Service time: Monday to Friday 9:00-18:00
PSR-SCP- 24DC/RSM4/4X1 - PSR-SCP- 24DC/RSM4/4X1 2981538 PHOENIX CONTACT Safety device
In Stock Hot Product

PSR-SCP- 24DC/RSM4/4X1

PSR-SCP- 24DC/RSM4/4X1 2981538 PHOENIX CONTACT Safety device

$0.00USD
4463 in stock
Key Specifications
GTIN:4017918996826
Orderkey:2981538
Catalog page:Page 275 (C-6-2017)
Depth (Note):114.5 mm
Supplier Information
Products: 0
Usually ships within 2-3 business days
Quality Guaranteed
Fast Shipping
Technical Support

Technical Specifications

ParameterValue
GTIN4017918996826
Orderkey2981538
Catalog pagePage 275 (C-6-2017)
Depth (Note)114.5 mm
Packing unit1 pc
Width (Note)45 mm
(Input data)68 MW (220 V DC, τ = 0 ms)
Height (Note)99 mm
(Output data)IP54
Country of originDE (Germany)
pluggable (General)Yes
Custom tariff number90328900
(Ambient conditions)400 kHz (RJ45)
Screw thread (General)M3
Net weight (Output data)365 g
Output fuse (Input data)6 A gL
Relay type (Output data)Electromechanical relay with forcibly guided contacts in accordance with EN 50205
Contact type (Input data)4 enabling current paths
Category (Connection data)4
Stripping length (General)7 mm
Connection method (General)Screw connection
Housing color (Output data)yellow
Mounting type (Output data)DIN rail mounting
(Standards and Regulations)For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”
Contact material (Input data)AgNi10, + 5 µm Au
Designation (Connection data)EN ISO 13849
Maximum altitude (Dimensions)max. 2000 m (Above sea level)
Sq. Total current (Input data)42.25 A2(ITH2= I12+ I22+ I32+ I42)
Mounting position (Output data)any
Stop category (Connection data)0
Degree of protection (Output data)IP20
Recovery time (Ambient conditions)1 s
Assembly instructions (Output data)In rows with zero spacing
Maximum inrush current (Input data)6 A
Status display (Ambient conditions)Green LED
Inrush current, minimum (Input data)1 mA
Limit frequency (Ambient conditions)2 kHz (IN1, IN2)
Mechanical service life (Input data)> 50x 106cycles
Nominal operating mode (Output data)100% operating factor
Switching capacity min. (Input data)1 mW
Weight per Piece (excluding packing)365.000 g
China RoHS (Standards and Regulations)Environmentally Friendly Use Period = 50
Maximum switching voltage (Input data)250 V AC/DC (when the gold layer is destroyed)
Minimum switching voltage (Input data)100 mV AC/DC
Protective circuit (Ambient conditions)Surge protection Suppressor diode
Limiting continuous current (Input data)5 A
Performance level (PL) (Connection data)e
Typical release time (Ambient conditions)12 ms
Conductor cross section AWG max. (General)12
Conductor cross section AWG min. (General)24
Typical response time (Ambient conditions)15 ms
Ambient temperature (operation) (Dimensions)-20 °C ... 55 °C
Conductor cross section solid max. (General)2.5 mm²
Conductor cross section solid min. (General)0.2 mm²
Nominal input voltage UN (Ambient conditions)24 V DC
Utilization restriction (Key Commercial Data)EMC: class A product, see manufacturer's declaration in the download area
Safety Integrity Level (SIL) (Connection data)3
Conductor cross section flexible max. (General)2.5 mm²
Conductor cross section flexible min. (General)0.2 mm²
Designation (Safety-related characteristic data)Air clearances and creepage distances between the power circuits
Typical input current at UN (Ambient conditions)100 mA
Interrupting rating (ohmic load) max. (Input data)67 W (24 V DC, τ = 0 ms)
Ambient temperature (storage/transport) (Dimensions)-40 °C ... 70 °C
Degree of pollution (Safety-related characteristic data)2
Min. degree of protection of inst. location (Output data)IP54
Overvoltage category (Safety-related characteristic data)III
Max. permissible humidity (storage/transport) (Dimensions)75 % (on average, 85% infrequently, non-condensing)
Standards/regulations (Safety-related characteristic data)EN 60664/VDE 0110
Input voltage range in reference to UN (Ambient conditions)0.85 ... 1.1
Max. permissible relative humidity (operation) (Dimensions)75 % (on average, 85% infrequently, non-condensing)
Rated control circuit supply voltage US (Ambient conditions)
Rated insulation voltage (Safety-related characteristic data)250 V
Safety Integrity Level Claim Limit (SIL CL) (Connection data)3
Voltage at input/start and feedback circuit (Ambient conditions)approx. 24 V DC
Rated surge voltage/insulation (Safety-related characteristic data)4 kV / Basic isolation, (safe isolation, reinforced insulation and 6 kV between input circuit and enabling current paths.)

Product Description

2-channel speed and stop controller up to SIL 3 or category 4, PL e according to EN ISO 13849, 4 NO contacts, suitable for connection of incremental encoders and initiators, plug-in screw connection t
Key Features
  • Industrial grade quality
  • RoHS compliant
  • CE certified
  • 1-year warranty

Product Documents

Datasheet

Technical specifications and performance data

User Manual

Installation and operation guide

Top