| Parameter | Value |
|---|---|
| GTIN | 4055626744865 |
| Orderkey | 1069556 |
| (Drawings) | |
| Catalog page | Page 423 (C-5-2019) |
| Depth (Note) | 86 mm |
| Packing unit | 1 pc |
| Width (Note) | 6.5 mm |
| Height (Note) | 80 mm |
| Country of origin | DE (Germany) |
| ETIM 5.0 (eCl@ss) | EC002055 |
| ETIM 6.0 (eCl@ss) | EC002055 |
| ETIM 7.0 (eCl@ss) | EC002055 |
| Note (Input data) | Protect the supply voltage at the output using a suitable fuse. |
| (Connection data 2) | EN 50178 |
| Custom tariff number | 85371098 |
| (Ambient conditions) | Surge protection |
| (Conformance/approvals) | For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |
| Output name (Input data) | DC output |
| Connection name (General) | Control circuits |
| Stripping length (General) | 8 mm |
| Connection method (General) | Push-in connection |
| eCl@ss 6.0 (Classifications) | 27371000 |
| eCl@ss 7.0 (Classifications) | 27371014 |
| eCl@ss 8.0 (Classifications) | 27371014 |
| eCl@ss 9.0 (Classifications) | 27371014 |
| Application drawing (Drawings) | |
| Insulation (Connection data 2) | Basic insulation |
| Designation (Connection data 2) | Air clearances and creepage distances between the power circuits |
| Input name (Ambient conditions) | Control input right/left |
| Type of protection (Input data) | Surge protection |
| Connection name (Connection data) | Load circuit |
| Degree of protection (Dimensions) | IP20 |
| China RoHS (Conformance/approvals) | Environmentally Friendly Use Period = 50 |
| REACh SVHC (Conformance/approvals) | Lead 7439-92-1 |
| Stripping length (Connection data) | 8 mm |
| Utilization restriction (Drawings) | EMC: class A product, see manufacturer's declaration in the download area |
| Connection method (Connection data) | Push-in connection |
| Nominal output voltage (Input data) | 24 V DC |
| Status display (Ambient conditions) | Yellow LED |
| Operating voltage range (Input data) | 10 V DC ... 30 V DC |
| Pollution degree (Connection data 2) | 2 |
| Weight per Piece (excluding packing) | 40.000 g |
| Conductor cross section AWG (General) | 26 ... 14 |
| Conductor cross section solid (General) | 0.14 mm² ... 2.5 mm² |
| Designation (Standards and Regulations) | CE |
| Note on protection circuit (Input data) | No continuous protection against polarity reversal |
| Protective circuit (Ambient conditions) | Reverse polarity protection Polarity protection diode |
| Rated surge voltage (Connection data 2) | 0.5 kV |
| Input voltage range (Ambient conditions) | 19.2 V DC ... 28.8 V DC |
| Operating mode (Output data load output) | 100% operating factor |
| Overvoltage category (Connection data 2) | II |
| Nominal output voltage range (Input data) | 10 V DC ... 30 V DC |
| Protective circuit/component (Input data) | Polarity protection diode |
| Standards/regulations (Connection data 2) | IEC 60664 |
| Conductor cross section flexible (General) | 0.14 mm² ... 2.5 mm² |
| Identification (Standards and Regulations) | CE-compliant |
| Typical response time (Ambient conditions) | 200 µs |
| Mounting position (Output data load output) | Vertical (horizontal DIN rail) |
| Transmission frequency (Ambient conditions) | 300 Hz |
| Ambient temperature (operation) (Dimensions) | -25 °C ... 60 °C |
| Rated insulation voltage (Connection data 2) | 50 V |
| Conductor cross section AWG (Connection data) | 26 ... 14 |
| Nominal input voltage UN (Ambient conditions) | 24 V DC |
| Surge voltage protection (Ambient conditions) | > 33 V DC |
| Assembly instructions (Output data load output) | In rows with zero spacing |
| Conductor cross section solid (Connection data) | 0.14 mm² ... 2.5 mm² |
| Typical input current at UN (Ambient conditions) | approx. 3 mA (Control input current ISTright/left) |
| Control supply voltage range (Ambient conditions) | 19.2 V DC ... 28.8 V DC |
| Conductor cross section flexible (Connection data) | 0.14 mm² ... 2.5 mm² |
| Ambient temperature (storage/transport) (Dimensions) | -40 °C ... 85 °C |
| Switchover time RL/LL(turn-on time) (Ambient conditions) | 80 ms |
| Input voltage range in reference to UN (Ambient conditions) | 0.8 ... 1.2 |
| Rated control circuit supply voltage US (Ambient conditions) | 24 V DC |
Technical specifications and performance data
Installation and operation guide