| Parameter | Value |
|---|---|
| GTIN | 4046356082488 |
| Note | Made to Order (non-returnable) |
| Orderkey | 2982566 |
| (General) | EN 50178 |
| Catalog page | Page 415 (C-5-2017) |
| Depth (Note) | 86 mm |
| Packing unit | 10 pc |
| Width (Note) | 6.2 mm |
| (Input data) | Surge protection |
| Height (Note) | 80 mm |
| Country of origin | DE (Germany) |
| Custom tariff number | 85364900 |
| Insulation (General) | Basic insulation |
| (Ambient conditions) | Surge protection |
| Designation (General) | Air clearances and creepage distances between the power circuits |
| Output circuit (Input data) | 2-wire, floating |
| (Standards and Regulations) | For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |
| Connection name (Output data) | Input side |
| Degree of pollution (General) | 2 |
| Rated surge voltage (General) | 4 kV |
| Overvoltage category (General) | III |
| Stripping length (Output data) | 8 mm |
| (Connection data, output side) | EN 50178 |
| Connection method (Output data) | Spring-cage connection |
| Standards/regulations (General) | IEC 60664 |
| Type of protection (Input data) | Reverse polarity protection |
| Degree of protection (Dimensions) | IP20 |
| Output voltage range (Input data) | 12 V DC ... 140 V DC (t < 1 s = 1.40 x UN) |
| Rated insulation voltage (General) | 160 V DC |
| Output nominal voltage (Input data) | 110 V DC |
| Weight per Piece (excluding packing) | 33.490 g |
| Surge voltage protection (Input data) | > 150 V |
| China RoHS (Standards and Regulations) | Environmentally Friendly Use Period = 50 |
| REACh SVHC (Standards and Regulations) | Lead 7439-92-1 |
| Type of protection (Ambient conditions) | Reverse polarity protection |
| Input voltage range (Ambient conditions) | 77 V DC ... 137.5 V DC |
| Limiting continuous current (Input data) | 3 A (see derating curve) |
| Conductor cross section AWG (Output data) | 26 ... 14 |
| Protective circuit/component (Input data) | Parallel polarity protection diode |
| Connection in acc. with standard (General) | CUL |
| Designation (Connection data, output side) | Air clearances and creepage distances between the power circuits |
| Typical response time (Ambient conditions) | 400 µs |
| Typical turn-off time (Ambient conditions) | 200 µs |
| Conductor cross section solid (Output data) | 0.14 mm² ... 2.5 mm² |
| Transmission frequency (Ambient conditions) | 300 Hz |
| Ambient temperature (operation) (Dimensions) | -25 °C ... 70 °C |
| Connection name (Connection data, input side) | Output side |
| Nominal input voltage UN (Ambient conditions) | 110 V DC |
| Operating mode (Connection data, output side) | 100% operating factor |
| Surge voltage protection (Ambient conditions) | > 150 V |
| Utilization restriction (Key Commercial Data) | EMC: class A product, see manufacturer's declaration in the download area |
| Conductor cross section flexible (Output data) | 0.14 mm² ... 2.5 mm² |
| Operating voltage display (Ambient conditions) | Yellow LED |
| Stripping length (Connection data, input side) | 8 mm |
| Connection method (Connection data, input side) | Spring-cage connection |
| Mounting position (Connection data, output side) | any |
| Typical input current at UN (Ambient conditions) | 5.5 mA |
| Protective circuit/component (Ambient conditions) | Series polarity protection diode |
| Degree of pollution (Connection data, output side) | 2 |
| Overvoltage category (Connection data, output side) | III |
| Ambient temperature (storage/transport) (Dimensions) | -40 °C ... 85 °C |
| Assembly instructions (Connection data, output side) | In rows with zero spacing |
| Standards/regulations (Connection data, output side) | IEC 60664 |
| Test voltage input/output (Connection data, output side) | 2.5 kVrms |
| Conductor cross section AWG (Connection data, input side) | 26 ... 14 |
| Conductor cross section solid (Connection data, input side) | 0.14 mm² ... 2.5 mm² |
| Input voltage range in reference to UN (Ambient conditions) | 0.7 ... 1.25 (t < 1 s = 0.6 ... 1.4 x UN) |
| Power dissipation for nominal condition (Ambient conditions) | 0.61 W |
| Voltage drop at max. limiting continuous current (Input data) | < 150 mV |
| Conductor cross section flexible (Connection data, input side) | 0.14 mm² ... 2.5 mm² |
| Switching threshold "0" signal in reference to UN (Ambient conditions) | < 0.3 |
| Switching threshold "1" signal in reference to UN (Ambient conditions) | > 0.6 |
Technical specifications and performance data
Installation and operation guide