| Parameter | Value |
|---|---|
| GTIN | 4046356927567 |
| Orderkey | 2905214 |
| Catalog page | Page 409 (C-5-2017) |
| Depth (Note) | 94 mm |
| Packing unit | 1 pc |
| Width (Note) | 14 mm |
| Height (Note) | 80 mm |
| Country of origin | DE (Germany) |
| Custom tariff number | 85364190 |
| Insulation (General) | safe isolation |
| (Ambient conditions) | Surge protection |
| Designation (General) | Air clearances and creepage distances between the power circuits |
| Designation (Input data) | AC hybrid output |
| Surge current (Input data) | 250 A (tp = 20 ms, at 25°C) |
| Output circuit (Input data) | 2-wire, floating |
| (Standards and Regulations) | For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |
| Leakage current (Input data) | < 1 mA |
| Max. load value (Input data) | 350 A2s (tp = 10 ms, at 25 °C) |
| Connection name (Output data) | Input side |
| Degree of pollution (General) | 2 |
| Rated surge voltage (General) | 6 kV |
| Min. load current (Input data) | 100 mA |
| Overvoltage category (General) | III |
| Connection method (Output data) | Screw connection |
| Standards/regulations (General) | DIN EN 50178 |
| Type of protection (Input data) | RCV circuit |
| Degree of protection (Dimensions) | IP20 |
| Output voltage range (Input data) | 24 V AC ... 253 V AC (50/60 Hz) |
| Rated insulation voltage (General) | 260 V AC |
| Status display (Ambient conditions) | Yellow LED |
| Weight per Piece (excluding packing) | 63.060 g |
| Surge voltage protection (Input data) | > 275 V |
| China RoHS (Standards and Regulations) | Environmentally Friendly Use Period = 50 |
| REACh SVHC (Standards and Regulations) | Lead 7439-92-1 |
| Type of protection (Ambient conditions) | Reverse polarity protection |
| Input voltage range (Ambient conditions) | 19.2 V DC ... 28.8 V DC |
| Limiting continuous current (Input data) | 10 A (see derating curve) |
| Conductor cross section AWG (Output data) | 26 ... 14 |
| Designation (Connection data, output side) | Air clearances and creepage distances between the power circuits |
| Typical response time (Ambient conditions) | 30 ms |
| Typical turn-off time (Ambient conditions) | 20 ms |
| Conductor cross section solid (Output data) | 0.14 mm² ... 2.5 mm² |
| Transmission frequency (Ambient conditions) | 1 Hz |
| Ambient temperature (operation) (Dimensions) | -25 °C ... 60 °C |
| Connection name (Connection data, input side) | Output side |
| Operating mode (Connection data, output side) | 100% operating factor |
| Surge voltage protection (Ambient conditions) | > 33 V DC |
| Utilization restriction (Key Commercial Data) | EMC: class A product, see manufacturer's declaration in the download area |
| Conductor cross section flexible (Output data) | 0.14 mm² ... 2.5 mm² |
| Connection method (Connection data, input side) | Screw connection |
| Rated actuating voltage UC (Ambient conditions) | 24 V DC |
| Mounting position (Connection data, output side) | any |
| Degree of pollution (Connection data, output side) | 2 |
| Overvoltage category (Connection data, output side) | III |
| Ambient temperature (storage/transport) (Dimensions) | -40 °C ... 85 °C |
| Assembly instructions (Connection data, output side) | See derating curve |
| Rated control supply current IS (Ambient conditions) | 14 mA (Input low, output low) |
| Standards/regulations (Connection data, output side) | DIN EN 50178 |
| Conductor cross section AWG (Connection data, input side) | 26 ... 14 |
| Conductor cross section solid (Connection data, input side) | 0.14 mm² ... 2.5 mm² |
| Power dissipation for nominal condition (Ambient conditions) | 0.16 W |
| Rated control circuit supply voltage US (Ambient conditions) | 24 V DC |
| Conductor cross section flexible (Connection data, input side) | 0.14 mm² ... 2.5 mm² |
| "0" signal switching threshold in reference to UC (Ambient conditions) | < 0.4 |
| "1" signal switching threshold in reference to UC (Ambient conditions) | > 0.8 |
Technical specifications and performance data