| Parameter | Value |
|---|---|
| GTIN | 4046356483605 |
| Note | Made to Order (non-returnable) |
| Orderkey | 2865696 |
| Catalog page | Page 265 (NTK-2010) |
| Depth (Note) | 147 mm |
| Packing unit | 1 pc |
| Width (Note) | 12.4 mm |
| (Input data) | 0 mA (Cable short-circuit in the input) |
| Height (Note) | 145 mm |
| (Safety data) | II 3 (1) G Ex nA [ia] IIC T4 |
| (Power supply) | II 3 (1) G Ex nA [ia] IIC T4 |
| Country of origin | DE (Germany) |
| ATEX (Safety data) | II (1) G [Ex ia] IIC |
| SIL (Power supply) | 2 |
| ATEX (Power supply) | II (1) G [Ex ia] IIC |
| Color (Power supply) | green |
| Custom tariff number | 85437090 |
| (Ambient conditions) | 4 mA ... 20 mA |
| HART function (General) | Yes |
| Conformance (Safety data) | CE-compliant, additionally EN 61326 |
| Conformance (Power supply) | CE-compliant, additionally EN 61326 |
| Designation (Power supply) | Input/power supply |
| Output ripple (Input data) | < 20 mVrms |
| Signal output (Input data) | Current output |
| (Standards and Regulations) | For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |
| Protocols supported (General) | HART |
| Status display (Power supply) | Green LED (supply voltage, PWR) |
| (Data communication (bypass)) | 7.52 x 10-4(5 years) |
| No. of channels (Power supply) | 1 |
| Housing material (Power supply) | PBT and polyamide PA non-reinforced |
| Power dissipation (Output data) | < 0.9 W (at 24 V DC / 20 mA) |
| Signal input (Ambient conditions) | Intrinsically safe |
| Voltage drop (Ambient conditions) | < 3.5 V |
| Current output signal (Input data) | 0 mA ... 20 mA (active) |
| Degree of pollution (Power supply) | 2 |
| Supply voltage range (Output data) | 19.2 V DC ... 30 V DC |
| λDD (Data communication (bypass)) | 2.05 x 10-7(205 FIT) |
| λDU (Data communication (bypass)) | 3.4 x 10-8(34 FIT) |
| λSD (Data communication (bypass)) | 0 |
| λSU (Data communication (bypass)) | 1.23 x 10-7(123 FIT) |
| Electrical isolation (Power supply) | 375 V (Peak value in accordance with EN 60079-11) |
| Overvoltage category (Power supply) | II |
| Weight per Piece (excluding packing) | 93.900 g |
| Step response (10-90%) (Power supply) | < 600 µs (for 4 mA ... 20 mA step) |
| China RoHS (Standards and Regulations) | Environmentally Friendly Use Period = 50 |
| Functional Safety (SIL) (Power supply) | SIL 2 according to IEC 61508 |
| Max. current consumption (Output data) | < 36 mA (at 24 V) |
| Current input signal (Ambient conditions) | 0 mA ... 20 mA |
| Maximum transmission error (Power supply) | < 0.2 % (of final value) |
| Transmission error, typical (Power supply) | < 0.1 % (of final value) |
| Ambient temperature (operation) (Dimensions) | -20 °C ... 60 °C |
| Equipment type (Data communication (bypass)) | Type A |
| Load/output load current output (Input data) | ≤ 600 Ω (at 20 mA) |
| Permissible humidity (operation) (Dimensions) | 10 % ... 95 % (non-condensing) |
| Utilization restriction (Key Commercial Data) | EMC: class A product, see manufacturer's declaration in the download area |
| Maximum temperature coefficient (Power supply) | < 0.01 %/K |
| Integrity requirement (Data communication (bypass)) | IEC 61508 - Low demand |
| Ambient temperature (storage/transport) (Dimensions) | -40 °C ... 80 °C |
| Flammability rating according to UL 94 (Safety data) | V0 |
| Flammability rating according to UL 94 (Power supply) | V0 |
| Output behavior in the event of an error (Input data) | 0 mA (Cable break in the input) |
| Diagnostic coverage (DC) (Data communication (bypass)) | DCS= 0%, DCD= 86% |
| Safe Failure Fraction (SFF) (Data communication (bypass)) | 90.5 % |
| Safety Integrity Level (SIL) (Data communication (bypass)) | 2 |
| Safety-related maximum voltage Um (Safety characteristic data) | 253 V AC |
| Probability of a hazardous failure on demand (PFDAVG) (Data communication (bypass)) | 1.62 x 10-4(1 year) |
Technical specifications and performance data
Installation and operation guide