| Parameter | Value |
|---|---|
| GTIN | 4046356902465 |
| Orderkey | 2904871 |
| Packing unit | 1 |
| (Input data) | 20 mA ... 4 mA |
| Custom tariff number | 85437090 |
| (Ambient conditions) | -10 mV ... 100 mV (min. measurement range 5 mV) |
| Conformance (General) | CE-compliant |
| Color (Connection data) | green |
| Designation (Output data) | Loop-powered |
| Signal output (Input data) | Current output |
| Depth (Key Commercial Data) | 114.5 mm |
| Screw thread (Power supply) | M3 |
| Width (Key Commercial Data) | 12.5 mm |
| (Standards and Regulations) | For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |
| Height (Key Commercial Data) | 99 mm |
| Conformance (Connection data) | CE-compliant |
| Standards/regulations (General) | NAMUR recommendation NE 21 |
| Stripping length (Power supply) | 8 mm |
| Connection method (Power supply) | Pluggable screw connection |
| Line monitoring (Connection data) | NE 43 |
| Switch-on delay (Connection data) | 4 s |
| Current output signal (Input data) | 4 mA ... 20 mA |
| Housing material (Connection data) | Polyamide PA non-reinforced |
| Supply voltage range (Output data) | 12 V DC ... 30 V DC |
| Tightening torque max (Power supply) | 0.6 Nm |
| Tightening torque, min (Power supply) | 0.5 Nm |
| China RoHS (Standards and Regulations) | Environmentally Friendly Use Period = 50 |
| Configurable/programmable (Input data) | no |
| Max. current consumption (Output data) | < 3.5 mA |
| Input signal range (Ambient conditions) | 10 Ω ... 400 Ω (min. measurement range 10 Ω) |
| Max. current output signal (Input data) | ≤ 23 mA |
| Standards/regulations (Connection data) | NAMUR recommendation NE 21 |
| Step response (10-90%) (Connection data) | < 2 s |
| Output current with wire break (Input data) | ≤ 3.6 mA or ≥ 21 mA (adjustable) |
| Ambient temperature (operation) (Dimensions) | -40 °C ... 55 °C |
| Load/output load current output (Input data) | ≤ 520 Ω (At UV= 24 V; Usupply- 12 V / 0.023 A) |
| Configurable/programmable (Ambient conditions) | no, preconfigured |
| Output current with short-circuit (Input data) | ≤ 3.6 mA or ≥ 21 mA (adjustable, not for thermocouples) |
| Conductor cross section AWG max. (Power supply) | 14 |
| Conductor cross section AWG min. (Power supply) | 24 |
| Flammability rating according to UL 94 (General) | V0 |
| Temperature measuring range (Ambient conditions) | -25 °C ... 200 °C |
| Conductor cross section solid max. (Power supply) | 2.5 mm² |
| Conductor cross section solid min. (Power supply) | 0.2 mm² |
| Conductor cross section flexible max. (Power supply) | 2.5 mm² |
| Conductor cross section flexible min. (Power supply) | 0.2 mm² |
| Sensor types that can be used (TC) (Ambient conditions) | B, C, D, E, J, K, L, N, R, S, T, U; min. measurement range 50 K/500 K |
| Flammability rating according to UL 94 (Connection data) | V0 |
| Sensor types (RTD) that can be used (Ambient conditions) | Pt, Ni (100, 500, 1000); min. measurement range 10 K |
| Output current range with overrange/underrange (Input data) | 3.8 mA ... 20.5 mA |
Technical specifications and performance data