| Parameter | Value |
|---|---|
| GTIN | 4046356046459 |
| Orderkey | 2864105 |
| (EMC data) | Class I, Div. 2, Groups A, B, C, D T4 |
| Catalog page | Page 112 (C-7-2015) |
| Depth (Note) | 102.5 mm |
| Packing unit | 1 pc |
| Width (Note) | 6.2 mm |
| Height (Note) | 93.1 mm |
| ATEX (EMC data) | II 3 G Ex nA nC IIC T4 Gc X |
| Country of origin | DE (Germany) |
| (Connection data) | Class I, Div. 2, Groups A, B, C, D T4 |
| Custom tariff number | 85437090 |
| Designation (General) | Conducted interferences |
| ATEX (Connection data) | II 3 G Ex nA nC IIC T4 Gc X |
| Conformance (EMC data) | CE-compliant |
| Designation (EMC data) | Conducted interferences |
| Color (Connection data) | green |
| Noise emission (EMC data) | EN 61000-6-4 |
| UL, USA/Canada (EMC data) | UL 508 Recognized |
| Screw thread (Power supply) | M3 |
| (Standards and Regulations) | For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |
| Conformance (Connection data) | CE-compliant |
| Maximum altitude (Dimensions) | ≤ 2000 m |
| Evaluation criterion (General) | A |
| Electrical isolation (EMC data) | Reinforced insulation according to EN 61010-1 |
| Evaluation criterion (EMC data) | A |
| Standards/regulations (General) | EN 61000-4-6 |
| Stripping length (Power supply) | 12 mm |
| Connection method (Power supply) | Screw connection |
| Designation (Ambient conditions) | Supply |
| Noise emission (Connection data) | EN 61000-6-4 |
| Noise immunity (Connection data) | EN 61000-6-2 When being exposed to interference, there may be minimal deviations. |
| Standards/regulations (EMC data) | EN 61000-4-6 |
| Status display (Connection data) | Red LED (error messages) |
| UL, USA/Canada (Connection data) | UL 508 Recognized |
| No. of channels (Connection data) | 1 |
| Housing material (Connection data) | PBT |
| Mounting position (Connection data) | any |
| Weight per Piece (excluding packing) | 71.200 g |
| Degree of pollution (Connection data) | 2 |
| China RoHS (Standards and Regulations) | Environmentally Friendly Use Period = 50 |
| Electrical isolation (Connection data) | Reinforced insulation according to EN 61010-1 |
| Overvoltage category (Connection data) | II |
| Power consumption (Ambient conditions) | < 600 mW |
| Electromagnetic compatibility (EMC data) | Conformance with EMC directive |
| Supply voltage range (Ambient conditions) | 19.2 V DC ... 30 V DC (The DIN rail bus connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, Order No. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715)) |
| Rated insulation voltage (Connection data) | 150 V AC (Input/relay outputs (reinforced insulation)) |
| Connection in acc. with standard (EMC data) | CUL |
| Nominal supply voltage (Ambient conditions) | 24 V DC |
| Ambient temperature (operation) (Dimensions) | -20 °C ... 65 °C |
| Max. current consumption (Ambient conditions) | < 25 mA |
| Utilization restriction (Key Commercial Data) | EMC: class A product, see manufacturer's declaration in the download area |
| Certificate of classification (Connection data) | DNV GL TAA00000N1 |
| Conductor cross section AWG max. (Power supply) | 12 |
| Conductor cross section AWG min. (Power supply) | 26 |
| Electromagnetic compatibility (Connection data) | Conformance with EMC directive |
| Conductor cross section solid max. (Power supply) | 2.5 mm² |
| Conductor cross section solid min. (Power supply) | 0.2 mm² |
| Test voltage, input/output/supply (Connection data) | 1.5 kV (50 Hz, 1 min.) |
| Ambient temperature (storage/transport) (Dimensions) | -40 °C ... 85 °C |
| Conductor cross section flexible max. (Power supply) | 2.5 mm² |
| Conductor cross section flexible min. (Power supply) | 0.2 mm² |
| Fire protection for rail vehicles (DIN EN 45545-2) R22 (EMC data) | HL 1 - HL 2 |
| Fire protection for rail vehicles (DIN EN 45545-2) R23 (EMC data) | HL 1 - HL 2 |
| Fire protection for rail vehicles (DIN EN 45545-2) R24 (EMC data) | HL 1 - HL 2 |
| Fire protection for rail vehicles (DIN EN 45545-2) R22 (Connection data) | HL 1 - HL 2 |
| Fire protection for rail vehicles (DIN EN 45545-2) R23 (Connection data) | HL 1 - HL 2 |
| Fire protection for rail vehicles (DIN EN 45545-2) R24 (Connection data) | HL 1 - HL 2 |
Technical specifications and performance data