

| Parameter | Value |
|---|---|
| High continuous currents | |
| EMC | B |
| Color | gray (RAL 7042) |
| Depth | 104 mm |
| Width | 14 mm |
| Height | 80 mm |
| Altitude | ≤ 2000 m |
| Humidity | A |
| Enclosure | Required protection according to the Rules shall be provided upon installation on board |
| Vibration | B/C |
| Insulation | Safe isolation, reinforced insulation |
| Application | Palm switch |
| Certificate | CE-compliant |
| Temperature | D |
| Product type | Relay Module |
| Assembly note | in rows with zero spacing |
| Mounting type | DIN rail mounting |
| Identification | UL 508 |
| Operating mode | 100% operating factor |
| Product family | PLC-INTERFACE |
| Article revision | 03 |
| Contact material | AgNi |
| Drive (polarity) | polarized |
| Pollution degree | 2 |
| Stripping length | 10 mm |
| Connection method | Push-in connection |
| Mounting position | any |
| Drive and function | monostable |
| Protective circuit | Bridge rectifier; Bridge rectifier |
| Switching capacity | 2 A (24 V, DC13) |
| Input voltage range | 20.6 V AC/DC ... 33.6 V AC/DC (20 °C) |
| Rated surge voltage | 6 kV |
| Overvoltage category | III |
| Low Voltage Directive | Conformance with Low Voltage Directive |
| Standards/regulations | IEC 60947-5-1 |
| Typical response time | 3 ms ... 15 ms |
| Contact switching type | 1 changeover contact |
| Maximum inrush current | 24 A (20 ms) |
| Min. switching current | 10 mA (12 V) |
| Type of switch contact | Single contact |
| Mechanical service life | 5x 106cycles |
| Nominal input voltage UN | 24 V AC/DC |
| Rated insulation voltage | 250 V AC |
| Maximum switching voltage | 250 V AC/DC (The separating plate PLC-ATP should be installed for voltages larger than 250 V (L1, L2, L3) between identical terminal blocks in adjacent modules. Potential bridging is then carried out with FBST 8-PLC... or ...FBST 500...) |
| Minimum switching voltage | 12 V (10 mA) |
| Operating voltage display | Yellow LED |
| Typical release time range | 3 ms ... 15 ms |
| Conductor cross section AWG | 26 ... 14 |
| Limiting continuous current | 10 A |
| Typical input current at UN | 18 mA |
| Date of last data management | 08.07.2024 |
| Degree of protection (Relay) | RT II (Relay) |
| Conductor cross section rigid | 0.14 mm² ... 2.5 mm² |
| Electromagnetic compatibility | Conformance with EMC directive |
| Test voltage (Winding/contact) | 4 kVrms(50 Hz, 1 min., winding/contact) |
| Ambient temperature (operation) | -40 °C ... 60 °C |
| Conductor cross section flexible | 0.14 mm² ... 2.5 mm² |
| Degree of protection (Relay base) | IP20 (Relay base) |
| Interrupting rating (ohmic load) max. | 264 W (24 V DC) |
| Flammability rating according to UL 94 | V0 (Housing) |
| Ambient temperature (storage/transport) | -20 °C ... 85 °C |
| Degree of protection (Installation location) | ≥ IP54 (Installation location) |
| Maximum power dissipation for nominal condition | 0.44 W |
| Nominal voltage (plugged-in electromechanical relay) | 24 V DC |
Technical specifications and performance data
Installation and operation guide