| Parameter | Value |
|---|---|
| Free-wheeling diode | |
| Depth | 94 mm |
| Width | 6.2 mm |
| Height | 80 mm |
| Operating mode | 100% operating factor |
| Output circuit | 2-wire, floating |
| Connection name | Input side |
| Pollution degree | 2 |
| Stripping length | 8 mm |
| Connection method | Push-in connection |
| Mounting position | any |
| Type of protection | Protection against polarity reversal |
| Output voltage range | 3 V DC ... 33 V DC |
| Overvoltage category | III |
| Assembly instructions | In rows with zero spacing |
| Typical response time | 30 µs (at UN) |
| Typical turn-off time | 300 µs (at UN) |
| Maximum inrush current | 15 A (10 ms) |
| Transmission frequency | 300 Hz |
| Nominal input voltage UN | 48 V DC |
| Operating voltage display | Yellow LED |
| Test voltage input/output | 2.5 kV (50 Hz, 1 min.) |
| Conductor cross section AWG | 26 ... 14 |
| Limiting continuous current | 3 A (see derating curve) |
| Typical input current at UN | 9 mA |
| Protective circuit/component | Polarity protection diode |
| Conductor cross section solid | 0.14 mm² ... 2.5 mm² |
| Ambient temperature (operation) | -25 °C ... 60 °C |
| Conductor cross section flexible | 0.14 mm² ... 2.5 mm² |
| Flammability rating according to UL 94 | V0 |
| Input voltage range in reference to UN | 0.8 ... 1.2 |
| Ambient temperature (storage/transport) | -25 °C ... 70 °C |
| Voltage drop at max. limiting continuous current | ≤ 200 mV |
| Switching threshold "0" signal in reference to UN | ≤ 0.4 |
| Switching threshold "1" signal in reference to UN | ≥ 0.8 |
Technical specifications and performance data
Installation and operation guide