Service time: Monday to Friday 9:00-18:00
MINI MCR-SL-U-I-0 - MINI MCR-SL-U-I-0 2813512 PHOENIX CONTACT MCR 3-way isolating amplifier, for electrical isolation of analog ..
In Stock Hot Product

MINI MCR-SL-U-I-0

MINI MCR-SL-U-I-0 2813512 PHOENIX CONTACT MCR 3-way isolating amplifier, for electrical isolation of analog ..

$0.00USD
4075 in stock
Key Specifications
:Class I, Div. 2, Groups A, B, C, D T5 applied for
GL:GL EMC 2 D
ATEX:Ex II 3 G Ex nA IIC T4 Gc X
Color:green
Supplier Information
Products: 0
Usually ships within 2-3 business days
Quality Guaranteed
Fast Shipping
Technical Support

Technical Specifications

ParameterValue
Class I, Div. 2, Groups A, B, C, D T5 applied for
GLGL EMC 2 D
ATEXEx II 3 G Ex nA IIC T4 Gc X
Colorgreen
Depth102.5 mm
Width6.2 mm
Height93.1 mm
ConformanceCE-compliant
DesignationElectromagnetic RF field
Screw threadM3
Noise emissionEN 61000-6-4
Noise immunityEN 61000-6-2 When being exposed to interference, there may be minimal deviations.
No. of channels1
Housing materialPBT
Number of inputs1
Pollution degree2
Stripping length12 mm
UL, USA / CanadaUL 508 Recognized
Connection methodScrew connection
Mounting positionany
Number of outputs1
Power consumption< 450 mW
Max. input voltage30 V
Max. output current28 mA
Degree of protectionIP20
Electrical isolationBasic insulation according to EN 61010
Overvoltage categoryII
Supply voltage range19.2 V DC ... 30 V DC (The DIN rail bus connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, Order No. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715))
Voltage input signal0 V ... 10 V
Assembly instructionsThe T connector can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715.
Current output signal0 mA ... 20 mA
Standards/regulationsEN 61000-4-3
Limit frequency (3 dB)approx. 100 Hz
Nominal supply voltage24 V DC
Step response (10-90%)approx. 3.5 ms
Max. current consumption< 20 mA
Rated insulation voltage50 V AC/DC
Configurable/programmableno
Maximum transmission error≤ 0.1 % (of final value)
Electromagnetic compatibilityConformance with EMC Directive 2004/108/EC
Ambient temperature (operation)-20 °C ... 65 °C
Load/output load current output≤ 500 Ω
Maximum temperature coefficient< 0.01 %/K
Conductor cross section AWG max.12
Conductor cross section AWG min.26
Temperature coefficient, typical< 0.002 %/K
Input resistance of voltage inputapprox. 100 kΩ
Test voltage, input/output/supply1.5 kV (50 Hz, 1 min.)
Conductor cross section solid max.2.5 mm²
Conductor cross section solid min.0.2 mm²
Conductor cross section flexible max.2.5 mm²
Conductor cross section flexible min.0.2 mm²
Ambient temperature (storage/transport)-40 °C ... 85 °C
Typical deviation from the measuring range final value5 %

Product Description

More details
Key Features
  • Industrial grade quality
  • RoHS compliant
  • CE certified
  • 1-year warranty

Technical Details

The 6.2 mm wide standard signal 3-way isolating amplifier MINI MCR-SL-U-I-... is used for electrical isolation, conversion, amplification and filtering of standard signals.

Product Documents

Datasheet

Technical specifications and performance data

User Manual

Installation and operation guide

Top