| Parameter | Value |
|---|---|
| Pitch | 7.62 mm |
| Width | 22.86 mm |
| Height | 26.6 mm |
| Length | 12.5 mm |
| Dimension a | 15.24 mm |
| Screw thread | M3 |
| Hole diameter | 1.3 mm |
| Pin dimensions | 0,9 x 0,9 mm |
| Stripping length | 8 mm |
| Range of articles | MKDS 5 |
| Nominal current IN | 32 A |
| Solder pin surface | Sn |
| Insulating material | PA |
| Number of positions | 3 |
| Maximum load current | 32 A (with 6 mm² conductor cross section) |
| Rated voltage (II/2) | 1000 V |
| Constructional height | 21.5 mm |
| Nominal cross section | 4 mm² |
| Rated voltage (III/2) | 630 V |
| Rated voltage (III/3) | 500 V |
| Tightening torque max | 0.6 Nm |
| Tightening torque, min | 0.5 Nm |
| Length of the solder pin | 5.1 mm |
| Insulating material group | I |
| Internal cylindrical gage | A4 |
| Rated surge voltage (II/2) | 6 kV |
| Rated surge voltage (III/2) | 6 kV |
| Rated surge voltage (III/3) | 6 kV |
| Conductor cross section AWG max. | 10 |
| Conductor cross section AWG min. | 24 |
| Connection in acc. with standard | EN-VDE |
| Conductor cross section solid max. | 6 mm² |
| Conductor cross section solid min. | 0.2 mm² |
| Conductor cross section flexible max. | 4 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Flammability rating according to UL 94 | V0 |
| 2 conductors with same cross section, solid max. | 1.5 mm² |
| 2 conductors with same cross section, solid min. | 0.2 mm² |
| 2 conductors with same cross section, stranded max. | 1.5 mm² |
| 2 conductors with same cross section, stranded min. | 0.2 mm² |
| Conductor cross section flexible, with ferrule with plastic sleeve max. | 4 mm² |
| Conductor cross section flexible, with ferrule with plastic sleeve min. | 0.25 mm² |
| Conductor cross section flexible, with ferrule without plastic sleeve max. | 4 mm² |
| Conductor cross section flexible, with ferrule without plastic sleeve min. | 0.25 mm² |
| 2 conductors with same cross section, stranded, ferrules without plastic sleeve, max. | 0.75 mm² |
| 2 conductors with same cross section, stranded, ferrules without plastic sleeve, min. | 0.25 mm² |
| 2 conductors with same cross section, stranded, TWIN ferrules with plastic sleeve, max. | 2.5 mm² |
| 2 conductors with same cross section, stranded, TWIN ferrules with plastic sleeve, min. | 0.5 mm² |
Technical specifications and performance data
Installation and operation guide