| Parameter | Value |
|---|---|
| GTIN | 4055626145488 |
| Orderkey | 2702383 |
| Catalog page | Page 259 (C-6-2017) |
| Depth (Note) | 114.5 mm |
| Packing unit | 1 pc |
| Width (Note) | 17.5 mm |
| Height (Note) | 116.6 mm |
| (Power supply) | 6 A gL/gG (for low-demand applications) |
| Country of origin | DE (Germany) |
| Net weight (Times) | 210.3 g |
| Relay type (Times) | Electromechanical relay with forcibly guided contacts in accordance with EN 50205 |
| pluggable (General) | Yes |
| Custom tariff number | 85371098 |
| (Ambient conditions) | Reverse polarity protection Universal diode |
| Housing color (Times) | yellow |
| Mounting type (Times) | DIN rail mounting |
| Status display (Times) | 2 x green LEDs |
| Mounting position (Times) | vertical or horizontal |
| Category (Connection data) | 4 (In conjunction with suitable evaluating device) |
| Output fuse (Power supply) | 10 A gL/gG |
| Output name (Power supply) | Enabling current path |
| Stripping length (General) | 8 mm |
| Connection method (General) | Spring-cage connection |
| Contact type (Power supply) | 5 enabling current paths |
| (Standards and Regulations) | No hazardous substances above threshold values |
| Degree of protection (Times) | IP20 |
| Assembly instructions (Times) | See derating curve |
| Designation (Connection data) | EN 62061 |
| Inrush current (Power supply) | min. 10 mA |
| Maximum altitude (Dimensions) | max. 2000 m (Above sea level) |
| Recovery time (Alarm outputs) | < 100 ms |
| Nominal operating mode (Times) | 100% operating factor |
| Contact material (Power supply) | AgSnO2 |
| Stop category (Connection data) | 0 |
| Filter time (Ambient conditions) | 4 ms (at A1 in the event of voltage dips at Us) |
| Number of outputs (Power supply) | 5 (undelayed) |
| Sq. Total current (Power supply) | 64 A2(observe derating) |
| Switching voltage (Power supply) | min. 5 V AC/DC |
| Output description (Power supply) | safety-related N/O contacts |
| Switching capacity (Power supply) | min. 50 mW |
| Switching frequency (Power supply) | 0.5 Hz |
| Inrush current (Ambient conditions) | 30 mA (Δt = 7 ms at Us) |
| Weight per Piece (excluding packing) | 210.300 g |
| (Safety-related characteristic data) | Safe isolation, reinforced insulation 6 kV between input circuits and enabling current paths 33/34, 43/44, and 63/64 |
| China RoHS (Standards and Regulations) | Environmentally friendly use period: unlimited = EFUP-e |
| Mechanical service life (Power supply) | 10x 106cycles |
| (Relay outputs: enabling current path) | min. 10 mA |
| Protective circuit (Ambient conditions) | Surge protection Suppressor diode |
| Performance level (PL) (Connection data) | e (In conjunction with suitable evaluating device) |
| Typical pickup time at US (Alarm outputs) | < 50 ms (when controlled via A1/A2) |
| Conductor cross section AWG max. (General) | 16 |
| Conductor cross section AWG min. (General) | 24 |
| Limiting continuous current (Power supply) | 6 A (observe derating) |
| Shock (Safety-related characteristic data) | 15g (In the event of stress caused by shock, contact reactions are possible for up to 6 ms.) |
| Typical release time at US (Alarm outputs) | < 25 ms (when controlled via A1/A2) |
| Typical response time at US (Alarm outputs) | < 50 ms |
| Ambient temperature (operation) (Dimensions) | -20 °C ... 60 °C (observe derating) |
| Conductor cross section solid max. (General) | 1.5 mm² |
| Conductor cross section solid min. (General) | 0.2 mm² |
| Power consumption at US (Ambient conditions) | typ. 1.92 W |
| Utilization restriction (Key Commercial Data) | EMC: class A product, see manufacturer's declaration in the download area |
| Safety Integrity Level (SIL) (Connection data) | 3 (In conjunction with suitable evaluating device) |
| Conductor cross section flexible max. (General) | 1.5 mm² |
| Conductor cross section flexible min. (General) | 0.2 mm² |
| Conformance (Safety-related characteristic data) | CE-compliant |
| Designation (Safety-related characteristic data) | Air clearances and creepage distances between the power circuits |
| Output name (Relay outputs: enabling current path) | Confirmation current path |
| Contact type (Relay outputs: enabling current path) | 1 confirmation current path |
| Min. degree of protection of inst. location (Times) | IP54 |
| Ambient temperature (storage/transport) (Dimensions) | -40 °C ... 80 °C |
| Rated control supply current IS (Ambient conditions) | typ. 80 mA |
| Inrush current (Relay outputs: enabling current path) | max. 100 mA |
| Contact material (Relay outputs: enabling current path) | AgSnO |
| Degree of pollution (Safety-related characteristic data) | 2 |
| Number of outputs (Relay outputs: enabling current path) | 1 (undelayed) |
| Switching voltage (Relay outputs: enabling current path) | min. 5 V AC/DC |
| Output description (Relay outputs: enabling current path) | Safety-related N/C contacts |
| Overvoltage category (Safety-related characteristic data) | III |
| Switching capacity (Relay outputs: enabling current path) | min. 50 mW |
| Max. permissible humidity (storage/transport) (Dimensions) | 75 % (on average, 85% infrequently, non-condensing) |
| Standards/regulations (Safety-related characteristic data) | DIN EN 50178 |
| Switching frequency (Relay outputs: enabling current path) | max. 0.5 Hz |
| Vibration (operation) (Safety-related characteristic data) | 10 Hz ...150 Hz, 2g (In the event of stress caused by vibration, contact reactions are possible for up to 1 ms.) |
| Max. permissible relative humidity (operation) (Dimensions) | 75 % (on average, 85% infrequently, non-condensing) |
| Rated control circuit supply voltage US (Ambient conditions) | 24 V DC -20 % / +25 % |
| Rated insulation voltage (Safety-related characteristic data) | 250 V AC |
| Safety Integrity Level Claim Limit (SIL CL) (Connection data) | 3 (In conjunction with suitable evaluating device) |
| Current (Relay outputs: return current/signaling current path) | max. 100 mA |
| Mechanical service life (Relay outputs: enabling current path) | 10x 106cycles |
| Voltage (Relay outputs: return current/signaling current path) | typ. 23 V DC (US- 1 V) |
| Limiting continuous current (Relay outputs: enabling current path) | 100 mA |
| Rated surge voltage/insulation (Safety-related characteristic data) | Basic insulation 4 kV between all current paths |
| Number of outputs (Relay outputs: return current/signaling current path) | 1 (digital, PNP) |
| Output description (Relay outputs: return current/signaling current path) | non-safety-related |
| Maximum inrush current (Relay outputs: return current/signaling current path) | 500 mA (Δt = 1 ms at Us) |
| Short-circuit protection (Relay outputs: return current/signaling current path) | Yes |
Technical specifications and performance data
Installation and operation guide