| Parameter | Value |
|---|---|
| GTIN | 4046356577731 |
| Orderkey | 2320199 |
| Catalog page | Page 257 (C-4-2017) |
| Packing unit | 1 pc |
| (Input data) | 60 V DC |
| Country of origin | CN (China) |
| Custom tariff number | 85044030 |
| Derating (Input data) | 60 °C ... 70 °C (2.5%/K) |
| Screw thread (General) | M3 |
| Efficiency (Output data) | > 95.7 % (For 42 V AC and nominal values) |
| Net weight (Output data) | 0.16 kg |
| (Connection data, output) | 15 Hz ...150 Hz, 2.3g |
| Stripping length (General) | 7 mm |
| Climatic class (Dimensions) | 3K3 (in acc. with EN 60721) |
| Connection method (General) | Pluggable screw connection |
| Depth (Key Commercial Data) | 107 mm |
| Width (Key Commercial Data) | 22.5 mm |
| (Standards and Regulations) | For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |
| Height (Key Commercial Data) | 99 mm |
| Residual ripple (Input data) | < 3.6 VPP |
| Protection class (Output data) | III |
| Mounting position (Output data) | horizontal DIN rail NS 35, EN 60715 |
| Shock (Connection data, output) | 18 ms, 30g, in each space direction (according to IEC 60068-2-27) |
| Degree of pollution (Dimensions) | 2 |
| Connection in series (Input data) | No |
| Degree of protection (Dimensions) | IP20 |
| Output voltage range (Input data) | 15 V DC ... 60 V DC |
| Comments (Connection data, output) | Criterion B |
| Degree of protection (Output data) | IP20 |
| Assembly instructions (Output data) | alignable: horizontally 0 mm, vertically 50 mm |
| Nominal output voltage (Input data) | 28 V DC ±1 % |
| Weight per Piece (excluding packing) | 160.000 g |
| Screw thread (Connection data, input) | M3 |
| China RoHS (Standards and Regulations) | Environmentally Friendly Use Period = 25; |
| UL approvals (Connection data, output) | UL/C-UL listed UL 508 |
| AC frequency range (Ambient conditions) | 45 Hz ... 65 Hz |
| Current consumption (Ambient conditions) | 6.5 A |
| Input voltage range (Ambient conditions) | 10 V AC ... 42 V AC |
| MTBF (IEC 61709, SN 29500) (Output data) | > 18175000 h (40 °C) |
| Noise emission (Connection data, output) | EN 55011 (EN 55022) |
| Noise immunity (Connection data, output) | EN 61000-6-2:2005 |
| Nominal output current (IN) (Input data) | 3 A (-25 °C ... 60 °C) |
| Frequency range (Connection data, output) | 80 MHz ... 3 GHz |
| Inrush surge current (Ambient conditions) | < 45 A (typical) |
| Power loss nominal load max. (Input data) | < 6.9 W |
| Stripping length (Connection data, input) | 7 mm |
| Conductor cross section AWG max. (General) | 12 |
| Conductor cross section AWG min. (General) | 24 |
| Connection method (Connection data, input) | Pluggable screw connection |
| Nominal input voltage (Ambient conditions) | 24 V AC |
| Contact discharge (Connection data, output) | 8 kV (Contact discharge) |
| Rail applications (Connection data, output) | EN 50121-4 |
| Ambient temperature (operation) (Dimensions) | -25 °C ... 70 °C (> 60 °C Derating: 2.5 %/K) |
| Conductor cross section solid max. (General) | 2.5 mm² |
| Conductor cross section solid min. (General) | 0.2 mm² |
| Test field strength (Connection data, output) | 10 V/m |
| Conductor cross section flexible max. (General) | 2.5 mm² |
| Conductor cross section flexible min. (General) | 0.2 mm² |
| Low Voltage Directive (Connection data, output) | Conformance with LV directive 2006/95/EC |
| Standards/regulations (Connection data, output) | EN 61000-4-4 |
| Vibration (operation) (Connection data, output) | < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6) |
| Nominal input voltage range (Ambient conditions) | 10 V AC ... 42 V AC |
| Ambient temperature (storage/transport) (Dimensions) | -40 °C ... 85 °C |
| Standard - Electrical safety (Connection data, output) | EN 60950-1/VDE 0805 (SELV) |
| Electromagnetic compatibility (Connection data, output) | Conformance with EMC Directive 2014/30/EU |
| Choice of suitable circuit breakers (Ambient conditions) | 16 A (Characteristic C) |
| Conductor cross section AWG max. (Connection data, input) | 12 |
| Conductor cross section AWG min. (Connection data, input) | 24 |
| Connection in acc. with standard (Connection data, output) | CUL |
| Conductor cross section solid max. (Connection data, input) | 2.5 mm² |
| Conductor cross section solid min. (Connection data, input) | 0.2 mm² |
| Max. permissible relative humidity (operation) (Dimensions) | ≤ 95 % (at 25 °C, non-condensing) |
| Maximum power dissipation in no-load condition (Input data) | < 0.04 W |
| Conductor cross section flexible max. (Connection data, input) | 2.5 mm² |
| Conductor cross section flexible min. (Connection data, input) | 0.2 mm² |
| Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations (Connection data, output) | EN 50178/VDE 0160 (PELV) |
Technical specifications and performance data
Installation and operation guide