| Parameter | Value |
|---|---|
| GTIN | 4046356134842 |
| Note | Made to Order (non-returnable) |
| Orderkey | 2865201 |
| (General) | 0 (10 years) |
| Catalog page | Page 462 (IF-2009) |
| Depth (Note) | 147 mm |
| Packing unit | 1 pc |
| Width (Note) | 12.4 mm |
| Height (Note) | 145 mm |
| (Output data) | Seitz Pilot valve PV 12F73 Xi oH-2 |
| (Safety data) | IIC |
| λDD (General) | 0 |
| λDU (General) | 0 |
| λSD (General) | 0 |
| λSU (General) | 2.84 x 10-7(284 FIT) |
| (Power supply) | II 3 G Ex nA II T4 X |
| Country of origin | DE (Germany) |
| ATEX (Safety data) | II (1) GD [Ex ia] IIC / IIB / IIA |
| SIL (Power supply) | 3 |
| ATEX (Power supply) | II (1) GD [Ex ia] IIC / IIB / IIA |
| Group (Safety data) | IIA |
| Color (Power supply) | green |
| Custom tariff number | 85437090 |
| Equipment type (General) | Type A |
| Conformance (Safety data) | CE-compliant |
| Conformance (Power supply) | CE-compliant |
| Designation (Power supply) | Input/output |
| (Standards and Regulations) | For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |
| Status display (Power supply) | Yellow LED (status display) |
| Compatible valve (Output data) | Norgren Herion Coil 2080 / 2082 |
| Housing material (Power supply) | PBT and polyamide PA non-reinforced |
| Integrity requirement (General) | IEC 61508 - Low demand |
| Diagnostic coverage (DC) (General) | DCS=0 %, DCD=0 % |
| Group (Safety characteristic data) | IIC |
| Response time (Ambient conditions) | < 30 ms |
| Electrical isolation (Power supply) | 375 V (Peak value as per EN 50020 / EN 60079-11) |
| Weight per Piece (excluding packing) | 69.610 g |
| Power dissipation (Compatible valves) | max. 0.9 W (at 24 V) |
| Safe Failure Fraction (SFF) (General) | 100 % |
| China RoHS (Standards and Regulations) | Environmentally Friendly Use Period = 50 |
| Functional Safety (SIL) (Power supply) | SIL 3 |
| Safety Integrity Level (SIL) (General) | 3 |
| Ambient temperature (operation) (Dimensions) | -20 °C ... 55 °C |
| Max. current consumption (Compatible valves) | 50 mA (at 24 V) |
| Permissible humidity (operation) (Dimensions) | 10 % ... 95 % (relative humidity, non-condensing) |
| Utilization restriction (Key Commercial Data) | EMC: class A product, see manufacturer's declaration in the download area |
| Maximum temperature coefficient (Power supply) | 0.01 %/K |
| Max. output power Po (Safety characteristic data) | 245 mW |
| Max. output current Io (Safety characteristic data) | 39 mA |
| Max. output voltage Uo (Safety characteristic data) | 25.1 V |
| Ambient temperature (storage/transport) (Dimensions) | -40 °C ... 85 °C |
| Flammability rating according to UL 94 (Safety data) | V0 |
| Flammability rating according to UL 94 (Power supply) | V0 |
| Max. external capacity Co (Safety characteristic data) | 0.093 µF |
| Max. external inductivity Lo (Safety characteristic data) | 0.5 mH |
| Safety-related maximum voltage Um (Safety characteristic data) | 250 V AC (125 V DC) |
| Probability of a hazardous failure on demand (PFDAVG) (General) | 0 (1 year) |
| Output characteristic curve: Output resistor (Ambient conditions) | 654 Ω (Internal resistance Ri) |
Technical specifications and performance data