| Parameter | Value |
|---|---|
| GTIN | 4046356164290 |
| Orderkey | 2865243 |
| Catalog page | Page 264 (NTK-2010) |
| Depth (Note) | 147 mm |
| Packing unit | 1 pc |
| Width (Note) | 12.4 mm |
| (Input data) | ≥ 24 mA (Cable short-circuit in the input) |
| Height (Note) | 145 mm |
| (Safety data) | IIC |
| (Power supply) | II 3 (1) G Ex nA [ia] IIC T4 |
| Country of origin | DE (Germany) |
| ATEX (Safety data) | II (1) G [Ex ia] IIC |
| SIL (Power supply) | 2 |
| ATEX (Power supply) | II (1) G [Ex ia] IIC |
| Group (Safety data) | IIB |
| Color (Power supply) | green |
| Custom tariff number | 85437090 |
| (Ambient conditions) | > 15.3 V (at 22.5 mA) |
| HART function (General) | Yes |
| Conformance (Safety data) | CE-compliant, additionally EN 61326 |
| Conformance (Power supply) | CE-compliant, additionally EN 61326 |
| Designation (Power supply) | Input/power supply |
| Output ripple (Input data) | < 20 mVrms |
| Signal output (Input data) | Current output |
| (Standards and Regulations) | For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |
| Protocols supported (General) | HART |
| Status display (Power supply) | Green LED (supply voltage, PWR) |
| (Data communication (bypass)) | 8.41 x 10-4(5 years) |
| No. of channels (Power supply) | 1 |
| Housing material (Power supply) | PBT and polyamide PA non-reinforced |
| Power dissipation (Output data) | < 1.1 W (at 24 V DC / 20 mA) |
| Signal input (Ambient conditions) | Intrinsically safe |
| Current output signal (Input data) | 4 mA ... 20 mA (active) |
| Degree of pollution (Power supply) | 2 |
| Group (Safety characteristic data) | IIC |
| Supply voltage range (Output data) | 19.2 V DC ... 30 V DC |
| λDD (Data communication (bypass)) | 2.44 x 10-7(244 FIT) |
| λDU (Data communication (bypass)) | 3.8 x 10-8(38 FIT) |
| λSD (Data communication (bypass)) | 0 |
| λSU (Data communication (bypass)) | 1.52 x 10-7(152 FIT) |
| Electrical isolation (Power supply) | 375 V (Peak value in accordance with EN 60079-11) |
| Overvoltage category (Power supply) | II |
| Weight per Piece (excluding packing) | 97.300 g |
| Step response (10-90%) (Power supply) | < 600 µs (for 4 mA ... 20 mA step) |
| China RoHS (Standards and Regulations) | Environmentally Friendly Use Period = 50 |
| Functional Safety (SIL) (Power supply) | SIL 2 according to IEC 61508 |
| Max. current consumption (Output data) | < 60 mA (at 24 V DC) |
| REACh SVHC (Standards and Regulations) | Lead 7439-92-1 |
| Current input signal (Ambient conditions) | 4 mA ... 20 mA |
| Designation (Data communication (bypass)) | Input isolating amplifier (4 ... 20 mA) |
| Maximum transmission error (Power supply) | < 0.1 % (of final value) |
| Transmission error, typical (Power supply) | < 0.05 % (of final value) |
| Ambient temperature (operation) (Dimensions) | -20 °C ... 60 °C |
| Equipment type (Data communication (bypass)) | Type A |
| Load/output load current output (Input data) | < 600 Ω (at 20 mA) |
| Permissible humidity (operation) (Dimensions) | 10 % ... 95 % (non-condensing) |
| Utilization restriction (Key Commercial Data) | EMC: class A product, see manufacturer's declaration in the download area |
| Maximum temperature coefficient (Power supply) | < 0.01 %/K |
| Transmitter supply voltage (Ambient conditions) | > 16 V (at 20 mA) |
| Max. output power Po (Safety characteristic data) | 590 mW |
| Integrity requirement (Data communication (bypass)) | IEC 61508 - Low demand |
| Max. output current Io (Safety characteristic data) | 93 mA |
| Max. output voltage Uo (Safety characteristic data) | 25.2 V |
| Ambient temperature (storage/transport) (Dimensions) | -40 °C ... 80 °C |
| Flammability rating according to UL 94 (Safety data) | V0 |
| Flammability rating according to UL 94 (Power supply) | V0 |
| Output behavior in the event of an error (Input data) | 0 mA (Cable break in the input) |
| Diagnostic coverage (DC) (Data communication (bypass)) | DCS= 0%, DCD= 86% |
| Max. external capacity Co (Safety characteristic data) | 107 nF |
| Max. external inductivity Lo (Safety characteristic data) | 2 mH |
| Safe Failure Fraction (SFF) (Data communication (bypass)) | 91.2 % |
| Safety Integrity Level (SIL) (Data communication (bypass)) | 2 |
| Safety-related maximum voltage Um (Safety characteristic data) | 253 V AC |
| Probability of a hazardous failure on demand (PFDAVG) (Data communication (bypass)) | 1.81 x 10-4(1 year) |