| Parameter | Value |
|---|---|
| 0.14 mm² ... 2.5 mm² (without lug) | |
| Link | Screw connection |
| Depth | 119.2 mm |
| Input | < 1.4 W |
| width | 6.2 mm |
| Thread | M3 |
| height | 109.81 mm |
| Marking | II (1) G [Ex ia Ga] IIC |
| isolation | Dual/reinforced insulation |
| Certificate | CE Compliance |
| Height range | > 2000 m ... 3000 m |
| Product Type | Valve control module |
| Test voltage | 2.5 kV AC (50 Hz, 60 s) |
| Response time | < 50 ms |
| Noise emission | IEC/EN 61000-6-4 |
| Output voltage | ≥ 10.7 V DC (50 mA) |
| Product Family | MINI Analog Pro |
| No-load voltage | > 16 V DC |
| Output Resistor | ≥ 103 Ω (internal resistance Rthe) |
| Current limiting | > 50 mA |
| Number of inputs | 1 |
| Stripping length | 10 mm |
| Number of outputs | 1 |
| Tightening torque | 0.5 Nm ... 0.6 Nm |
| Degree of pollution | 2 (≤ 5000 m) |
| Ex i Circuits (EPL) | Ga |
| Degree of protection | Ip20 |
| Overvoltage Category | II (≤ 5000 m) |
| Standards/Provisions | IEC/EN 61010-1 |
| Supply voltage range | Self-powered in a loop, no external power supply required |
| Ex Installation (EPL) | Gc |
| Input signal, voltage | 19.2 V DC ... 30 V DC (24 V DC, -20 % ... +25 %) |
| Max. output power Por | 888 mW |
| Max. output current Ior | 185 mA |
| Max. output voltage Uor | 19.2 V |
| Immunity to disturbances | IEC/EN 61000-6-2 |
| Max. internal choke Lthe | negligible |
| Rated insulation voltage | 300 VEff |
| Maximum safety voltage Um | 253 V AC |
| Conductor cross-section AWG | (converted according to IEC) |
| Max. C internal capacitythe | 11 nF |
| Resistant to short circuits | Yes |
| Electromagnetic Compatibility | Tested according to the following standards and requirements: EN 61326-1 Use in an industrial environment, NAMUR NE 21 |
| Rigid conductor cross-section | 0.2 mm² ... 1.5 mm² (with lug) |
| Ambient temperature (operating) | -40 °C ... 70 °C |
| Flexible conductor cross-section | 0.14 mm² ... 2.5 mm² |
| Permissible humidity (operation) | 5 % ... 95 % (non-condensing) |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| I (simple current circuit): Max. external inductivity Lor/ Max. external capacity Cor | 10 mH / 8.7 μF |
| IIA (Simple Current Circuit): Max. External Inductivity Lor/ Max. external capacity Cor | 7 mH / 6.1 μF |
| IIC (Simple Current Circuit): Max. External Inductivity Lor/ Max. external capacity Cor | 0.8 mH / 240 nF |
| IIB/IIIC (simple current circuit): Max. external inductivity Lor/ Max. external capacity Cor | 4 mH / 1.53 μF |
Technical specifications and performance data