| Parameter | Value |
|---|---|
| 60 V DC | |
| Shielded | yes |
| Sensor type | PROFIBUS |
| Cable length | Free entry (1.0 ... 1000.0 m) |
| Cable weight | 80 kg/km |
| Product type | Data cable by the meter |
| Signal speed | 0.81 c |
| Test voltage | 3600 V DC (3 s) |
| UL AWM Style | 21694 (60 °C / 600 V) |
| Overall twist | 2 wires, twisted |
| Cable capacity | approx. 28.5 nF/km (at 1 kHz) |
| AWG signal line | 22 |
| Cable impedance | 150 Ω ±10 % (3 ... 20 MHz) |
| Loop resistance | ≤ 110.00 Ω/km |
| Flame resistance | according to IEC 60332-3-24 (Cat. C ) |
| Other resistance | Cold bending resistance (according to DIN VDE 0473 Part 811-1-4 (after 16 h at -40 °C)) |
| Tensile strength | ≤ 100 N |
| Resistance to oil | Limited resistance to mineral oils and greases |
| Conductor material | Bare Cu wire |
| Nominal voltage UN | 48 V AC |
| Shield attenuation | ≤ 42.00 dB/km (at 16 MHz) |
| Single wire, color | red, green |
| Conductor structure | 1x2xAWG22/1 |
| Number of positions | 2 |
| Transmission medium | Copper |
| Signal type/category | PROFIBUS, 12 Mbps |
| Insulation resistance | ≥ 16 GΩ*km |
| Thickness, insulation | 0.95 mm |
| External sheath, color | violet |
| Outer sheath, material | PVC FR VI |
| Conductor cross section | 2x 0.34 mm² |
| External cable diameter | 8.00 mm ±0.4 mm |
| Optical shield covering | 55 % |
| Thickness, outer sheath | 0.90 mm |
| Material wire insulation | PE |
| Wiring standards/regulations | Conductor material DIN EN 13602 Cu-ETP-A... |
| Wire diameter incl. insulation | 2.55 mm |
| Ambient temperature (operation) | -40 °C ... 60 °C |
| Conductor structure signal line | 1x 0.65 mm |
| Smallest bending radius, fixed installation | ≥ 150 mm |
Technical specifications and performance data
Installation and operation guide