| Parameter | Value |
|---|---|
| GTIN | 4046356701990 |
| Orderkey | 2200855 |
| Packing unit | 1 |
| (Connection data) | CUL |
| Custom tariff number | 85369010 |
| Screw thread (Dimensions) | M3 |
| (Standards and Regulations) | For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |
| Stripping length (Dimensions) | 8 mm |
| Nominal current IN (Dimensions) | 24 A |
| Rated voltage (II/2) (Dimensions) | 1000 V |
| Nominal cross section (Dimensions) | 2.5 mm² |
| Rated voltage (III/2) (Dimensions) | 630 V |
| Rated voltage (III/3) (Dimensions) | 600 V |
| Tightening torque max (Dimensions) | 0.6 Nm |
| Hole diameter (Key Commercial Data) | 1.4 mm |
| Tightening torque, min (Dimensions) | 0.5 Nm |
| China RoHS (Standards and Regulations) | Environmentally Friendly Use Period = 50 |
| Internal cylindrical gage (Dimensions) | A2 |
| Rated surge voltage (II/2) (Dimensions) | 6 kV |
| Rated surge voltage (III/2) (Dimensions) | 6 kV |
| Rated surge voltage (III/3) (Dimensions) | 6 kV |
| Conductor cross section AWG max. (General) | 14 |
| Conductor cross section AWG min. (General) | 24 |
| Connection in acc. with standard (Dimensions) | EN-VDE |
| Connection in acc. with standard (Connection data) | EN-VDE |
| 2 conductors with same cross section, solid max. (General) | 0.75 mm² |
| 2 conductors with same cross section, solid min. (General) | 0.2 mm² |
| 2 conductors with same cross section, stranded max. (General) | 0.75 mm² |
| 2 conductors with same cross section, stranded min. (General) | 0.25 mm² |
| 2 conductors with same cross section, stranded, ferrules without plastic sleeve, max. (General) | 0.75 mm² |
| 2 conductors with same cross section, stranded, ferrules without plastic sleeve, min. (General) | 0.25 mm² |
| 2 conductors with same cross section, stranded, TWIN ferrules with plastic sleeve, max. (General) | 1.5 mm² |
| 2 conductors with same cross section, stranded, TWIN ferrules with plastic sleeve, min. (General) | 0.25 mm² |
Technical specifications and performance data
Installation and operation guide