| Parameter | Value |
|---|---|
| GTIN | 4017918960902 |
| Orderkey | 2866284 |
| (Signaling) | UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D (Hazardous Location) |
| Catalog page | Page 256 (C-4-2017) |
| Packing unit | 1 pc |
| (Output data) | |
| Country of origin | CN (China) |
| Comments (Signaling) | Level 2 - asymmetrical cable to ground |
| Custom tariff number | 85044030 |
| (Ambient conditions) | typ. 20 ms (24 V DC) |
| Derating (Input data) | 60 °C ... 70 °C (2.5%/K) |
| Screw thread (General) | M3 |
| Efficiency (Output data) | > 83 % (at 24 V DC and nominal values) |
| Net weight (Output data) | 0.2 kg |
| UL approvals (Signaling) | UL/C-UL listed UL 508 |
| Output power (Input data) | 24 W |
| Noise emission (Signaling) | EN 55011 (EN 55022) |
| Noise immunity (Signaling) | EN 61000-6-2:2005 |
| Stripping length (General) | 7 mm |
| Connection method (General) | Pluggable screw connection |
| Depth (Key Commercial Data) | 107 mm |
| Frequency range (Signaling) | 0.15 MHz ... 80 MHz (10 V) |
| Width (Key Commercial Data) | 22.5 mm |
| (Standards and Regulations) | For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |
| Height (Key Commercial Data) | 99 mm |
| Residual ripple (Input data) | < 30 mVPP(20 MHz) |
| Contact discharge (Signaling) | 8 kV (Contact discharge) |
| Rail applications (Signaling) | EN 50121-4 |
| Protection class (Output data) | III |
| Input fuse (Ambient conditions) | 6.3 A (slow-blow, internal) |
| Mounting position (Output data) | horizontal DIN rail NS 35, EN 60715 |
| Test field strength (Signaling) | 10 V/m |
| Connection in series (Input data) | yes |
| Degree of protection (Dimensions) | IP20 |
| Low Voltage Directive (Signaling) | Conformance with LV directive 2006/95/EC |
| Shipbuilding approval (Signaling) | DNV GL (EMC A) |
| Standards/regulations (Signaling) | EN 61000-4-11 |
| Degree of protection (Output data) | IP20 |
| Typical response time (Input data) | < 0.5 s |
| Assembly instructions (Output data) | alignable: horizontally 0 mm, vertically 50 mm |
| Connection in parallel (Input data) | Yes, for assembling redundant systems and increasing efficiency |
| Nominal output voltage (Input data) | 24 V DC ±1 % |
| Mains buffering (Ambient conditions) | typ. 3 ms (12 V DC) |
| Weight per Piece (excluding packing) | 245.700 g |
| Output name (Connection data, output) | DC OK active |
| Screw thread (Connection data, input) | M3 |
| Standard - Safe isolation (Signaling) | DIN VDE 0100-410 |
| China RoHS (Standards and Regulations) | Environmentally Friendly Use Period = 25; |
| Screw thread (Connection data, output) | M3 |
| Frequency range DC (Ambient conditions) | 0 Hz |
| Operating voltage display (Output data) | Green LED |
| Current consumption (Ambient conditions) | 2.6 A (12 V DC) |
| Input voltage range (Ambient conditions) | 10 V DC ... 32 V DC |
| MTBF (IEC 61709, SN 29500) (Output data) | |
| Nominal output current (IN) (Input data) | 1 A (-25 °C ... 60 °C) |
| Output voltage (Connection data, output) | + 24 V (Signal) |
| Standard - Electrical safety (Signaling) | EN 60950-1/VDE 0805 (SELV) |
| Status display (Connection data, output) | "DC OK" LED green |
| Electromagnetic compatibility (Signaling) | Conformance with EMC Directive 2014/30/EU |
| Inrush surge current (Ambient conditions) | < 15 A (typical) |
| Power loss nominal load max. (Input data) | < 5 W |
| Stripping length (Connection data, input) | 7 mm |
| Conductor cross section AWG max. (General) | 14 |
| Conductor cross section AWG min. (General) | 24 |
| Connection method (Connection data, input) | Pluggable screw connection |
| Ambient temperature (operation) (Dimensions) | -25 °C ... 70 °C (> 60 °C Derating: 2.5 %/K) |
| Conductor cross section solid max. (General) | 2.5 mm² |
| Conductor cross section solid min. (General) | 0.2 mm² |
| Connection in acc. with standard (Signaling) | CUL |
| Output description (Connection data, output) | UOUT> 21.5 V: High signal |
| Insulation voltage input/output (Output data) | 1.5 kV (type test) |
| Conductor cross section flexible max. (General) | 2.5 mm² |
| Conductor cross section flexible min. (General) | 0.2 mm² |
| Tightening torque max (Connection data, output) | 0.6 Nm |
| Nominal input voltage range (Ambient conditions) | 12 V DC ... 24 V DC |
| Tightening torque, min (Connection data, output) | 0.5 Nm |
| Continuous load current (Connection data, output) | ≤ 20 mA |
| Peak switching voltages nominal load (Input data) | < 100 mVPP(20 MHz) |
| Maximum switching voltage (Connection data, output) | ≤ 24 V DC |
| Ambient temperature (storage/transport) (Dimensions) | -40 °C ... 85 °C |
| Setting range of the output voltage (USet) (Input data) | 22.5 V DC ... 28.5 V DC (> 24 V DC, constant capacity restricted) |
| Conductor cross section AWG max. (Connection data, input) | 14 |
| Conductor cross section AWG min. (Connection data, input) | 24 |
| Conductor cross section AWG max. (Connection data, output) | 14 |
| Conductor cross section AWG min. (Connection data, output) | 24 |
| Conductor cross section solid max. (Connection data, input) | 2.5 mm² |
| Conductor cross section solid min. (Connection data, input) | 0.2 mm² |
| Max. permissible relative humidity (operation) (Dimensions) | ≤ 95 % (at 25 °C, non-condensing) |
| Maximum power dissipation in no-load condition (Input data) | < 1.2 W |
| Conductor cross section solid max. (Connection data, output) | 2.5 mm² |
| Conductor cross section solid min. (Connection data, output) | 0.2 mm² |
| Conductor cross section flexible max. (Connection data, input) | 2.5 mm² |
| Conductor cross section flexible min. (Connection data, input) | 0.2 mm² |
| Conductor cross section flexible max. (Connection data, output) | 2.5 mm² |
| Conductor cross section flexible min. (Connection data, output) | 0.2 mm² |
| Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations (Signaling) | EN 50178/VDE 0160 (PELV) |
Technical specifications and performance data
Installation and operation guide