Service time: Monday to Friday 9:00-18:00
MINI MCR-SL-2CP-I-I - MINI MCR-SL-2CP-I-I 2864655 PHOENIX CONTACT Loop-powered isolators
In Stock Hot Product

MINI MCR-SL-2CP-I-I

MINI MCR-SL-2CP-I-I 2864655 PHOENIX CONTACT Loop-powered isolators

$0.00USD
4290 in stock
Key Specifications
GTIN:4017918974893
Orderkey:2864655
(EMC data):Class I, Div. 2, Groups A, B, C, D
Catalog page:Page 101 (C-7-2015)
Supplier Information
Products: 0
Usually ships within 2-3 business days
Quality Guaranteed
Fast Shipping
Technical Support

Technical Specifications

ParameterValue
GTIN4017918974893
Orderkey2864655
(EMC data)Class I, Div. 2, Groups A, B, C, D
Catalog pagePage 101 (C-7-2015)
Packing unit1 pc
(Input data)4 mA ... 20 mA
GL (EMC data)GL EMC 2 D
ATEX (EMC data) II 3 G Ex nA II T6 X
Country of originDE (Germany)
(Connection data)Class I, Div. 2, Groups A, B, C, D
Ripple (Input data)< 10 mVrms(at 600 Ω)
Custom tariff number85437090
GL (Connection data)GL EMC 2 D
(Ambient conditions)4 mA ... 20 mA
Designation (General)Conducted interferences
ATEX (Connection data) II 3 G Ex nA II T6 X
Conformance (EMC data)CE-compliant
Designation (EMC data)Conducted interferences
Color (Connection data)green
Output name (Input data)Current output
Noise emission (EMC data)EN 61000-6-4
UL, USA/Canada (EMC data)UL 508 Recognized
Depth (Key Commercial Data)102.5 mm
Screw thread (Power supply)M3
Width (Key Commercial Data)6.2 mm
(Standards and Regulations)For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”
Height (Key Commercial Data)93.1 mm
Conformance (Connection data)CE-compliant
Evaluation criterion (General)A
Number of outputs (Input data)2
Electrical isolation (EMC data)Basic insulation according to EN 61010
Evaluation criterion (EMC data)A
Power consumption (Output data)34 mW (per channel)
Standards/regulations (General)EN 61000-4-6
Stripping length (Power supply)12 mm
Connection method (Power supply)Screw connection
Noise emission (Connection data)EN 61000-6-4
Noise immunity (Connection data)EN 61000-6-2 When being exposed to interference, there may be minimal deviations.
Standards/regulations (EMC data)EN 61000-4-6
UL, USA/Canada (Connection data)UL 508 Recognized
No. of channels (Connection data)2
Current output signal (Input data)0 mA ... 20 mA
Housing material (Connection data)PBT
Supply voltage range (Output data)no separate supply voltage necessary
Transmission Behavior (Input data)1:1 to input signal
Mounting position (Connection data)any
Weight per Piece (excluding packing)61.000 g
Degree of pollution (Connection data)2
Number of inputs (Ambient conditions)2
Response current (Ambient conditions)approx. 190 µA
China RoHS (Standards and Regulations)Environmentally Friendly Use Period = 50
Configurable/programmable (Input data)no
Electrical isolation (Connection data)Basic insulation according to EN 61010
Overvoltage category (Connection data)II
Assembly instructions (Connection data)The T connector can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715.
Max. input current (Ambient conditions)40 mA
max. input voltage (Ambient conditions)18 V
Electromagnetic compatibility (EMC data)Conformance with EMC directive
Limit frequency (3 dB) (Connection data)75 Hz
Step response (10-90%) (Connection data)5 ms (at 600 Ω load)
Voltage dissipation (Ambient conditions)1.9 V (I = 20 mA)
Current input signal (Ambient conditions)0 mA ... 20 mA
Rated insulation voltage (Connection data)50 V AC/DC
Connection in acc. with standard (EMC data)CUL
Test voltage input/output (Connection data)1.5 kV (50 Hz, 1 min.)
Ambient temperature (operation) (Dimensions)-20 °C ... 65 °C
Load/output load current output (Input data)< 600 Ω (at I = 20 mA output signal)
Maximum transmission error (Connection data)≤ 0.1 % (of final value)
Description of the input (Ambient conditions)Current input
Input voltage limitation (Ambient conditions)< 2 V (20 mA)
Configurable/programmable (Ambient conditions)no
Test voltage channel/channel (Connection data)1.5 kV (50 Hz, 1 min.)
Conductor cross section AWG max. (Power supply)12
Conductor cross section AWG min. (Power supply)26
Electromagnetic compatibility (Connection data)Conformance with EMC directive
Conductor cross section solid max. (Power supply)2.5 mm²
Conductor cross section solid min. (Power supply)0.2 mm²
Maximum temperature coefficient (Connection data)≤ 0.002 %/K (of measured value / 100 Ω load)
Additional error, load-dependent (Connection data)< 0.03 % (of measured value / 100 Ω load)
Temperature coefficient, typical (Connection data)< 0.002 %/K (of measured value / 100 Ω load)
Ambient temperature (storage/transport) (Dimensions)-40 °C ... 85 °C
Conductor cross section flexible max. (Power supply)2.5 mm²
Conductor cross section flexible min. (Power supply)0.2 mm²
Fire protection for rail vehicles (DIN EN 45545-2) R22 (EMC data)HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R23 (EMC data)HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R24 (EMC data)HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R22 (Connection data)HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R23 (Connection data)HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R24 (Connection data)HL 1 - HL 2

Product Description

MCR passive separator, with two channels, for galvanic separation of current signals without supply voltage, with screw connection
Key Features
  • Industrial grade quality
  • RoHS compliant
  • CE certified
  • 1-year warranty

Product Documents

Datasheet

Technical specifications and performance data

User Manual

Installation and operation guide

Top