| Parameter | Value |
|---|---|
| GTIN | 4017918899820 |
| Orderkey | 2864561 |
| Catalog page | Page 196 (C-5-2017) |
| Packing unit | 1 pc |
| (Input data) | 20 mA ... 4 mA |
| Country of origin | DE (Germany) |
| Custom tariff number | 85437090 |
| Conformance (General) | CE-compliant |
| Color (Connection data) | green |
| Noise emission (General) | EN 61326-1 (IEC 61326) and NAMUR NE 21 |
| Noise immunity (General) | EN 61326-1 (IEC 61326) and NAMUR NE 21 |
| Output name (Input data) | Current output |
| UL, USA/Canada (General) | Class I, Div. 2, Groups A, B, C, D |
| Designation (Output data) | Loop-powered |
| Depth (Key Commercial Data) | 114.5 mm |
| Screw thread (Power supply) | M3 |
| Width (Key Commercial Data) | 12.5 mm |
| (Standards and Regulations) | No hazardous substances above threshold values |
| Height (Key Commercial Data) | 99 mm |
| Conformance (Connection data) | CE-compliant |
| Number of outputs (Input data) | 1 |
| Configuration (Connection data) | Using MCR-PI-CONF-WIN configuration software package |
| Stripping length (Power supply) | 8 mm |
| Connection method (Power supply) | Screw connection |
| Noise emission (Connection data) | EN 61326-1 (IEC 61326) and NAMUR NE 21 |
| Noise immunity (Connection data) | EN 61326-1 (IEC 61326) and NAMUR NE 21 |
| UL, USA/Canada (Connection data) | Class I, Div. 2, Groups A, B, C, D |
| Switch-on delay (Connection data) | 4 s |
| Current output signal (Input data) | 4 mA ... 20 mA |
| Housing material (Connection data) | Polyamide PA non-reinforced |
| Supply voltage range (Output data) | 12 V DC ... 35 V DC |
| Mounting position (Connection data) | any |
| Weight per Piece (excluding packing) | 105.600 g |
| China RoHS (Standards and Regulations) | Environmentally friendly use period: unlimited = EFUP-e |
| Configurable/programmable (Input data) | Yes |
| Max. current consumption (Output data) | < 3.5 mA |
| Step response (10-90%) (Connection data) | < 2 s |
| Connection in acc. with standard (General) | CUL |
| Connection technology (Ambient conditions) | 2, 3, 4-wire |
| Output current with wire break (Input data) | ≤ 3.6 mA or ≥ 21 mA (adjustable) |
| Test voltage input/output (Connection data) | 2 kV (50 Hz, 1 min.) |
| Ambient temperature (operation) (Dimensions) | -40 °C ... 85 °C |
| Load/output load current output (Input data) | max (Vsupply-12 V) / 0.023 A (current output) |
| Configurable/programmable (Ambient conditions) | Yes, programmable |
| Output current with short-circuit (Input data) | ≤ 3.6 mA or ≥ 21 mA (adjustable, not for thermocouples) |
| Conductor cross section AWG max. (Power supply) | 14 |
| Conductor cross section AWG min. (Power supply) | 24 |
| Conductor cross section solid max. (Power supply) | 2.5 mm² |
| Conductor cross section solid min. (Power supply) | 0.2 mm² |
| Transmission error thermocouples (Connection data) | typ. 0.5 K (K, J, T, E, L, U), 1.0 K (N, C, D), 2.0 K (S, B, R) |
| Transmission error voltage sensor (Connection data) | ± 20 µV (-10...100 mV) |
| Conductor cross section flexible max. (Power supply) | 2.5 mm² |
| Conductor cross section flexible min. (Power supply) | 0.2 mm² |
| Linear resistance measuring range (Ambient conditions) | Resistance-type sensor from 10 Ω to 400 Ω and from 10 Ω to 2000 Ω; minimum measurement range 10 Ω/100 Ω |
| Sensor types that can be used (TC) (Ambient conditions) | B, C, D, E, J, K, L, N, R, S, T, U; minimum measurement range 50 K/500 K |
| Sensor types (RTD) that can be used (Ambient conditions) | Pt, Ni (100, 500, 1000); minimum measurement range 10 K |
| Output current range with overrange/underrange (Input data) | ≤ 20.5 mA / ≥ 3.8 mA (linear increase/decrease) |
| Transmission error resistance thermometer (Connection data) | 0.2 K (Pt 100, Ni 100), 0.5 K (Pt 500, Ni 500), 0.3 K (Pt 1000, Ni 1000) |
| Transmission error resistance-type sensor (Connection data) | ± 0.1 Ω (10...400 Ω), ± 1.5 Ω (10...2000 Ω) |
Technical specifications and performance data
Installation and operation guide