| Parameter | Value |
|---|---|
| GTIN | 4046356540797 |
| Orderkey | 2986711 |
| Catalog page | Page 95 (C-8-2013) |
| Depth (Note) | 114.5 mm |
| Packing unit | 1 pc |
| Width (Note) | 17.5 mm |
| (Dimensions) | ≤ 85 % (On an individual basis, condensation and icing are not permitted) |
| Height (Note) | 99 mm |
| (Output data) | IP54 |
| Country of origin | DE (Germany) |
| pluggable (General) | Yes |
| Custom tariff number | 85364900 |
| Screw thread (General) | M3 |
| Net weight (Output data) | 187 g |
| Relay type (Output data) | Electromechanical relay with forcibly guided contacts in accordance with EN 50205 |
| Contact type (Input data) | 1 enabling current path |
| Stripping length (General) | 7 mm |
| Connection method (General) | Screw connection |
| Housing color (Output data) | yellow |
| Mounting type (Output data) | DIN rail mounting |
| (Standards and Regulations) | For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |
| Contact material (Input data) | AgNi, gold-flashed |
| Designation (Connection data) | IEC 61508 - Low demand |
| Maximum altitude (Dimensions) | ≤ 2000 m (Above sea level) |
| Sq. Total current (Input data) | 25 A2(ITH2= I12+ ... + IN2) |
| Mounting position (Output data) | optional (Observe derating) |
| Degree of protection (Output data) | IP20 |
| Recovery time (Ambient conditions) | 1 s |
| Assembly instructions (Output data) | In rows with zero spacing |
| Inrush current (Ambient conditions) | 200 mA |
| Maximum inrush current (Input data) | 5 A |
| Inrush current, minimum (Input data) | 100 mA |
| Mechanical service life (Input data) | approx. 107cycles |
| Nominal operating mode (Output data) | 100% operating factor |
| Switching capacity min. (Input data) | 1.5 W |
| Weight per Piece (excluding packing) | 187.000 g |
| China RoHS (Standards and Regulations) | Environmentally Friendly Use Period = 50 |
| Maximum switching voltage (Input data) | 250 V AC (125 V DC) |
| Minimum switching voltage (Input data) | 15 V AC/DC |
| Input voltage range (Ambient conditions) | 20.4 V DC ... 26.4 V DC |
| Limiting continuous current (Input data) | 5 A (N/O contact, pay attention to the derating) |
| Conductor cross section AWG max. (General) | 12 |
| Conductor cross section AWG min. (General) | 24 |
| Shock (Safety-related characteristic data) | 15g |
| Typical response time (Ambient conditions) | 30 ms |
| Ambient temperature (operation) (Dimensions) | -20 °C ... 55 °C |
| Conductor cross section solid max. (General) | 2.5 mm² |
| Conductor cross section solid min. (General) | 0.2 mm² |
| Nominal input voltage UN (Ambient conditions) | 24 V DC |
| Utilization restriction (Key Commercial Data) | EMC: class A product, see manufacturer's declaration in the download area |
| Operating voltage display (Ambient conditions) | Green LED (POWER) |
| Safety Integrity Level (SIL) (Connection data) | 3 |
| Conductor cross section flexible max. (General) | 2.5 mm² |
| Conductor cross section flexible min. (General) | 0.2 mm² |
| Designation (Safety-related characteristic data) | Air clearances and creepage distances between the power circuits |
| Typical input current at UN (Ambient conditions) | 75 mA |
| UL, USA/Canada (Safety-related characteristic data) | UL applied for |
| Ambient temperature (storage/transport) (Dimensions) | -40 °C ... 65 °C |
| Degree of pollution (Safety-related characteristic data) | 2 |
| Min. degree of protection of inst. location (Output data) | IP54 |
| Overvoltage category (Safety-related characteristic data) | III |
| Max. permissible humidity (storage/transport) (Dimensions) | ≤ 85 % (Condensation and icing are not permitted based on the average annual temperature) |
| Standards/regulations (Safety-related characteristic data) | DIN EN 50178 |
| Vibration (operation) (Safety-related characteristic data) | 10 Hz ... 150 Hz, 2g |
| Input voltage range in reference to UN (Ambient conditions) | 0.85 ... 1.1 |
| Rated control circuit supply voltage US (Ambient conditions) | |
| Rated insulation voltage (Safety-related characteristic data) | 250 V AC |
| Rated surge voltage/insulation (Safety-related characteristic data) | 6 kV/safe isolation (through protective impedance) |
Technical specifications and performance data