| Parameter | Value |
|---|---|
| GTIN | 4017918911065 |
| Orderkey | 2981020 |
| Catalog page | Page 288 (C-6-2017) |
| Depth (Note) | 114.5 mm |
| Packing unit | 1 pc |
| Width (Note) | 22.5 mm |
| (Input data) | 4 A gL/gG NEOZED (Low demand) |
| Height (Note) | 99 mm |
| (Output data) | IP54 |
| Country of origin | DE (Germany) |
| pluggable (General) | Yes |
| Custom tariff number | 85371098 |
| (Ambient conditions) | Reverse polarity protection |
| Screw thread (General) | M3 |
| Net weight (Output data) | 199.6 g |
| Output fuse (Input data) | 6 A gL/gG NEOZED (High demand) |
| Relay type (Output data) | Electromechanical relay with forcibly guided contacts in accordance with EN 50205 |
| Contact type (Input data) | 2 enabling current paths |
| Category (Connection data) | 4 |
| Stripping length (General) | 7 mm |
| Connection method (General) | Screw connection |
| Housing color (Output data) | yellow |
| Mounting type (Output data) | DIN rail mounting |
| (Standards and Regulations) | For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |
| Contact material (Input data) | AgSnO2, gold-flashed |
| Designation (Connection data) | EN 62061 |
| Maximum altitude (Dimensions) | ≤ 2000 m (Above sea level) |
| Housing material (Output data) | PBT |
| Sq. Total current (Input data) | 72 A2(observe derating) |
| Mounting position (Output data) | On horizontal and vertical DIN rail |
| Stop category (Connection data) | 0 |
| Filter time (Ambient conditions) | max. 3 ms (Test pulse duration) |
| Degree of protection (Output data) | IP20 |
| Recovery time (Ambient conditions) | approx. 1 s |
| Inrush current (Ambient conditions) | 1 A (Δt <10 ms at Us) |
| Maximum inrush current (Input data) | 6 A |
| Status display (Ambient conditions) | Green LED |
| Inrush current, minimum (Input data) | 10 mA |
| Mechanical service life (Input data) | approx. 107cycles |
| Nominal operating mode (Output data) | 100% operating factor |
| Switching capacity min. (Input data) | 0.2 W |
| Weight per Piece (excluding packing) | 199.600 g |
| (Safety-related characteristic data) | Basic insulation 4 kV between all current paths and housing |
| China RoHS (Standards and Regulations) | Environmentally Friendly Use Period = 50 |
| Maximum switching voltage (Input data) | 250 V AC/DC (Observe the load curve) |
| Minimum switching voltage (Input data) | 10 V |
| Protective circuit (Ambient conditions) | Surge protection Suppressor diode, 33 V (A1 - A2, Y2 - A2) |
| Limiting continuous current (Input data) | 6 A (N/O contact/N/C contact, high demand) |
| Performance level (PL) (Connection data) | e |
| Typical release time (Ambient conditions) | 20 ms |
| Conductor cross section AWG max. (General) | 12 |
| Conductor cross section AWG min. (General) | 24 |
| Shock (Safety-related characteristic data) | 15g |
| Typical response time (Ambient conditions) | 60 ms (Automatic/manual start) |
| Ambient temperature (operation) (Dimensions) | -20 °C ... 55 °C |
| Conductor cross section solid max. (General) | 2.5 mm² |
| Conductor cross section solid min. (General) | 0.2 mm² |
| Power consumption at US (Ambient conditions) | 1.2 W |
| Utilization restriction (Key Commercial Data) | 1 |
| Operating voltage display (Ambient conditions) | Green LED |
| Safety Integrity Level (SIL) (Connection data) | 3 |
| Switching capacity (360/h cycles) (Input data) | 5 A (24 V (DC13)) |
| Conductor cross section flexible max. (General) | 2.5 mm² |
| Conductor cross section flexible min. (General) | 0.2 mm² |
| Conformance (Safety-related characteristic data) | CE-compliant |
| Designation (Safety-related characteristic data) | Air clearances and creepage distances between the power circuits |
| Interrupting rating (ohmic load) max. (Input data) | 144 W (24 V DC, τ = 0 ms) |
| Ambient temperature (storage/transport) (Dimensions) | -40 °C ... 70 °C |
| Rated control supply current IS (Ambient conditions) | typ. 50 mA DC |
| Degree of pollution (Safety-related characteristic data) | 2 |
| Maximum interrupting rating (inductive load) (Input data) | 42 W (24 V DC, τ = 40 ms) |
| Min. degree of protection of inst. location (Output data) | IP54 |
| Overvoltage category (Safety-related characteristic data) | III |
| Max. permissible humidity (storage/transport) (Dimensions) | 75 % (on average, 85% infrequently, non-condensing) |
| Standards/regulations (Safety-related characteristic data) | DIN EN 50178/VDE 0160 |
| Vibration (operation) (Safety-related characteristic data) | 10 Hz ... 150 Hz, 2g |
| Max. permissible relative humidity (operation) (Dimensions) | 75 % (on average, 85% infrequently, non-condensing) |
| Rated control circuit supply voltage US (Ambient conditions) | 24 V DC -15 % / +10 % |
| Rated insulation voltage (Safety-related characteristic data) | 250 V |
| Safety Integrity Level Claim Limit (SIL CL) (Connection data) | 3 |
| Rated surge voltage/insulation (Safety-related characteristic data) | 6 kV / Safe isolation, increased insulation |
Technical specifications and performance data
Installation and operation guide