| Parameter | Value |
|---|---|
| GTIN | 4017918819347 |
| Orderkey | 2742638 |
| Catalog page | Page 255 (AX-2009) |
| Depth (Note) | 71.5 mm |
| Packing unit | 1 pc |
| Width (Note) | 182.6 mm |
| (Interfaces) | max. 176 Byte (Output) |
| Height (Note) | 140.5 mm |
| Country of origin | DE (Germany) |
| (Digital outputs) | RS-485 interface / local bus 500 V AC |
| Custom tariff number | 85389091 |
| Designation (General) | Supply |
| (Electrical isolation) | Shock in acc. with EN 60068-2-27/IEC 60068-2-27 Operation: 25g, 11 ms duration, semi-sinusoidal shock impulse |
| No. of channels (General) | 1 |
| Dimensional drawing (Note) | |
| Connection method (General) | 8-pos. Inline power connector |
| (Standards and Regulations) | For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |
| Output name (Digital inputs) | Digital outputs |
| Transmission speed (General) | 500 kbps |
| Input name (Inline potentials) | Digital inputs |
| Test section (Digital outputs) | RS-485 interface / supply voltage 500 V AC |
| Net weight (Ambient conditions) | 395 g |
| Output voltage (Digital inputs) | 24 V DC -1 V (At nominal current) |
| Degree of protection (Dimensions) | IP20 |
| Input voltage (Inline potentials) | 24 V DC |
| Connection method (Digital inputs) | Spring-cage connection |
| Mounting type (Ambient conditions) | DIN rail |
| Number of outputs (Digital inputs) | 16 |
| (System limits of the bus coupler) | max. 1.25 A (with max. number of connected I/O terminal blocks) |
| Amount of process data (Interfaces) | max. 176 Byte (per station) |
| Nominal load, lamp (Digital inputs) | 12 W |
| Type of protection (Digital inputs) | Short-circuit and overload protection |
| Nominal load, ohmic (Digital inputs) | 12 W |
| Number of inputs (Inline potentials) | 16 |
| Weight per Piece (excluding packing) | 395.000 g |
| Air pressure (operation) (Dimensions) | 80 kPa ... 106 kPa (up to 3000 m above sea level) |
| Connection method (Inline potentials) | Spring-cage connection |
| China RoHS (Standards and Regulations) | Environmentally Friendly Use Period = 50 |
| Connection technology (Digital inputs) | 3-wire |
| Type of protection (Inline potentials) | Polarity reversal |
| Mechanical tests (Electrical isolation) | Vibration resistance in acc. with EN 60068-2-6/IEC 60068-2-6 5g |
| Nominal output voltage (Digital inputs) | 24 V DC |
| Nominal load, inductive (Digital inputs) | 12 VA |
| Connection technology (Inline potentials) | 3-wire |
| Ambient temperature (operation) (Dimensions) | 0 °C ... 55 °C |
| Description of the input (Inline potentials) | EN 61131-2 type 1 |
| Air pressure (storage/transport) (Dimensions) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Permissible humidity (operation) (Dimensions) | 95 % (non-condensing) |
| Utilization restriction (Key Commercial Data) | 1 |
| Designation (System limits of the bus coupler) | Segment circuit supply (US) |
| Supply voltage (System limits of the bus coupler) | 24 V DC (via voltage jumper) |
| Input voltage range "1" signal (Inline potentials) | 15 V DC ... 30 V DC |
| Maximum output current per module (Digital inputs) | 8 A |
| Note on weight specifications (Ambient conditions) | with connectors |
| Maximum output current per channel (Digital inputs) | 500 mA |
| Power supply unit (System limits of the bus coupler) | max. 8 A DC (sum of UM+ US) |
| Number of devices with parameter channel (Interfaces) | max. 16 |
| Permissible humidity (storage/transport) (Dimensions) | 95 % (non-condensing) |
| Typical input current per channel (Inline potentials) | typ. 3 mA |
| Current consumption (System limits of the bus coupler) | typ. 100 mA (without connected Inline I/O terminals) |
| Supply voltage range (System limits of the bus coupler) | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
| Number of local bus devices that can be connected (Interfaces) | max. 63 |
| Number of supported branch terminals with remote bus branch (Interfaces) | 0 |
Technical specifications and performance data
Installation and operation guide