Service time: Monday to Friday 9:00-18:00
PSR-ME30-4NO-1NC-24DC-SC - PSR-ME30-4NO-1NC-24DC-SC 1397656 PHOENIX CONTACT Safety relay as contact extension, 4 enabling circuits, 1 f..
In Stock Hot Product

PSR-ME30-4NO-1NC-24DC-SC

PSR-ME30-4NO-1NC-24DC-SC 1397656 PHOENIX CONTACT Safety relay as contact extension, 4 enabling circuits, 1 f..

$0.00USD
4684 in stock
Key Specifications
:max. 250 V AC
Depth:114.5 mm
Shock:15g
Width:22.5 mm
Supplier Information
Products: 0
Usually ships within 2-3 business days
Quality Guaranteed
Fast Shipping
Technical Support

Technical Specifications

ParameterValue
max. 250 V AC
Depth114.5 mm
Shock15g
Width22.5 mm
Height112.2 mm
Category3
pluggableyes
Relay typeElectromechanical relay with force-guided contacts in accordance with IEC/EN 61810-3
ApplicationExtension module
Output fuse10 A gL/gG
Product typeSafety relays
Screw threadM3
Mounting typeDIN rail mounting
Set comprises1397657 PSR-ME30-4NO-1NC-24DC-SC-SET35
Stop category0
IdentificationCE-compliant
Inrush currenttyp. 130 mA (Δt = 800 ms)
Product familyPSRclassic
Contact materialAgSnO2
Housing materialPolyamide
Maximum altitude≤ 2000 m (Above sea level)
Number of inputs1
Stripping length7 mm
Connection methodScrew connection
Mounting positionvertical or horizontal
Number of outputs4
Sq. Total current72 A2(observe derating)
Switching voltagemin. 10 V AC/DC
Tightening torque0.5 Nm ... 0.6 Nm
Output description2 N/O contacts each in series, safety-related, floating
Protective circuitSuppressor diode
Switching capacitymin. 100 mW
Current consumptiontyp. 67 mA
Switching frequencymax. 0.5 Hz
Degree of protectionIP20
Typical release time20 ms (when requested via K1/K2)
Assembly instructionsSee derating curve
Standards/regulationsDIN EN 60947-1
Vibration (operation)10 Hz ... 150 Hz, 2g
Contact switching type4 enabling current paths
Nominal operating mode100% operating factor
Performance level (PL)d
Mechanical service lifeapprox. 107cycles
Description of the inputsafety-related
Rated insulation voltage250 V
Operating voltage display1 x green LED
Typ. starting time with Us20 ms (when controlled via K1/K2)
Conductor cross-section AWG24 ... 12
Limiting continuous current6 A (Observe derating and load limit curve)
Safety Integrity Level (SIL)2
Conductor cross section rigid0.2 mm² ... 2.5 mm²
Input voltage range "1" signal20.4 V ... 26.4 V
Rated surge voltage/insulationSee section “Insulation coordination”
Ambient temperature (operation)-20 °C ... 55 °C (observe derating)
Conductor cross section flexible0.2 mm² ... 2.5 mm²
Ambient temperature (storage/transport)-40 °C ... 70 °C
Min. degree of protection of inst. locationIP54
Max. permissible humidity (storage/transport)75 % (on average, 85% infrequently, non-condensing)
Max. permissible overall conductor resistance50 Ω
Max. permissible relative humidity (operation)75 % (on average, 85% infrequently, non-condensing)
Maximum power dissipation for nominal condition16.4 W (UK1/K2= 26.4 V, IL² = 72 A², PTotal max= 2 W + 14.4 W)
Switching capacity in accordance with IEC 60947-5-15 A (AC15)

Product Description

Safety Relay
Key Features
  • Industrial grade quality
  • RoHS compliant
  • CE certified
  • 1-year warranty

Product Documents

Datasheet

Technical specifications and performance data

User Manual

Installation and operation guide

Top