| Parameter | Value |
|---|---|
| GTIN | 4055626280233 |
| Orderkey | 2702663 |
| (Drawings) | |
| Catalog page | Page 250 (C-6-2019) |
| Depth (Note) | 102.5 mm |
| Packing unit | 1 pc |
| Width (Note) | 6.8 mm |
| Height (Note) | 93.1 mm |
| (Power supply) | 4 A gL/gG (for low-demand applications) |
| Torque (General) | 0.5 Nm ... 0.6 Nm |
| Country of origin | DE (Germany) |
| ETIM 5.0 (eCl@ss) | EC001449 |
| ETIM 6.0 (eCl@ss) | EC001449 |
| ETIM 7.0 (eCl@ss) | EC001449 |
| Net weight (Times) | 70.162 g |
| Relay type (Times) | Electromechanical relay with forcibly guided contacts in accordance with IEC/EN 61810-3 (EN 50205) |
| pluggable (General) | no |
| Custom tariff number | 85364900 |
| (Ambient conditions) | > 1 s (at A1-A2; high test pulse rate) |
| Housing color (Times) | yellow |
| Mounting type (Times) | DIN rail mounting |
| Screw thread (General) | M3 |
| Status display (Times) | 1 x green LED |
| Block diagram (Drawings) | |
| Housing material (Times) | PBT |
| Mounting position (Times) | vertical or horizontal |
| Output fuse (Power supply) | 6 A gL/gG |
| Output name (Power supply) | Enabling current path |
| Stripping length (General) | 12 mm |
| Connection method (General) | Screw connection |
| Contact type (Power supply) | 1 enabling current path |
| (Standards and Regulations) | For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |
| Degree of protection (Times) | IP20 |
| eCl@ss 5.1 (Classifications) | 27371901 |
| eCl@ss 6.0 (Classifications) | 27371800 |
| eCl@ss 7.0 (Classifications) | 27371819 |
| eCl@ss 8.0 (Classifications) | 27371819 |
| eCl@ss 9.0 (Classifications) | 27371819 |
| Assembly instructions (Times) | See derating curve |
| Designation (Connection data) | EN 50156-2 |
| Inrush current (Power supply) | min. 3 mA |
| Maximum altitude (Dimensions) | ≤ 2000 m (Above sea level) |
| Nominal operating mode (Times) | 100% operating factor |
| Contact material (Power supply) | AgSnO2 |
| Stop category (Connection data) | 0 |
| Filter time (Ambient conditions) | max. 2 ms (at A1-A2 in the event of voltage dips at Us) |
| Number of outputs (Power supply) | 1 (safety-related N/O contacts: 13/14) |
| Sq. Total current (Power supply) | 36 A2(observe derating) |
| Switching voltage (Power supply) | min. 12 V AC/DC |
| Operating voltage display (Times) | 1 x yellow LED |
| Output description (Power supply) | 2 N/O contacts in series, without delay, floating |
| Switching capacity (Power supply) | min. 60 mW |
| Switching frequency (Power supply) | max. 1 Hz |
| Utilization restriction (Drawings) | EMC: class A product, see manufacturer's declaration in the download area |
| Inrush current (Ambient conditions) | typ. 120 mA (Δt <10 ms at Us) |
| Weight per Piece (excluding packing) | 160.000 g |
| (Safety-related characteristic data) | Class I, Div. 2, Groups A, B, C, D, T4 |
| China RoHS (Standards and Regulations) | Environmentally Friendly Use Period = 50 |
| Mechanical service life (Power supply) | 10x 106cycles |
| REACh SVHC (Standards and Regulations) | Lead 7439-92-1 |
| (Relay outputs: enabling current path) | max. 100 mA |
| Protective circuit (Ambient conditions) | Serial protection against polarity reversal 35 V suppressor diode (A1-A2) |
| ATEX (Safety-related characteristic data) | II 3 G Ex nA nC IIC T4 Gc |
| Conductor cross section AWG max. (General) | 12 |
| Conductor cross section AWG min. (General) | 26 |
| IECEx (Safety-related characteristic data) | Ex nA nC IIC T4 Gc |
| Limiting continuous current (Power supply) | 6 A (High demand) |
| Shock (Safety-related characteristic data) | 15g |
| Ambient temperature (operation) (Dimensions) | -40 °C ... 70 °C (observe derating) |
| Conductor cross section solid max. (General) | 2.5 mm² |
| Conductor cross section solid min. (General) | 0.2 mm² |
| Power consumption at US (Ambient conditions) | typ. 1.08 W |
| Safety Integrity Level (SIL) (Connection data) | 3 (Reference IEC 61508) |
| Conductor cross section flexible max. (General) | 2.5 mm² |
| Conductor cross section flexible min. (General) | 0.2 mm² |
| Conformance (Safety-related characteristic data) | CE-compliant |
| Designation (Safety-related characteristic data) | Air clearances and creepage distances between the power circuits |
| Output fuse (Relay outputs: enabling current path) | 150 mA Fast-blow |
| Output name (Relay outputs: enabling current path) | Confirmation current path |
| Contact type (Relay outputs: enabling current path) | 1 confirmation current path |
| Min. degree of protection of inst. location (Times) | IP54 |
| UL, USA/Canada (Safety-related characteristic data) | cULus |
| Ambient temperature (storage/transport) (Dimensions) | -40 °C ... 85 °C |
| Rated control supply current IS (Ambient conditions) | typ. 45 mA |
| Inrush current (Relay outputs: enabling current path) | min. 1 mA |
| Contact material (Relay outputs: enabling current path) | AgCuNi, + Au |
| Degree of pollution (Safety-related characteristic data) | 2 |
| Number of outputs (Relay outputs: enabling current path) | 1 (safety-related N/C contacts: 21/22) |
| Switching voltage (Relay outputs: enabling current path) | min. 5 V DC |
| Output description (Relay outputs: enabling current path) | 2 N/C contacts in series, without delay, floating |
| Overvoltage category (Safety-related characteristic data) | III |
| Switching capacity (Relay outputs: enabling current path) | min. 20 mW |
| Max. permissible humidity (storage/transport) (Dimensions) | 75 % (on average, 85% infrequently, non-condensing) |
| Standards/regulations (Safety-related characteristic data) | DIN EN 50178, EN 60079-15 |
| Switching frequency (Relay outputs: enabling current path) | max. 1 Hz |
| Vibration (operation) (Safety-related characteristic data) | 10 Hz ... 150 Hz, 2g |
| Max. permissible relative humidity (operation) (Dimensions) | 75 % (on average, 85% infrequently, non-condensing) |
| Rated control circuit supply voltage US (Ambient conditions) | 24 V DC -20 % / +25 % (A1/A2) |
| Switching capacity according to IEC 60947-5-1 (Power supply) | 4 A (24 V (DC13)) |
| Rated insulation voltage (Safety-related characteristic data) | 250 V AC |
| Mechanical service life (Relay outputs: enabling current path) | 10x 106cycles |
| Environmental simulation test (Safety-related characteristic data) | ISA-S71.04 (G3) |
| Limiting continuous current (Relay outputs: enabling current path) | 100 mA |
| Rated surge voltage/insulation (Safety-related characteristic data) | Basic insulation 4 kV between all current paths and housing |
| Recovery time (Relay outputs: return current/signaling current path) | 500 ms |
| Typical pickup time at US (Relay outputs: return current/signaling current path) | < 70 ms (with Uswhen controlled via A1) |
| Typical release time at US (Relay outputs: return current/signaling current path) | < 30 ms (when controlled via A1) |
Technical specifications and performance data
Installation and operation guide