| Parameter | Value |
|---|---|
| GTIN | 4055626155517 |
| Note | Made to Order (non-returnable) |
| Orderkey | 2906920 |
| Catalog page | Page 431 (C-5-2017) |
| Packing unit | 1 pc |
| (Input data) | 4 mA ... 20 mA |
| Country of origin | DE (Germany) |
| Input name (Supply) | Digital input |
| Ripple (Input data) | < 20 mVPP |
| Custom tariff number | 85389099 |
| (Ambient conditions) | Surge protection |
| Screw thread (General) | M3 |
| Output name (Input data) | Analog output for current |
| Stripping length (General) | 8 mm |
| Connection method (General) | Screw connection |
| Depth (Key Commercial Data) | 86 mm |
| Width (Key Commercial Data) | 6.2 mm |
| (Standards and Regulations) | For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |
| Height (Key Commercial Data) | 80 mm |
| Insulation (Connection data) | Basic insulation |
| Operating mode (Output data) | 100% operating factor |
| Conformance (Connection data) | CE-compliant |
| Designation (Connection data) | Air clearances and creepage distances |
| Output protection (Input data) | |
| Indication (Ambient conditions) | Red LED |
| Mounting position (Output data) | any |
| Number of connections (General) | 4 |
| UL, USA/Canada (Connection data) | UL 508 Listed |
| Current output signal (Input data) | 0 mA ... 20 mA |
| Degree of protection (Output data) | IP20 |
| Voltage output signal (Input data) | 0 V ... 10 V |
| Assembly instructions (Output data) | In rows with zero spacing |
| Maximum output current (Input data) | 24.6 mA |
| Maximum output voltage (Input data) | 12.3 V |
| Weight per Piece (excluding packing) | 50.300 g |
| Conductor cross section AWG (General) | 26 ... 14 |
| Degree of pollution (Connection data) | 2 |
| Rated surge voltage (Connection data) | 0.5 kV |
| Surge voltage protection (Input data) | > 33 V |
| China RoHS (Standards and Regulations) | Environmentally Friendly Use Period = 50 |
| Overvoltage category (Connection data) | III |
| Conductor cross section solid (General) | 0.14 mm² ... 2.5 mm² |
| Maximum transmission error (Input data) | 1 % |
| Standards/regulations (Connection data) | DIN EN 50178 |
| Type of protection (Ambient conditions) | Reverse polarity protection |
| Conductor cross section flexible (General) | 0.14 mm² ... 2.5 mm² |
| Rated insulation voltage (Connection data) | 50 V |
| Ambient temperature (operation) (Dimensions) | -20 °C ... 50 °C |
| Load/output load current output (Input data) | 500 Ω (20 mA) |
| Load/output load voltage output (Input data) | 10 kΩ |
| Operating voltage display (Ambient conditions) | Green LED |
| Ambient temperature (storage/transport) (Dimensions) | -20 °C ... 70 °C |
| Rated control supply current IS (Ambient conditions) | ≤ 28 mA |
| Rated control circuit supply voltage US (Ambient conditions) | 24 V DC |
| Rated control supply voltage range with reference to US (Ambient conditions) | 0.8 ... 1.1 |
Technical specifications and performance data
Installation and operation guide