| Parameter | Value |
|---|---|
| GTIN | 4046356167802 |
| Note | Made to Order (non-returnable) |
| Orderkey | 2834876 |
| (General) | EN 50178 |
| (Coil side) | 1500 VA (for 250 V AC) |
| Catalog page | Page 404 (C-5-2017) |
| Depth (Note) | 86 mm |
| Packing unit | 10 pc |
| Width (Note) | 6.2 mm |
| Height (Note) | 80 mm |
| (Contact side) | 2x 0.5 mm² ... 1.5 mm² () |
| Country of origin | DE (Germany) |
| Custom tariff number | 85364190 |
| Designation (General) | Air clearances and creepage distances between the power circuits |
| Contact type (Coil side) | 1 N/O contact with switch |
| Screw thread (Contact side) | M3 |
| (Standards and Regulations) | For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |
| Contact material (Coil side) | AgSnO |
| (Connection data input side) | 2x 0.5 mm² ... 1.5 mm² () |
| Degree of pollution (General) | 2 |
| Rated surge voltage (General) | 6 kV |
| (Connection data output side) | IP20 (Relay base) |
| Connection name (Contact side) | Coil side |
| Overvoltage category (General) | III |
| Standards/regulations (General) | IEC 60664 |
| Stripping length (Contact side) | 8 mm |
| Connection method (Contact side) | Screw connection |
| Maximum inrush current (Coil side) | on request |
| Min. switching current (Coil side) | 10 mA (at 12 V) |
| Rated insulation voltage (General) | 250 V AC |
| Type of switch contact (Coil side) | Single contact |
| Weight per Piece (excluding packing) | 38.160 g |
| Maximum switching voltage (Coil side) | 250 V AC/DC |
| Minimum switching voltage (Coil side) | 5 V (at 100 mA) |
| China RoHS (Standards and Regulations) | Environmentally Friendly Use Period = 50 |
| Limiting continuous current (Coil side) | 6 A |
| Protective circuit (Ambient conditions) | Bridge rectifier Bridge rectifier |
| Screw thread (Connection data input side) | M3 |
| Typical release time (Ambient conditions) | 15 ms |
| Conductor cross section AWG (Contact side) | 26 ... 14 |
| Connection in acc. with standard (General) | CUL |
| Typical response time (Ambient conditions) | 6 ms |
| Ambient temperature (operation) (Dimensions) | -20 °C ... 60 °C |
| Conductor cross section solid (Contact side) | 0.14 mm² ... 2.5 mm² |
| Connection name (Connection data input side) | Contact side |
| Operating mode (Connection data output side) | 100% operating factor |
| Nominal input voltage UN (Ambient conditions) | 24 V AC/DC |
| Stripping length (Connection data input side) | 8 mm |
| Utilization restriction (Key Commercial Data) | EMC: class A product, see manufacturer's declaration in the download area |
| Connection method (Connection data input side) | Screw connection |
| Net weight (SAP) (Connection data output side) | 38.16 g |
| Operating voltage display (Ambient conditions) | Yellow LED |
| Conductor cross section flexible (Contact side) | 0.14 mm² ... 2.5 mm² |
| Mounting position (Connection data output side) | any |
| Flammability rating according to UL 94 (General) | V0 |
| Typical input current at UN (Ambient conditions) | 11 mA |
| Interrupting rating (ohmic load) max. (Coil side) | 140 W (at 24 V DC) |
| Degree of protection (Connection data output side) | RT III (Relay) |
| Assembly instructions (Connection data output side) | In rows with zero spacing |
| Ambient temperature (storage/transport) (Dimensions) | -20 °C ... 85 °C |
| Conductor cross section AWG (Connection data input side) | 26 ... 14 |
| Conductor cross section solid (Connection data input side) | 0.14 mm² ... 2.5 mm² |
| Input voltage range in reference to UN (Ambient conditions) | see diagram |
| Power dissipation for nominal condition (Ambient conditions) | 0.26 W |
| Conductor cross section flexible (Connection data input side) | 0.14 mm² ... 2.5 mm² |
Technical specifications and performance data