Service time: Monday to Friday 9:00-18:00
PSR-PS21-1NO-1NC-24DC-SC - PSR-PS21-1NO-1NC-24DC-SC 2700357 PHOENIX CONTACT Coupling relay
In Stock Hot Product

PSR-PS21-1NO-1NC-24DC-SC

PSR-PS21-1NO-1NC-24DC-SC 2700357 PHOENIX CONTACT Coupling relay

$0.00USD
3518 in stock
Key Specifications
GTIN:4046356912907
Orderkey:2700357
Catalog page:Page 281 (C-6-2017)
Depth (Note):102.5 mm
Supplier Information
Products: 0
Usually ships within 2-3 business days
Quality Guaranteed
Fast Shipping
Technical Support

Technical Specifications

ParameterValue
GTIN4046356912907
Orderkey2700357
Catalog pagePage 281 (C-6-2017)
Depth (Note)102.5 mm
Packing unit1 pc
Width (Note)6.8 mm
Height (Note)93.1 mm
(Power supply)4 A gL/gG (for low-demand applications)
Torque (General)0.5 Nm ... 0.6 Nm
Country of originDE (Germany)
Indication (Times)1 x red LED
Net weight (Times)136.4 g
Relay type (Times)Electromechanical relay with forcibly guided contacts in accordance with IEC/EN 61810-3 (EN 50205)
pluggable (General)no
Custom tariff number85364900
(Ambient conditions)≥ 100 ms (at A1-A2; test pulse rate)
Housing color (Times)yellow
Mounting type (Times)DIN rail mounting
Screw thread (General)M3
Status display (Times)2 x green LEDs
Housing material (Times)PBT
Mounting position (Times)vertical, horizontal, with front of module upward
Output fuse (Power supply)6 A gL/gG
Output name (Power supply)Enabling current path
Stripping length (General)12 mm
Connection method (General)Screw connection
Contact type (Power supply)1 enabling current path
(Standards and Regulations)For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”
Degree of protection (Times)IP20
Assembly instructions (Times)See derating curve
Designation (Connection data)EN 50156
Inrush current (Power supply)min. 3 mA
Maximum altitude (Dimensions)≤ 2000 m (Above sea level)
Recovery time (Alarm outputs)500 ms
Nominal operating mode (Times)100% operating factor
Contact material (Power supply)AgSnO2
Stop category (Connection data)0
Filter time (Ambient conditions)max. 2 ms (at A1-A2; test pulse width)
Number of outputs (Power supply)1 (safety-related N/O contacts: 13/14)
Sq. Total current (Power supply)36 A2(observe derating)
Switching voltage (Power supply)min. 12 V AC/DC
Operating voltage display (Times)1 x yellow LED
Output description (Power supply)1 N/O contact, without delay, floating
Switching capacity (Power supply)min. 60 mW
Switching frequency (Power supply)max. 1 Hz
Inrush current (Ambient conditions)typ. 400 mA (Δt s)
Weight per Piece (excluding packing)136.400 g
(Safety-related characteristic data)Class I, Div. 2, Groups A, B, C, D, T4
China RoHS (Standards and Regulations)Environmentally Friendly Use Period = 50
Mechanical service life (Power supply)10x 106cycles
(Relay outputs: enabling current path)max. 100 mA
GL (Safety-related characteristic data)C, EMC2
Protective circuit (Ambient conditions)Serial protection against polarity reversal Suppressor diode 33 V (A1/A2), 38 V (21/A2)
Input current at UD (Ambient conditions)6 mA (at 21-A2 for UD; depending on load + 100 mA at M1 and 22)
Inrush current at UD (Ambient conditions)typ. 2.5 A (Δt D)
Typical pickup time at US (Alarm outputs)< 100 ms (with Uswhen controlled via A1)
Conductor cross section AWG max. (General)12
Conductor cross section AWG min. (General)26
Limiting continuous current (Power supply)6 A (High demand)
Shock (Safety-related characteristic data)15g
Typical release time at US (Alarm outputs)< 35 ms (when controlled via A1)
Ambient temperature (operation) (Dimensions)-40 °C ... 65 °C (observe derating)
Conductor cross section solid max. (General)2.5 mm²
Conductor cross section solid min. (General)0.2 mm²
Power consumption at US (Ambient conditions)typ. 1.08 W
Utilization restriction (Key Commercial Data)EMC: class A product, see manufacturer's declaration in the download area
