| Parameter | Value |
|---|---|
| max. 10 s (Boot time) | |
| Note | G3 |
| Depth | 113.6 mm |
| Shock | 10g for Δt = 16 ms (continuous shock, 1000 shocks in each space direction) |
| Width | 22.61 mm |
| Height | 107.74 mm |
| Current | max. 30 mA (Sensor current recording per channel) |
| Frequency | 20 Hz (max. recommended sensor signal frequency, as current input) |
| Precision | typ. ± 2 % (as current input, relative to the measuring range final value) |
| pluggable | yes |
| Input name | IN S1, IN S2, IN S3, IN S4 |
| Interfaces | DIN rail TBUS for connection to the master module, supplied as standard |
| Application | Analog IN |
| Description | Sensor supply voltage per analog input |
| Designation | A1/A2 |
| Filter time | typ. 5 ms (in the event of voltage dips at Us) |
| Product type | Safety device |
| Restart time | min. 5 s (Boot time) |
| Mounting type | DIN rail mounting |
| Response time | see user manual |
| Scanning rate | 2.5/5/10/16.6/20/50/60/100/200/400/800/1000/2000/4000 Hz |
| Stop category | 0 |
| Identification | CE-compliant |
| Inrush current | max. 14 A (Δt = 1 ms at Us) |
| Status display | 4x LED (yellow, red) |
| Supply voltage | 24 V DC ±3 % |
| Housing material | Polyamide PA non-reinforced |
| Maximum altitude | ≤ 2000 m (Above sea level) |
| Number of inputs | 4 |
| Protection class | III |
| Stripping length | 10 mm |
| Connection method | Push-in connection |
| Mounting position | vertical or horizontal |
| Protective circuit | Serial protection against polarity reversal |
| Permissible voltage | max. 24 V (as current input) |
| Short-circuit-proof | yes |
| Current input signal | 0 mA ... 25 mA (Measuring range) |
| Degree of protection | IP20 |
| Resolution (current) | 381 nA |
| Resolution (voltage) | 152 µV |
| Voltage input signal | 0 V ... 12 V (Measuring range) |
| Assembly instructions | Observe derating |
| Connection technology | 2-conductor, 3-conductor or 4-conductor (2-conductor sensor signal + 2-conductor sensor supply) |
| Vibration (operation) | 10 Hz ... 150 Hz, 2g |
| Limit frequency (3 dB) | 160 Hz (RC low pass, 1st order, as current input) |
| Nominal operating mode | 100% operating factor |
| Performance level (PL) | e (2-channel wiring) |
| Power consumption at US | typ. 1.96 W (without sensor supply) |
| A/D converter resolution | 16 bit |
| Description of the input | Safety-oriented analog inputs, configurable as current or voltage inputs, galvanically isolated |
| Max. permissible current | max. 35 mA (as current input) |
| Permissible cable length | max. 100 m (per input) |
| Rated insulation voltage | 250 V AC |
| Temperature coefficients | typ. ± 0.07 %/K |
| Operating voltage display | 1 x green LED |
| Conductor cross-section AWG | 24 ... 16 |
| Safety Integrity Level (SIL) | 3 |
| Conductor cross section rigid | 0.2 mm² ... 2.5 mm² |
| Input resistance current input | 290 Ω ±25 % (incl. internal protective circuit) |
| Rated surge voltage/insulation | Basic insulation 4 kV between all current paths and housing |
| Ambient temperature (operation) | -10 °C ... 70 °C (observe derating) |
| Rated control supply current IS | typ. 82 mA (without sensor supply) |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Input resistance of voltage input | 185 kΩ ±25 % |
| Ambient temperature (storage/transport) | -20 °C ... 85 °C |
| Rated control circuit supply voltage US | 19.2 V DC ... 28.8 V DC |
| Note regarding the connection technology | shielded |
| Min. degree of protection of inst. location | IP54 |
| Max. permissible humidity (storage/transport) | 95 % (non-condensing) |
| Max. permissible relative humidity (operation) | 95 % (non-condensing) |
| Maximum power dissipation for nominal condition | 2.76 W (with max. permissible load) |
Technical specifications and performance data
Installation and operation guide