| Parameter | Value |
|---|---|
| Note | Please observe the current carrying capacity of the DIN rails. |
| Color | green-yellow |
| Width | 5.2 mm |
| Height | 22 mm |
| Length | 42.7 mm |
| ASD level | 0.02 g²/Hz |
| Shock form | Half-sine |
| Acceleration | 0.8g |
| Test spectrum | Service life test category 1, class B, body mounted |
| Shock duration | 30 ms |
| Test frequency | f1= 5 Hz to f2= 150 Hz |
| End cover width | 4 mm |
| Height NS 35/15 | 39.5 mm |
| Open side panel | JA |
| Test directions | X-, Y- and Z-axis |
| Height NS 35/7,5 | 32 mm |
| Number of levels | 1 |
| Pollution degree | 3 |
| Stripping length | 8 mm |
| Connection method | Spring-cage connection |
| Finger protection | guaranteed |
| Shock test result | Test passed |
| Insulating material | PA |
| Rated surge voltage | 8 kV |
| Overvoltage category | III |
| Nominal cross section | 2.5 mm² |
| Number of connections | 2 |
| Test duration per axis | 5 h |
| Insulating material group | I |
| Internal cylindrical gage | A3 |
| Back of the hand protection | guaranteed |
| Number of shocks per direction | 3 |
| Test specification, shock test | DIN EN 50155 (VDE 0115-200):2008-03 |
| Conductor cross section AWG max. | 12 |
| Conductor cross section AWG min. | 28 |
| Connection in acc. with standard | IEC 60947-7-2 |
| Conductor cross section solid max. | 4 mm² |
| Conductor cross section solid min. | 0.08 mm² |
| Shock protection test specification | DIN EN 50274 (VDE 0660-514):2002-11 |
| Conductor cross section flexible max. | 2.5 mm² |
| Conductor cross section flexible min. | 0.08 mm² |
| Flammability rating according to UL 94 | V0 |
| Oscillation, broadband noise test result | Test passed |
| Max. AWG conductor cross section, flexible | 14 |
| Min. AWG conductor cross section, flexible | 28 |
| Static insulating material application in cold | -60 °C |
| Test specification, oscillation, broadband noise | DIN EN 50155 (VDE 0115-200):2008-03 |
| Relative insulation material temperature index (Elec., UL 746 B) | 130 °C |
| Conductor cross section flexible, with ferrule with plastic sleeve max. | 2.5 mm² |
| Conductor cross section flexible, with ferrule with plastic sleeve min. | 0.14 mm² |
| Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21)) | 130 °C |
| Conductor cross section flexible, with ferrule without plastic sleeve max. | 2.5 mm² |
| Conductor cross section flexible, with ferrule without plastic sleeve min. | 0.14 mm² |
| 2 conductors with same cross section, stranded, TWIN ferrules with plastic sleeve, max. | 0.5 mm² |
Technical specifications and performance data
Installation and operation guide