W) |
| Switching capacity in accordance with IEC 60947-5-1 | 6 A (DC13, enabling current paths) |
Technical specifications and performance data
Installation and operation guide