| Parameter | Value |
|---|---|
| Surge protection | |
| Depth | 95 mm |
| Width | 6.2 mm |
| Height | 80 mm |
| Insulation | Basic insulation |
| Application | Output function |
| Designation | Output data |
| Product type | Solid-state relay module |
| Mounting type | DIN rail mounting |
| Identification | ISA-S71.04. G3 Harsh Group |
| Operating mode | 100% operating factor |
| Output circuit | 2-conductor, zero voltage switch |
| Product family | PLC-INTERFACE |
| Status display | Yellow LED |
| Leakage current | < 3 mA |
| Max. load value | 340 A2s (tp = 10 ms, at 25 °C) |
| Pollution degree | 2 |
| Stripping length | 10 mm |
| Connection method | Push-in connection |
| Min. load current | 10 mA |
| Mounting position | any |
| Protective circuit | Reverse polarity protection |
| Input voltage range | 19.2 V DC ... 28.8 V DC |
| Rated surge voltage | 4 kV |
| Degree of protection | IP20 |
| Output voltage range | 24 V AC ... 253 V AC |
| Overvoltage category | III |
| Assembly instructions | in rows with zero spacing |
| Standards/regulations | IEC 60947-5-1 |
| Typical response time | 10 ms (at UC) |
| Typical turn-off time | 10 ms (at UC) |
| Contact switching type | 1 N/O contact |
| Maximum inrush current | 250 A (20 ms) |
| Transmission frequency | 10 Hz |
| Contact connection type | Power contact |
| Design of digital output | electronic |
| Rated insulation voltage | 260 V AC |
| Surge voltage protection | > 33 V |
| Rated actuating current IC | 8 mA |
| Rated actuating voltage UC | 24 V DC |
| Conductor cross section AWG | 26 ... 14 |
| Limiting continuous current | 2.4 A (see to derating) |
| Test voltage (Input/output) | 2.5 kV (50 Hz, 1 min., input/output) |
| Conductor cross section rigid | 0.14 mm² ... 2.5 mm² |
| Ambient temperature (operation) | -25 °C ... 60 °C |
| Conductor cross section flexible | 0.14 mm² ... 2.5 mm² |
| Voltage range with reference to UC | 0.8 ... 1.2 |
| Flammability rating according to UL 94 | V0 (Housing) |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Maximum power dissipation for nominal condition | 0.19 W |
| Voltage drop at max. limiting continuous current | < 1 V |
| "0" signal switching threshold in reference to UC | < 0.4 |
| "1" signal switching threshold in reference to UC | > 0.8 |
Technical specifications and performance data
Installation and operation guide