Service time: Monday to Friday 9:00-18:00
PSR-MC30-2NO-1DO-24DC-SC - PSR-MC30-2NO-1DO-24DC-SC 2700498 PHOENIX CONTACT Safety relays
In Stock Hot Product

PSR-MC30-2NO-1DO-24DC-SC

PSR-MC30-2NO-1DO-24DC-SC 2700498 PHOENIX CONTACT Safety relays

$0.00USD
4248 in stock
Key Specifications
GTIN:4046356912860
Orderkey:2700498
Catalog page:Page 253 (C-6-2017)
Depth (Note):114.5 mm
Supplier Information
Products: 0
Usually ships within 2-3 business days
Quality Guaranteed
Fast Shipping
Technical Support

Technical Specifications

ParameterValue
GTIN4046356912860
Orderkey2700498
Catalog pagePage 253 (C-6-2017)
Depth (Note)114.5 mm
Packing unit1 pc
Width (Note)12.5 mm
Height (Note)112.2 mm
(Power supply)Test pulse rate = 5 x Test pulse width
(Alarm outputs)< 175 ms (manual, monitored start)
(Digital inputs)4 A gL/gG (for low-demand applications)
Country of originDE (Germany)
Net weight (Times)159 g
Relay type (Times)Electromechanical relay with forcibly guided contacts in accordance with IEC/EN 61810-3 (EN 50205)
pluggable (General)Yes
Custom tariff number85371098
(Ambient conditions)Protection against polarity reversal for rated control circuit supply voltage
Housing color (Times)yellow
Mounting type (Times)DIN rail mounting
Screw thread (General)M3
Status display (Times)3 x green LED
Housing material (Times)PBT
Mounting position (Times)vertical or horizontal
Category (Connection data)4
Filter time (Power supply)max. 1.5 ms (at S12, S22; test pulse width)
Stripping length (General)7 mm
Connection method (General)Screw connection
(Standards and Regulations)For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”
Degree of protection (Times)IP20
Output fuse (Digital inputs)6 A gL/gG (N/O contact)
Output name (Digital inputs)Enabling current path
Assembly instructions (Times)See derating curve
Contact type (Digital inputs)2 enabling current paths
Designation (Connection data)EN 62061
Inrush current (Power supply)< 20 mA (with Us/Ixto S12)
Maximum altitude (Dimensions)≤ 2000 m (Above sea level)
Recovery time (Alarm outputs)< 500 ms
Nominal operating mode (Times)100% operating factor
Inrush current (Digital inputs)min. 3 mA
Stop category (Connection data)0
Filter time (Ambient conditions)1 ms (at A1 in the event of voltage dips at Us)
Contact material (Digital inputs)AgSnO2
Operating voltage display (Times)1 x green LED
Current consumption (Power supply)< 5 mA (with Us/Ixto S12)
Number of outputs (Digital inputs)2 (undelayed)
Sq. Total current (Digital inputs)72 A2(observe derating)
Switching voltage (Digital inputs)min. 12 V AC/DC
Inrush current (Ambient conditions)4 A (Δt = 200 µs at Us)
Output description (Digital inputs)safety-related N/O contacts
Switching capacity (Digital inputs)min. 60 mW
Switching frequency (Digital inputs)0.5 Hz
Weight per Piece (excluding packing)159.000 g
(Safety-related characteristic data)250 V AC
China RoHS (Standards and Regulations)Environmentally Friendly Use Period = 50
Protective circuit (Ambient conditions)Surge protection Suppressor diode
Mechanical service life (Digital inputs)10x 106cycles
Performance level (PL) (Connection data)e (4 A DC13; 5 A AC15; 8760 switching cycles/year)
Typical pickup time at US (Alarm outputs)< 250 ms (when controlled via A1)
Conductor cross section AWG max. (General)12
Conductor cross section AWG min. (General)24
Shock (Safety-related characteristic data)15g
Typical release time at US (Alarm outputs)< 20 ms (when controlled via A1 or S12 and S22.)
Typical response time at US (Alarm outputs)< 175 ms (automatic start)
Ambient temperature (operation) (Dimensions)-40 °C ... 55 °C (observe derating)
Conductor cross section solid max. (General)2.5 mm²
Conductor cross section solid min. (General)0.2 mm²
Limiting continuous current (Digital inputs)6 A (observe derating)
Power consumption at US (Ambient conditions)typ. 1.56 W
Input current range "0" signal (Power supply)0 mA ... 2 mA (for safe Off; at S12)
Input voltage range "0" signal (Power supply)0 V DC ... 5 V DC (for safe Off; at S12)
Utilization restriction (Key Commercial Data)1
Current (Relay outputs: enabling current path)max. 100 mA
Safety Integrity Level (SIL) (Connection data)3
Voltage (Relay outputs: enabling current path)22 V DC (Us- 2 V)
Conductor cross section flexible max. (General)2.5 mm²
Conductor cross section flexible min. (General)0.2 mm²
Conformance (Safety-related characteristic data)CE-compliant
Designation (Safety-related characteristic data)Air clearances and creepage distances between the power circuits
Min. degree of protection of inst. location (Times)IP54
Ambient temperature (storage/transport) (Dimensions)-40 °C ... 85 °C
Rated control supply current IS (Ambient conditions)typ. 65 mA
Degree of pollution (Safety-related characteristic data)2
Number of outputs (Relay outputs: enabling current path)1 (digital, PNP)
Output description (Relay outputs: enabling current path)non-safety-related
Overvoltage category (Safety-related characteristic data)III
Max. permissible humidity (storage/transport) (Dimensions)75 % (on average, 85% infrequently, non-condensing)
Standards/regulations (Safety-related characteristic data)DIN EN 50178
Vibration (operation) (Safety-related characteristic data)10 Hz ... 150 Hz, 2g
Voltage at input/start and feedback circuit (Power supply)24 V DC -15 % / +10 %
Max. permissible relative humidity (operation) (Dimensions)75 % (on average, 85% infrequently, non-condensing)
Max. permissible overall conductor resistance (Power supply)150 Ω
Rated control circuit supply voltage US (Ambient conditions)24 V DC -15 % / +10 %
Maximum inrush current (Relay outputs: enabling current path)500 mA (Δt = 1 ms at Us)
Rated insulation voltage (Safety-related characteristic data)250 V AC
Safety Integrity Level Claim Limit (SIL CL) (Connection data)3
Short-circuit protection (Relay outputs: enabling current path)no
Rated surge voltage/insulation (Safety-related characteristic data)Safe isolation, reinforced insulation 6 kV between input circuit and enabling current path (13/14) and enabling current path (23/24)Basic insulation 4 kV between all current paths and housing

Product Description

Safety relay for emergency stop and protective doors up to SIL 3, cat. 4, PL e, 1 or 2 channel service, automatic or manual, monitored start, transverse short circuit detection, 2 trip circuits, US =
Key Features
  • Industrial grade quality
  • RoHS compliant
  • CE certified
  • 1-year warranty

Product Documents

Datasheet

Technical specifications and performance data

User Manual

Installation and operation guide

Top