| Parameter | Value |
|---|---|
| 250 V AC | |
| Depth | 114.5 mm |
| Shock | 15g (In the event of stress caused by shock, contact reactions are possible for up to 6 ms.) |
| Width | 17.5 mm |
| Height | 112.2 mm |
| Current | max. 100 mA |
| Voltage | typ. 23 V DC (US- 1 V) |
| Category | 4 (In conjunction with suitable evaluating device) |
| pluggable | yes |
| Relay type | Electromechanical relay with force-guided contacts in accordance with IEC/EN 61810-3 |
| Application | Extension module |
| Designation | A1/A2 |
| Filter time | 4 ms (at A1 in the event of voltage dips at Us) |
| Output fuse | 10 A gL/gG |
| Product type | Safety relays |
| Screw thread | M3 |
| Assembly note | See derating curve |
| Mounting type | DIN rail mounting |
| Recovery time | < 100 ms |
| Stop category | 0 |
| Identification | CE-compliant |
| Inrush current | typ. 125 mA (Δt = 7 ms at Us) |
| Product family | PSRmini |
| Status display | 2 x LED (green) |
| Color (Housing) | yellow (RAL 1018) |
| Article revision | 06 |
| Contact material | AgSnO2 |
| Housing material | Polyamide |
| Maximum altitude | max. 2000 m (Above sea level) |
| Stripping length | 7 mm |
| Connection method | Screw connection |
| Mounting position | vertical or horizontal |
| Number of outputs | 5 (undelayed) |
| Sq. Total current | 64 A2(observe derating) |
| Switching voltage | min. 5 V AC/DC |
| Output description | safety-related N/O contacts |
| Protective circuit | Surge protection; Suppressor diode |
| Switching capacity | min. 50 mW (5 V / 10 mA) |
| Note on application | Only for industrial use |
| Switching frequency | max. 0.5 Hz |
| Degree of protection | IP20 |
| Typical release time | < 25 ms (when controlled via A1/A2) |
| Standards/regulations | EN 60947-1 |
| Typical response time | < 50 ms (Monitored/manual and auto-start) |
| Vibration (operation) | 10 Hz ... 150 Hz, 2g (In the event of stress caused by vibration, contact reactions are possible for up to 1 ms.) |
| Contact switching type | 5 enabling current paths |
| Maximum inrush current | 500 mA (Δt = 1 ms at Us) |
| Nominal operating mode | 100% operating factor |
| Performance level (PL) | e (In conjunction with suitable evaluating device) |
| Mechanical service life | 10x 106cycles |
| Power consumption at US | typ. 1.92 W |
| Rated insulation voltage | 250 V AC |
| Short-circuit protection | Yes |
| Typ. starting time with Us | < 50 ms (when controlled via A1/A2) |
| Conductor cross-section AWG | 24 ... 12 |
| Limiting continuous current | 6 A (observe derating) |
| Safety Integrity Level (SIL) | 3 (In conjunction with suitable evaluating device) |
| Conductor cross section rigid | 0.2 mm² ... 2.5 mm² |
| Rated surge voltage/insulation | |
| Ambient temperature (operation) | -20 °C ... 60 °C (observe derating) |
| Rated control supply current IS | typ. 80 mA |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Ambient temperature (storage/transport) | -40 °C ... 80 °C |
| Rated control circuit supply voltage US | 19.2 V DC ... 30 V DC |
| Min. degree of protection of inst. location | IP54 |
| Max. permissible humidity (storage/transport) | 75 % (on average, 85% infrequently, non-condensing) |
| Max. permissible relative humidity (operation) | 75 % (on average, 85% infrequently, non-condensing) |
| Maximum power dissipation for nominal condition | 15.2 W (at US= 30 V, IL² = 64 A²) |
| Switching capacity in accordance with IEC 60947-5-1 | 3 A (24 V (DC13)) |
Technical specifications and performance data
Installation and operation guide