| Parameter | Value |
|---|---|
| GTIN | 4046356682435 |
| Orderkey | 2902823 |
| (General) | Class I, Zone 2, Group IIC |
| Catalog page | Page 114 (C-7-2015) |
| Depth (Note) | 102.5 mm |
| Packing unit | 1 pc |
| Width (Note) | 6.2 mm |
| Height (Note) | 93.1 mm |
| (Output data) | < 540 mW (at 30 V IN) |
| ATEX (General) | II 3 G Ex nA IIC T4 Gc X |
| Country of origin | DE (Germany) |
| (Connection data) | Class I, Zone 2, Group IIC |
| Comments (General) | Criterion B |
| Ripple (Input data) | < 20 mVPP |
| Custom tariff number | 85437090 |
| Conformance (General) | CE-compliant |
| Designation (General) | Conducted interferences |
| ATEX (Connection data) | II 3 G Ex nA IIC T4 Gc X |
| Color (Connection data) | green |
| Noise emission (General) | EN 61000-6-4 |
| UL, USA/Canada (General) | UL 508 Listed |
| Output current (Input data) | ≤ 30 mA |
| (Standards and Regulations) | For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |
| Conformance (Connection data) | CE-compliant |
| Electrical isolation (General) | Basic insulation according to EN 61010 |
| Power consumption (Output data) | < 600 mW (at 24 V IN) |
| Standards/regulations (General) | EN 61000-4-6 |
| Stripping length (Power supply) | 8 mm |
| Connection method (Power supply) | Spring-cage connection |
| Noise emission (Connection data) | EN 61000-6-4 |
| Noise immunity (Connection data) | EN 61000-6-2 When being exposed to interference, there may be minimal deviations. |
| UL, USA/Canada (Connection data) | UL 508 Listed |
| Housing material (Connection data) | PBT |
| Short-circuit current (Input data) | approx. 32 mA |
| Supply voltage range (Output data) | 9.6 V DC ... 30 V DC (The DIN rail bus connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, Order No. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715)) |
| Mounting position (Connection data) | any |
| Nominal supply voltage (Output data) | 24 V DC |
| Weight per Piece (excluding packing) | 79.300 g |
| Degree of pollution (Connection data) | 2 |
| China RoHS (Standards and Regulations) | Environmentally Friendly Use Period = 50 |
| Configurable/programmable (Input data) | Yes, preconfigured |
| Electrical isolation (Connection data) | Basic insulation according to EN 61010 |
| Max. current consumption (Output data) | < 25 mA (10 V output with 30 mA load at 24 V DC IN) |
| Overvoltage category (Connection data) | II |
| Assembly instructions (Connection data) | The T connector can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715. |
| Electromagnetic compatibility (General) | Conformance with EMC directive |
| Voltage input signal (Ambient conditions) | 9.6 V DC ... 30 V DC |
| Rated insulation voltage (Connection data) | 50 V AC/DC |
| Setting range comparison (Connection data) | ± 300 mV |
| Test voltage input/output (Connection data) | 1.5 kV (50 Hz, 1 min.) |
| Ambient temperature (operation) (Dimensions) | -20 °C ... 65 °C |
| Maximum transmission error (Connection data) | ≤ 0.1 % (of final value) |
| Utilization restriction (Key Commercial Data) | 1 |
| Certificate of classification (Connection data) | DNV GL 14085-15HH |
| Conductor cross section AWG max. (Power supply) | 12 |
| Conductor cross section AWG min. (Power supply) | 24 |
| Electromagnetic compatibility (Connection data) | Conformance with EMC directive |
| Conductor cross section solid max. (Power supply) | 2.5 mm² |
| Conductor cross section solid min. (Power supply) | 0.2 mm² |
| Maximum temperature coefficient (Connection data) | < 0.01 %/K |
| Temperature coefficient, typical (Connection data) | < 0.002 %/K |
| Ambient temperature (storage/transport) (Dimensions) | -40 °C ... 85 °C |
| Conductor cross section flexible max. (Power supply) | 2.5 mm² |
| Conductor cross section flexible min. (Power supply) | 0.2 mm² |
| Fire protection for rail vehicles (DIN EN 45545-2) R22 (General) | HL 1 - HL 2 |
| Fire protection for rail vehicles (DIN EN 45545-2) R23 (General) | HL 1 - HL 2 |
| Fire protection for rail vehicles (DIN EN 45545-2) R24 (General) | HL 1 - HL 2 |
| Fire protection for rail vehicles (DIN EN 45545-2) R22 (Connection data) | HL 1 - HL 2 |
| Fire protection for rail vehicles (DIN EN 45545-2) R23 (Connection data) | HL 1 - HL 2 |
| Fire protection for rail vehicles (DIN EN 45545-2) R24 (Connection data) | HL 1 - HL 2 |
Technical specifications and performance data
Installation and operation guide