| Parameter | Value |
|---|---|
| 717 Years (SN 29500 standard, temperature 40°C, operating cycle 34.25%) | |
| MTBF | 1247 Years (Telcordia standard, 25°C temperature, 21% operating cycle (5 days a week, 8 hours a day)) |
| MTTF | 1439 Years (SN 29500 standard, temperature 25°C, operating cycle 21%) |
| Note | Please follow the special installation instructions in the documentation! |
| Depth | 105 mm |
| Input | ± 2 kV |
| Width | 35 mm |
| Height | 99 mm |
| Signal | Modbus |
| Voltage | 10 V |
| Altitude | ≤ 5000 m (For restrictions, see the manufacturer's declaration for altitude operation) |
| Comments | Criterion B |
| EMC note | EMC: class A product, see manufacturer's declaration in the download area |
| Bit delay | < 1 bit |
| CCCex note | Use in potentially explosive areas is not permitted in China. |
| Certificate | CE-compliant |
| Criterion A | Normal operating behavior within the specified limits. |
| Criterion B | Temporary impairment to operational behavior that is corrected by the device itself. |
| Product type | Interface converter |
| Mounting type | DIN rail mounting |
| Identification | II 3 G Ex ec IIC T5 Gc |
| Noise emission | EN 55011 |
| Noise immunity | EN 61000-4-2 |
| Color (Housing) | gray (RAL 7042) |
| Field intensity | 10 V/m |
| Frequency range | 80 MHz ... 3 GHz |
| Article revision | 11 |
| Discharge in air | ± 8 kV |
| Stripping length | 7.00 mm |
| Connection method | Pluggable screw connection |
| Contact discharge | ± 6 kV |
| Tightening torque | 0.6 Nm ... 0.8 Nm |
| File format/coding | UART (11/10 bit switchable; NRZ) |
| Material (Housing) | PA 6.6-FR |
| Transmission speed | 4.8/9.6/19.2/38.4/57.6/75/93.75/115.2/136/187.5/375/500 kbps (Can be set manually) |
| Dimensional drawing | |
| Note on application | Only for industrial use |
| Transmission length | ≤ 1200 m (depends on transmission speed, bus system and cable type) |
| Transmission medium | 2-wire twisted pair, shielded |
| Degree of protection | IP20 |
| Electrical isolation | VCC // TBUS // RS-485 (A) // RS-485 (B) |
| Supply voltage range | 18 V DC ... 30 V DC (via pluggable COMBICON screw terminal block) |
| Termination resistor | 390 Ω (Can be connected to port A and B) |
| Bit distortion, input | max. ± 35 % |
| Standards/regulations | EN 61000-4-2 |
| Transmission channels | 2 (1/1), TD, RD, half duplex |
| Bit distortion, output | < 6.25 % |
| Nominal supply voltage | 24 V DC (in acc. with UL) |
| Data direction switching | Automatic control, min. station response time 2 bits |
| Max. current consumption | ≤ 2 A (For operation in a joining station, via the DIN rail connector) |
| Typical current consumption | 75 mA (24 V DC) |
| Test voltage data interfaces | 1.5 kV |
| Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
| Ambient temperature (operation) | -20 °C ... 60 °C |
| Permissible humidity (operation) | 10 % ... 95 % (non-condensing) |
| Single-wire/terminal point, flexible | 0.2 mm² ... 2.5 mm² |
| Single conductor/terminal point, rigid | 0.2 mm² ... 2.5 mm² |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Test voltage data interface/power supply | 1.5 kVrms(50 Hz, 1 min.) |
| Max. AWG conductor cross section, flexible | 12 |
| Min. AWG conductor cross section, flexible | 24 |
| Single-wire/terminal point, rigid AWG max. | 12 |
| Single-wire/terminal point, rigid AWG min. | 24 |
| Maximum power dissipation for nominal condition | 1.8 W |
| Free from substances that could impair the application of coating | VDMA 24364:2018-05 |
Technical specifications and performance data
Installation and operation guide