| Parameter | Value |
|---|---|
| GTIN | 4055626482712 |
| Orderkey | 1009832 |
| (Drawings) | |
| Catalog page | Page 223 (C-6-2019) |
| Depth (Note) | 114.5 mm |
| Packing unit | 1 pc |
| Width (Note) | 22.5 mm |
| Height (Note) | 117.5 mm |
| (Power supply) | typ. 34 µA (Typically with USat S35) |
| (Alarm outputs) | 60 ms (when controlled via A1) |
| (Digital inputs) | 4 A gL/gG (for low-demand applications) |
| Country of origin | DE (Germany) |
| ETIM 5.0 (eCl@ss) | EC001449 |
| ETIM 6.0 (eCl@ss) | EC001449 |
| ETIM 7.0 (eCl@ss) | EC001449 |
| Net weight (Times) | 169.38 g |
| Relay type (Times) | Electromechanical relay with forcibly guided contacts in accordance with EN 50205 |
| pluggable (General) | no |
| Custom tariff number | 85371098 |
| Housing color (Times) | yellow |
| Mounting type (Times) | DIN rail mounting |
| Status display (Times) | 4 x green LEDs |
| Housing material (Times) | PBT |
| Input name (Power supply) | Start circuit |
| Mounting position (Times) | vertical or horizontal |
| Category (Connection data) | 4 (5 A DC13; 5 A AC15; 8760 switching cycles/year) |
| Filter time (Power supply) | 2 ms (At S10, S12, S13; test pulse width of low test pulses) |
| Stripping length (General) | 10 mm |
| Connection method (General) | Push-in connection |
| Degree of protection (Times) | IP20 |
| Output fuse (Digital inputs) | 10 A gL/gG |
| Output name (Digital inputs) | Enabling current path |
| Restart time (Alarm outputs) | < 1 s (Boot time) |
| eCl@ss 8.0 (Classifications) | 27371819 |
| eCl@ss 9.0 (Classifications) | 27371819 |
| Assembly instructions (Times) | See derating curve |
| Contact type (Digital inputs) | 2 enabling current paths |
| Designation (Connection data) | EN 62061 |
| Inrush current (Power supply) | < 60 mA (Typically with USat Y1, Δt = 150 ms) |
| Maximum altitude (Dimensions) | ≤ 2000 m (Above sea level) |
| Recovery time (Alarm outputs) | < 500 ms |
| Nominal operating mode (Times) | 100% operating factor |
| Inrush current (Digital inputs) | min. 10 mA |
| Number of inputs (Power supply) | 4 |
| Stop category (Connection data) | 0 |
| Designation (Ambient conditions) | A1/A2 |
| Filter time (Ambient conditions) | 20 ms (at A1 in the event of voltage dips at Us) |
| Contact material (Digital inputs) | AgSnO2 |
| Operating voltage display (Times) | 1 x green LED |
| Current consumption (Power supply) | typ. 10 mA (Typically with USat Y1) |
| Number of outputs (Digital inputs) | 2 (undelayed) |
| Sq. Total current (Digital inputs) | 72 A2(observe derating) |
| Switching voltage (Digital inputs) | min. 10 V AC/DC |
| Utilization restriction (Drawings) | EMC: class A product, see manufacturer's declaration in the download area |
| Inrush current (Ambient conditions) | < 4 A (Δt = 3 ms at Us) |
| Output description (Digital inputs) | safety-related N/O contacts |
| Switching capacity (Digital inputs) | min. 100 mW |
| Concurrence input 1/2 (Power supply) | ∞ |
| Switching frequency (Digital inputs) | max. 0.5 Hz |
| Weight per Piece (excluding packing) | 180.000 g |
| (Safety-related characteristic data) | 250 V |
| REACh SVHC (Standards and Regulations) | Lead 7439-92-1 |
| (Relay outputs: enabling current path) | non-safety-related |
| Description of the input (Power supply) | non-safety-related |
| Protective circuit (Ambient conditions) | Serial protection against polarity reversal Suppressor diode |
| Mechanical service life (Digital inputs) | 10x 106cycles |
| No preview imageBlock diagram (Drawings) | |
| Performance level (PL) (Connection data) | e |
| Typical pickup time at US (Alarm outputs) | 200 ms (when controlled via A1) |
| Conductor cross section AWG max. (General) | 14 |
| Conductor cross section AWG min. (General) | 24 |
| Shock (Safety-related characteristic data) | 15g |
| Typical release time at US (Alarm outputs) | 25 ms (when actuation is via the sensor circuit) |
| Protective circuit/component (Power supply) | Suppressor diode |
| Typical response time at US (Alarm outputs) | 200 ms (automatic start) |
| Ambient temperature (operation) (Dimensions) | -20 °C ... 55 °C (observe derating) |
| Conductor cross section solid max. (General) | 2.5 mm² |
| Conductor cross section solid min. (General) | 0.2 mm² |
| Limiting continuous current (Digital inputs) | 6 A |
| Power consumption at US (Ambient conditions) | typ. 1.8 W |
| Input voltage range "1" signal (Power supply) | 20.4 V DC ... 26.4 V DC |
| Current (Relay outputs: enabling current path) | max. 100 mA |
| Safety Integrity Level (SIL) (Connection data) | 3 |
| Voltage (Relay outputs: enabling current path) | approx. 23.9 V DC (Us- 0.1 V) |
| Conductor cross section flexible max. (General) | 2.5 mm² |
| Conductor cross section flexible min. (General) | 0.2 mm² |
| Conformance (Safety-related characteristic data) | CE-compliant |
| Designation (Safety-related characteristic data) | Air clearances and creepage distances between the power circuits |
| Designation (Relay outputs: enabling current path) | Y30 |
| Min. degree of protection of inst. location (Times) | IP54 |
| Ambient temperature (storage/transport) (Dimensions) | -40 °C ... 70 °C |
| Rated control supply current IS (Ambient conditions) | typ. 75 mA |
| Degree of pollution (Safety-related characteristic data) | 2 |
| Number of outputs (Relay outputs: enabling current path) | 1 |
| Output description (Relay outputs: enabling current path) | PNP |
| Overvoltage category (Safety-related characteristic data) | III |
| Max. permissible humidity (storage/transport) (Dimensions) | 75 % (on average, 85% infrequently, non-condensing) |
| Standards/regulations (Safety-related characteristic data) | DIN EN 50178 |
| Vibration (operation) (Safety-related characteristic data) | 10 Hz ... 150 Hz, 2g |
| Max. permissible relative humidity (operation) (Dimensions) | 75 % (on average, 85% infrequently, non-condensing) |
| Max. permissible overall conductor resistance (Power supply) | 50 Ω |
| Rated control circuit supply voltage US (Ambient conditions) | 24 V DC -15 % / +10 % (provide external protection) |
| Maximum inrush current (Relay outputs: enabling current path) | 500 mA (Δt = 1 ms at Us) |
| Rated insulation voltage (Safety-related characteristic data) | 250 V |
| Safety Integrity Level Claim Limit (SIL CL) (Connection data) | 3 |
| Switching capacity according to IEC 60947-5-1 (Digital inputs) | 5 A (24 V (DC13)) |
| Protective circuit/component (Relay outputs: enabling current path) | Suppressor diode |
Technical specifications and performance data
Installation and operation guide