| Parameter | Value |
|---|---|
| GTIN | 4046356912679 |
| Orderkey | 2700564 |
| Catalog page | Page 256 (C-6-2017) |
| Depth (Note) | 114.5 mm |
| Packing unit | 1 pc |
| Width (Note) | 12.5 mm |
| Height (Note) | 116.6 mm |
| (Power supply) | Test pulse rate = 5 x Test pulse width |
| (Alarm outputs) | < 175 ms (manual, monitored start) |
| (Digital inputs) | 4 A gL/gG (for low-demand applications) |
| Country of origin | DE (Germany) |
| Net weight (Times) | 177.4 g |
| Relay type (Times) | Electromechanical relay with forcibly guided contacts in accordance with IEC/EN 61810-3 (EN 50205) |
| pluggable (General) | Yes |
| Custom tariff number | 85371098 |
| (Ambient conditions) | Protection against polarity reversal for rated control circuit supply voltage |
| Housing color (Times) | yellow |
| Mounting type (Times) | DIN rail mounting |
| Status display (Times) | 3 x green LED |
| Housing material (Times) | PBT |
| Mounting position (Times) | vertical or horizontal |
| Category (Connection data) | 4 |
| Filter time (Power supply) | max. 1.5 ms (at S12, S13; test pulse width) |
| Stripping length (General) | 8 mm |
| Connection method (General) | Spring-cage connection |
| (Standards and Regulations) | No hazardous substances above threshold values |
| Degree of protection (Times) | IP20 |
| Output fuse (Digital inputs) | 6 A gL/gG (N/O contact) |
| Output name (Digital inputs) | Enabling current path |
| Assembly instructions (Times) | See derating curve |
| Contact type (Digital inputs) | 3 enabling current paths |
| Designation (Connection data) | EN 62061 |
| Inrush current (Power supply) | < 20 mA (with Us/Ixto S12) |
| Maximum altitude (Dimensions) | ≤ 2000 m (Above sea level) |
| Recovery time (Alarm outputs) | < 500 ms |
| Nominal operating mode (Times) | 100% operating factor |
| Inrush current (Digital inputs) | min. 3 mA |
| Stop category (Connection data) | 0 |
| Filter time (Ambient conditions) | 1 ms (at A1 in the event of voltage dips at Us) |
| Contact material (Digital inputs) | AgSnO2 |
| Operating voltage display (Times) | 1 x green LED |
| Current consumption (Power supply) | < 5 mA (with Us/Ixto S12) |
| Number of outputs (Digital inputs) | 3 (undelayed) |
| Sq. Total current (Digital inputs) | 48 A2(observe derating) |
| Switching voltage (Digital inputs) | min. 12 V AC/DC |
| Inrush current (Ambient conditions) | 5 A (Δt = 200 µs at Us) |
| Output description (Digital inputs) | safety-related N/O contacts |
| Switching capacity (Digital inputs) | min. 60 mW |
| Switching frequency (Digital inputs) | 0.5 Hz |
| Weight per Piece (excluding packing) | 177.400 g |
| (Safety-related characteristic data) | 250 V AC |
| China RoHS (Standards and Regulations) | Environmentally friendly use period: unlimited = EFUP-e |
| REACh SVHC (Standards and Regulations) | Lead 7439-92-1 |
| Protective circuit (Ambient conditions) | Surge protection Suppressor diode |
| Mechanical service life (Digital inputs) | 10x 106cycles |
| Performance level (PL) (Connection data) | e (4 A DC13; 5 A AC15; 8760 switching cycles/year) |
| Typical pickup time at US (Alarm outputs) | < 250 ms (when controlled via A1) |
| Conductor cross section AWG max. (General) | 16 |
| Conductor cross section AWG min. (General) | 24 |
| Shock (Safety-related characteristic data) | 15g |
| Typical release time at US (Alarm outputs) | < 20 ms (when controlled via A1 or S12 and S13.) |
| Typical response time at US (Alarm outputs) | < 175 ms (automatic start) |
| Ambient temperature (operation) (Dimensions) | -40 °C ... 55 °C (observe derating) |
| Conductor cross section solid max. (General) | 1.5 mm² |
| Conductor cross section solid min. (General) | 0.2 mm² |
| Limiting continuous current (Digital inputs) | 6 A (observe derating) |
| Power consumption at US (Ambient conditions) | typ. 1.92 W |
| Input current range "0" signal (Power supply) | 0 mA ... 2 mA (for safe Off; at S12) |
| Input voltage range "0" signal (Power supply) | 0 V DC ... 5 V DC (for safe Off; at S12) |
| Utilization restriction (Key Commercial Data) | 1 |
| Current (Relay outputs: enabling current path) | max. 100 mA |
| Safety Integrity Level (SIL) (Connection data) | 3 |
| Voltage (Relay outputs: enabling current path) | 22 V DC (Us- 2 V) |
| Conductor cross section flexible max. (General) | 1.5 mm² |
| Conductor cross section flexible min. (General) | 0.2 mm² |
| Designation (Safety-related characteristic data) | Air clearances and creepage distances between the power circuits |
| Min. degree of protection of inst. location (Times) | IP54 |
| Ambient temperature (storage/transport) (Dimensions) | -40 °C ... 85 °C |
| Rated control supply current IS (Ambient conditions) | typ. 80 mA |
| Degree of pollution (Safety-related characteristic data) | 2 |
| Number of outputs (Relay outputs: enabling current path) | 1 (digital, PNP) |
| Output description (Relay outputs: enabling current path) | non-safety-related |
| Overvoltage category (Safety-related characteristic data) | III |
| Max. permissible humidity (storage/transport) (Dimensions) | 75 % (on average, 85% infrequently, non-condensing) |
| Standards/regulations (Safety-related characteristic data) | DIN EN 50178 |
| Vibration (operation) (Safety-related characteristic data) | 10 Hz ... 150 Hz, 2g |
| Voltage at input/start and feedback circuit (Power supply) | 24 V DC -15 % / +10 % |
| Max. permissible relative humidity (operation) (Dimensions) | 75 % (on average, 85% infrequently, non-condensing) |
| Max. permissible overall conductor resistance (Power supply) | 150 Ω |
| Rated control circuit supply voltage US (Ambient conditions) | 24 V DC -15 % / +10 % |
| Maximum inrush current (Relay outputs: enabling current path) | 500 mA (Δt = 1 ms at Us) |
| Rated insulation voltage (Safety-related characteristic data) | 250 V AC |
| Safety Integrity Level Claim Limit (SIL CL) (Connection data) | 3 |
| Short-circuit protection (Relay outputs: enabling current path) | no |
| Rated surge voltage/insulation (Safety-related characteristic data) | Safe isolation, reinforced insulation 6 kV between input circuit and enabling current path (13/14) and enabling current path (23/24) and enabling current path (33/34)Basic insulation 4 kV between all current paths and housing |