| Parameter | Value |
|---|---|
| GTIN | 4017918169275 |
| Orderkey | 2814715 |
| (General) | Class I, Div. 2, Groups A, B, C and D or Non-Hazardous Locations Only |
| Catalog page | Page 242 (C-5-2017) |
| Depth (Note) | 114.5 mm |
| Packing unit | 1 pc |
| Width (Note) | 22.5 mm |
| (Input data) | 20 mA ... 4 mA |
| Height (Note) | 99 mm |
| Country of origin | DE (Germany) |
| (Connection data) | Class I, Div. 2, Groups A, B, C and D or Non-Hazardous Locations Only |
| Custom tariff number | 85437090 |
| Conformance (General) | CE-compliant |
| Color (Connection data) | green |
| Noise emission (General) | EN 61000-6-4 |
| Noise immunity (General) | EN 61000-6-2 |
| Output name (Input data) | Voltage output / current output |
| UL, USA/Canada (General) | Class I, Zone 2, AEx nA nC IIC T4, Ex nA nC IIC T4 Gc X |
| Output name (Output data) | No switching output |
| Input (Ambient conditions) | Current measuring input |
| Screw thread (Power supply) | M3 |
| (Standards and Regulations) | For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |
| Conformance (Connection data) | CE-compliant |
| Maximum altitude (Dimensions) | < 2000 m |
| Low Voltage Directive (General) | Conformance with Low Voltage Directive |
| Stripping length (Power supply) | 8 mm |
| Connection method (Power supply) | Screw connection |
| Noise emission (Connection data) | EN 61000-6-4 |
| Noise immunity (Connection data) | EN 61000-6-2 |
| Status display (Connection data) | Green LED |
| UL, USA/Canada (Connection data) | Class I, Zone 2, AEx nA nC IIC T4, Ex nA nC IIC T4 Gc X |
| Impulse form (Ambient conditions) | AC, DC or distorted currents |
| Current output signal (Input data) | 0 mA ... 20 mA |
| Housing material (Connection data) | Polyamide PA non-reinforced |
| Voltage output signal (Input data) | 0 V ... 10 V |
| Mounting position (Connection data) | any |
| Surge strength (Ambient conditions) | 20 x IN(1 s) |
| Weight per Piece (excluding packing) | 134.080 g |
| Degree of pollution (Connection data) | 2 |
| Number of inputs (Ambient conditions) | 3 |
| China RoHS (Standards and Regulations) | Environmentally Friendly Use Period = 50 |
| Configurable/programmable (Input data) | Yes, unconfigured |
| Connection method (Ambient conditions) | Screw connection |
| Operate threshold (Ambient conditions) | 2 % (of measuring range nominal value 1/5/10 A) |
| Overload capacity (Ambient conditions) | 2 x IN (continuous) |
| Overvoltage category (Connection data) | III |
| Electromagnetic compatibility (General) | Conformance with EMC directive |
| Supply voltage range (Switching output) | 20 V DC ... 30 V DC |
| Input current range (Ambient conditions) | 0 A ... 11 A (AC/DC) |
| Step response (10-90%) (Connection data) | 330 ms (with AC) |
| Connection in acc. with standard (General) | CUL |
| Rated insulation voltage (Connection data) | 300 V AC (to earth) |
| Max. current consumption (Switching output) | < 40 mA (without load) |
| Test voltage input/output (Connection data) | 4 kV (50 Hz, 1 min.) |
| Ambient temperature (operation) (Dimensions) | -20 °C ... 60 °C |
| Load/output load current output (Input data) | < 500 Ω |
| Load/output load voltage output (Input data) | > 10 kΩ |
| Maximum transmission error (Connection data) | < 0.5 % (of nominal range value under nominal conditions) |
| Utilization restriction (Key Commercial Data) | EMC: class A product, see manufacturer's declaration in the download area |
| Configurable/programmable (Ambient conditions) | Yes, unconfigured |
| Frequency measuring range (Ambient conditions) | 15 Hz ... 400 Hz |
| Conductor cross section AWG max. (Power supply) | 14 |
| Conductor cross section AWG min. (Power supply) | 24 |
| Electromagnetic compatibility (Connection data) | Conformance with EMC directive |
| Conductor cross section solid max. (Power supply) | 2.5 mm² |
| Conductor cross section solid min. (Power supply) | 0.2 mm² |
| Test voltage input/power supply (Connection data) | 4 kV (50 Hz, 1 min.) |
| Temperature coefficient, typical (Connection data) | < 0.025 %/K |
| Test voltage output/power supply (Connection data) | 500 V (50 Hz, 1 min.) |
| Ambient temperature (storage/transport) (Dimensions) | -40 °C ... 85 °C |
| Conductor cross section flexible max. (Power supply) | 2.5 mm² |
| Conductor cross section flexible min. (Power supply) | 0.2 mm² |
| Setting range for max. input current (Ambient conditions) | 0 A ... 11 A |
| Setting range for min. input current (Ambient conditions) | 0 A ... 200 mA |
Technical specifications and performance data