| Parameter | Value |
|---|---|
| RS-422 | |
| EMC | B |
| MTBF | 10 Years (Telcordia standard, temperature 40 °C, operating cycle 100 % (7 days a week, 24 hours a day)) |
| MTTF | 1654 Years (SN 29500 standard, temperature 25°C, operating cycle 21%) |
| Note | Please follow the special installation instructions in the documentation! |
| Depth | 114.5 mm |
| Input | ± 2.2 kV (Test Level 3) |
| Width | 22.5 mm |
| Height | 99 mm |
| Signal | Modbus |
| Voltage | 10 V |
| Altitude | ≤ 5000 m (For restrictions, see the manufacturer's declaration for altitude operation) |
| Comments | Criterion B |
| EMC note | EMC: class A product, see manufacturer's declaration in the download area |
| Humidity | A |
| Bit delay | ≤ 2.5 µs |
| Enclosure | Required protection according to the Rules shall be provided upon installation on board |
| Interface | RS-232/-485 |
| Vibration | A |
| CCCex note | Use in potentially explosive areas is not permitted in China. |
| Application | RS-232 |
| Certificate | CE-compliant |
| Criterion A | Normal operating behavior within the specified limits. |
| Criterion B | Temporary impairment to operational behavior that is corrected by the device itself. |
| Temperature | B |
| Product type | Interface converter |
| Mounting type | DIN rail mounting |
| Bit distortion | ≤ 5 % |
| Identification | II 3 G Ex nA IIC T4 Gc |
| Noise emission | EN 61000-6-4 |
| Noise immunity | EN 61000-6-2:2005 |
| Pin assignment | DTE/DCE switchover via switch |
| Color (Housing) | green (RAL 6021) |
| Field intensity | 10 V/m |
| Frequency range | 26 MHz ... 3 GHz (Test Level 3) |
| Article revision | 22 |
| Discharge in air | ± 8 kV (Test Level 3) |
| Pollution degree | 2 |
| Connection method | D-SUB 9 plug |
| Contact discharge | ± 6 kV (Test Level 3) |
| Tightening torque | 0.56 Nm ... 0.79 Nm |
| Material (Housing) | PA 6.6-FR |
| Dimensional drawing | |
| Note on application | Only for industrial use |
| Protocols supported | transparent protocol |
| Transmission length | 15 m (shielded twisted pair) |
| Degree of protection | IP20 |
| Electrical isolation | VCC // V.24 (RS-232) // RS-485 |
| Supply voltage range | 18 V AC/DC ... 30 V AC/DC (via pluggable COMBICON screw terminal block) |
| Termination resistor | 390 Ω |
| Standards/regulations | EN 61000-4-2 |
| Transmission channels | 2 (1/1), RxD, TxD, full duplex |
| Nominal supply voltage | 24 V AC/DC |
| Data direction switching | Automatic control or via RTS/CTS |
| Max. current consumption | 100 mA |
| Serial transmission speed | 1.2; 2.4; 4.8; 7.2; 9.6; 19.2; 31.25; 38.4; 57.6; 75; 93.75; 115.2 kbps |
| Typical current consumption | 85 mA (24 V DC) |
| Test voltage data interfaces | 1.5 kV AC |
| Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
| Ambient temperature (operation) | -40 °C ... 70 °C |
| Permissible humidity (operation) | 10 % ... 95 % (non-condensing) |
| Single-wire/terminal point, flexible | 0.2 mm² ... 2.5 mm² |
| Single conductor/terminal point, rigid | 0.2 mm² ... 2.5 mm² |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Conductor cross section, flexible [AWG] | 24 ... 12 |
| Test voltage data interface/power supply | 1.5 kV AC |
| Max. AWG conductor cross section, flexible | 12 |
| Min. AWG conductor cross section, flexible | 24 |
| Maximum power dissipation for nominal condition | 2.04 W |
Technical specifications and performance data
Installation and operation guide