| Parameter | Value |
|---|---|
| GTIN | 4046356649476 |
| Orderkey | 2901996 |
| (General) | Class I, Zone 2, Group IIC T6 |
| Catalog page | Page 78 (C-5-2017) |
| Depth (Note) | 120.5 mm |
| GL (General) | GL applied for |
| Packing unit | 1 pc |
| Width (Note) | 6.2 mm |
| (Input data) | 4 mA ... 20 mA |
| Height (Note) | 110.5 mm |
| ATEX (General) | II 3 G Ex nA IIC T4 Gc X |
| Country of origin | DE (Germany) |
| (Connection data) | Class I, Zone 2, Group IIC T6 |
| Custom tariff number | 85437090 |
| GL (Connection data) | GL applied for |
| (Ambient conditions) | 4 mA ... 20 mA |
| Conformance (General) | CE-compliant |
| ATEX (Connection data) | II 3 G Ex nA IIC T4 Gc X |
| Color (Connection data) | gray |
| Noise emission (General) | EN 61000-6-4 |
| Output name (Input data) | Current output |
| UL, USA/Canada (General) | UL 508 Listed |
| Screw thread (Power supply) | M3 |
| (Standards and Regulations) | For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |
| Conformance (Connection data) | CE-compliant |
| Electrical isolation (General) | Reinforced insulation in accordance with IEC 61010-1 |
| Number of outputs (Input data) | 2 |
| Power consumption (Output data) | 600 mW |
| Stripping length (Power supply) | 10 mm |
| Connection method (Power supply) | Screw connection |
| Noise emission (Connection data) | EN 61000-6-4 |
| Noise immunity (Connection data) | EN 61000-6-2 When being exposed to interference, there may be minimal deviations. |
| UL, USA/Canada (Connection data) | UL 508 Listed |
| No. of channels (Connection data) | 2 |
| Current output signal (Input data) | 0 mA ... 20 mA |
| Housing material (Connection data) | PBT |
| Supply voltage range (Output data) | 9.6 V DC ... 30 V DC (no separate supply voltage necessary) |
| Transmission Behavior (Input data) | 1:1 to input signal |
| Mounting position (Connection data) | any |
| Weight per Piece (excluding packing) | 61.000 g |
| Degree of pollution (Connection data) | 2 |
| Number of inputs (Ambient conditions) | 2 |
| Response current (Ambient conditions) | approx. 200 µA |
| China RoHS (Standards and Regulations) | Environmentally Friendly Use Period = 50 |
| Configurable/programmable (Input data) | no |
| Electrical isolation (Connection data) | Reinforced insulation in accordance with IEC 61010-1 |
| Overvoltage category (Connection data) | II |
| Electromagnetic compatibility (General) | Conformance with EMC directive |
| Limit frequency (3 dB) (Connection data) | 100 Hz |
| Voltage dissipation (Ambient conditions) | 3.1 V (I = 20 mA) |
| Current input signal (Ambient conditions) | 0 mA ... 20 mA |
| Rated insulation voltage (Connection data) | 300 V (effective) |
| Ambient temperature (operation) (Dimensions) | -40 °C ... 70 °C |
| Load/output load current output (Input data) | < 600 Ω (at I = 20 mA output signal) |
| Maximum transmission error (Connection data) | ≤ 0.1 % (of final value) |
| Description of the input (Ambient conditions) | Current input |
| Input voltage limitation (Ambient conditions) | 30 V |
| Utilization restriction (Key Commercial Data) | EMC: class A product, see manufacturer's declaration in the download area |
| Configurable/programmable (Ambient conditions) | no |
| Test voltage channel/channel (Connection data) | 3 kV (50 Hz, 1 min.) |
| Electromagnetic compatibility (Connection data) | Conformance with EMC directive |
| Maximum temperature coefficient (Connection data) | ≤ 0.002 %/K (of measured value / 100 Ω load) |
| Additional error, load-dependent (Connection data) | < 0.075 % (of measured value / 100 Ω load) |
| Test voltage, input/output/supply (Connection data) | 3 kV (50 Hz, 1 min.) |
| Ambient temperature (storage/transport) (Dimensions) | -40 °C ... 85 °C |
| Conductor cross section flexible max. (Power supply) | 1.5 mm² |
| Conductor cross section flexible min. (Power supply) | 0.2 mm² |
| Max. AWG conductor cross section, flexible (Power supply) | 12 |
| Min. AWG conductor cross section, flexible (Power supply) | 24 |
| Fire protection for rail vehicles (DIN EN 45545-2) R22 (General) | HL 1 - HL 2 |
| Fire protection for rail vehicles (DIN EN 45545-2) R23 (General) | HL 1 - HL 2 |
| Fire protection for rail vehicles (DIN EN 45545-2) R24 (General) | HL 1 - HL 2 |
| Fire protection for rail vehicles (DIN EN 45545-2) R22 (Connection data) | HL 1 - HL 2 |
| Fire protection for rail vehicles (DIN EN 45545-2) R23 (Connection data) | HL 1 - HL 2 |
| Fire protection for rail vehicles (DIN EN 45545-2) R24 (Connection data) | HL 1 - HL 2 |
| Single conductor/terminal point, solid, with ferrule, max. (Power supply) | 1.5 mm² |
| Single conductor/terminal point, solid, with ferrule, min. (Power supply) | 0.2 mm² |
| Single conductor/terminal point, solid, without ferrule, max. (Power supply) | 2.5 mm² |
| Single conductor/terminal point, solid, without ferrule, min. (Power supply) | 0.2 mm² |
Technical specifications and performance data
Installation and operation guide