| Parameter | Value |
|---|---|
| Light grid | |
| Note | G3 |
| Depth | 113.6 mm |
| Shock | 10g for Δt = 16 ms (continuous shock, 1000 shocks in each space direction) |
| Width | 22.61 mm |
| Height | 107.74 mm |
| Voltage | 24 V DC (via A1) |
| pluggable | yes |
| Interfaces | DIN rail TBUS for connection to the master module, supplied as standard |
| Application | Emergency stop |
| Designation | A1/A2 |
| Filter time | typ. 5 ms (in the event of voltage dips at Us) |
| Test pulses | < 250 µs (Test pulse width of low test pulses) |
| Cable length | max. 100 m (per input) |
| Product type | Safety device |
| Restart time | min. 5 s (Boot time) |
| Mounting type | DIN rail mounting |
| Response time | see user manual |
| Stop category | 0 |
| Identification | CE-compliant |
| Inrush current | 7.5 A (Δt = 0.4 ms at Us) |
| Status display | 1 x LED (green), 2 x LED (orange) |
| Leakage current | max. 4.5 mA (in the Low state) |
| Error indication | 2 x LED (red) |
| Housing material | Polyamide PA non-reinforced |
| Maximum altitude | ≤ 2000 m (Above sea level) |
| Number of inputs | 8 |
| Protection class | III |
| Stripping length | 10 mm |
| Connection method | Push-in connection |
| Mounting position | vertical or horizontal |
| Number of outputs | 4 |
| Output description | Safety-related digital outputs |
| Protective circuit | Serial protection against polarity reversal |
| Current consumption | typ. 3.7 mA (typically with US) |
| Discharging circuit | Yes, internal |
| Max. inductive load | See "Protective circuit" |
| Switching frequency | max. 1/4 x tCycle[Hz] |
| Degree of protection | IP20 |
| Max. capacitive load | max. 820 nF |
| Assembly instructions | Observe derating |
| Vibration (operation) | 10 Hz ... 150 Hz, 2g |
| Maximum inrush current | 1.1 A (Δt = 3 s at Us) |
| Nominal operating mode | 100% operating factor |
| Nominal output voltage | 24 V DC (Supply via A1) |
| Performance level (PL) | e (2-channel wiring) |
| Power consumption at US | typ. 1.2 W (Outputs inactive) |
| Description of the input | Safety-related digital inputs |
| Rated insulation voltage | 250 V AC |
| Short-circuit protection | Yes (self-limitation at 1.1 A) |
| Operating voltage display | 1 x green LED |
| Conductor cross-section AWG | 24 ... 16 |
| Limiting continuous current | 400 mA (per channel) |
| Nominal output voltage range | 18.6 V DC ... 28.2 V DC (US- 0,7 V) |
| Safety Integrity Level (SIL) | 3 |
| Conductor cross section rigid | 0.2 mm² ... 2.5 mm² |
| Input current range "0" signal | < 0.2 mA |
| Input voltage range "0" signal | 0 V DC ... 5 V DC (for safe Off) |
| Input voltage range "1" signal | 11 V DC ... 28.8 V DC |
| Rated surge voltage/insulation | Basic insulation 4 kV between 24 V power supply and I/Os to the housing |
| Ambient temperature (operation) | -10 °C ... 70 °C (observe derating) |
| Rated control supply current IS | typ. 50 mA (Outputs inactive) |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Output voltage when switched off | < 0.3 V |
| Ambient temperature (storage/transport) | -20 °C ... 85 °C |
| Rated control circuit supply voltage US | 19.2 V DC ... 28.8 V DC |
| Min. degree of protection of inst. location | IP54 |
| Max. permissible humidity (storage/transport) | 95 % (non-condensing) |
| Max. permissible overall conductor resistance | max. 1.2 kΩ (Input and reset circuit at US) |
| Max. permissible relative humidity (operation) | 95 % (non-condensing) |
| Maximum power dissipation for nominal condition | 7.48 W (with max. permissible load) |
Technical specifications and performance data