Safety Integrity Level (SIL) (Connection data)2
Conductor cross section flexible max. (General)2.5 mm²
Conductor cross section flexible min. (General)0.2 mm²
Conformance (Safety-related characteristic data)CE-compliant
Designation (Safety-related characteristic data)Air clearances and creepage distances between the power circuits
Diagnostic supply voltage UD (Ambient conditions)24 V DC -15 % / +10 % (21/A2)
Output fuse (Relay outputs: enabling current path)150 mA Fast-blow
Output name (Relay outputs: enabling current path)Confirmation current path
Contact type (Relay outputs: enabling current path)1 confirmation current path
Min. degree of protection of inst. location (Times)IP54
UL, USA/Canada (Safety-related characteristic data)cULus
Ambient temperature (storage/transport) (Dimensions)-40 °C ... 85 °C
Rated control supply current IS (Ambient conditions)typ. 45 mA
Inrush current (Relay outputs: enabling current path)min. 1 mA
Contact material (Relay outputs: enabling current path)AgCuNi, + Au
Degree of pollution (Safety-related characteristic data)2
Number of outputs (Relay outputs: enabling current path)1 (safety-related N/C contacts: 21/22)
Switching voltage (Relay outputs: enabling current path)min. 20.4 V DC
Output description (Relay outputs: enabling current path)1 N/C contact, without delay, not floating (reference ground: A2)
Overvoltage category (Safety-related characteristic data)III
Switching capacity (Relay outputs: enabling current path)min. 20 mW
Max. permissible humidity (storage/transport) (Dimensions)75 % (on average, 85% infrequently, non-condensing)
Standards/regulations (Safety-related characteristic data)DIN EN 50178, EN 60079-15
Switching frequency (Relay outputs: enabling current path)max. 1 Hz
Vibration (operation) (Safety-related characteristic data)10 Hz ...150 Hz, 2g
Max. permissible relative humidity (operation) (Dimensions)75 % (on average, 85% infrequently, non-condensing)
Rated control circuit supply voltage US (Ambient conditions)24 V DC -15 % / +10 % (A1/A2)
Switching capacity according to IEC 60947-5-1 (Power supply)4 A (24 V (DC13))
Rated insulation voltage (Safety-related characteristic data)250 V AC
Current (Relay outputs: return current/signaling current path)max. 100 mA
Mechanical service life (Relay outputs: enabling current path)10x 106cycles
Voltage (Relay outputs: return current/signaling current path)approx. 22 V DC (UD- 2 V)
Environmental simulation test (Safety-related characteristic data)ISA-S71.04 (G3)
Limiting continuous current (Relay outputs: enabling current path)100 mA
Output fuse (Relay outputs: return current/signaling current path)150 mA fast blow
Rated surge voltage/insulation (Safety-related characteristic data)Safe isolation, 6 kV reinforced insulation from control circuit, start circuit, confirmation current path, signal output to the enabling current path; 4 kV/basic insulation between all current paths and housing
Number of outputs (Relay outputs: return current/signaling current path)1 (non-safety-related)
Output description (Relay outputs: return current/signaling current path)PNP
Maximum inrush current (Relay outputs: return current/signaling current path)500 mA (Δt = 1 ms at Us)
Short-circuit protection (Relay outputs: return current/signaling current path)no

Product Description

SIL 2 coupling relay for high and low demand applications, couples digital output signals to the periphery, 1 trip circuit, 1 acknowledgment circuit, 1 digital warning output, Safe-State-Off applicati
Key Features
  • Industrial grade quality
  • RoHS compliant
  • CE certified
  • 1-year warranty

Product Documents

Datasheet

Technical specifications and performance data

User Manual

Installation and operation guide

Top