| Parameter | Value |
|---|---|
| ≤ 1.7 s | |
| EMC | B |
| Note | and EN 61326 |
| Type | Signal conditioners with SIL functional safety |
| Color | gray (RAL 7042) |
| Depth | 113.7 mm |
| Width | 12.5 mm |
| Height | 112.5 mm |
| Altitude | ≤ 2000 m (The technical data refers to altitudes ≤2000 m above mean sea level. For altitudes >2000 m above mean sea level, refer to the data sheet.) |
| EMC note | EMC: class A product, see manufacturer's declaration in the download area |
| Humidity | B |
| Enclosure | Required protection according to the Rules shall be provided upon installation on board |
| Vibration | A |
| Insulation | Safe isolation in accordance with IEC/EN 61010-1 |
| Application | Temperature |
| Certificate | CE-compliant |
| Designation | Electromagnetic RF field |
| Temperature | B |
| Height range | > 2000 m ... 3000 m |
| Input signal | Temperature |
| Product type | Temperature transmitter |
| Screw thread | M3 |
| Sensor type: | 500 °C ... 1820 °C |
| Test voltage | 2.5 kV AC (50 Hz, 60 s) |
| Configuration | Software |
| Max. diameter | 2 mm |
| Mounting type | DIN rail mounting |
| Identification | II 3 G Ex ec ic IIC T4 Gc |
| Noise emission | EN 61000-6-4 |
| Noise immunity | EN 61000-6-2 |
| Product family | MACX Analog |
| Status display | Green LED (supply voltage) |
| No. of channels | 1 |
| Article revision | 06 |
| Depth NS 35/7,5 | 114.5 mm (Snapped onto DIN rail NS 35/7,5 in accordance with EN 60715) |
| Housing material | PA 6.6-FR |
| Number of inputs | 1 |
| Pollution degree | 2 |
| Stripping length | 7 mm |
| Connection method | Screw connection |
| Number of outputs | 1 |
| Power consumption | ≤ 1 W |
| Power dissipation | ≤ 0.76 W |
| Tightening torque | 0.5 Nm ... 0.6 Nm |
| Dimensional drawing | |
| Degree of protection | IP20 |
| Electrical isolation | 3-way isolation |
| Overvoltage category | II |
| Supply voltage range | 19.2 V DC ... 30 V DC (24 V DC, -20 % ... +25 %) |
| Current output signal | 0 mA ... 20 mA |
| Ex installation (EPL) | Gc |
| Standards/regulations | EN 61000-4-3 |
| Cold point error, max. | ± 2 K |
| Linear mV signal range | -1000 mV ... 1000 mV |
| Nominal supply voltage | 24 V DC |
| Output ripple (current) | < 15 µAPP |
| Step response (0–99%) | 1 s |
| Max. current consumption | < 40 mA (24 V DC) |
| Rated insulation voltage | 300 Vrms |
| Configurable/programmable | Yes |
| Conductor cross section AWG | 24 ... 14 |
| Temperature measuring range | -250 °C ... 2500 °C (Range depending on the sensor type) |
| Transmission error, typical | 0.1 % (For full identification of transmission errors, see the data sheet) |
| Conductor cross section rigid | 0.2 mm² ... 2.5 mm² |
| Electromagnetic compatibility | Conformance with EMC directive |
| Ambient temperature (operation) | -40 °C ... 70 °C (Any mounting position) |
| Load/output load current output | ≤ 600 Ω |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Permissible humidity (operation) | 5 % ... 95 % (non-condensing) |
| Temperature coefficient, typical | 0.01 %/K |
| Sensor types that can be used (TC) | B, E, J, K, N, R, S, T, L, U, C, D, A-1, A-2, A-3, M, Lr |
| Flammability rating according to UL 94 | V0 (Housing) |
| Ambient temperature (storage/transport) | -40 °C ... 80 °C |
| Behavior in the event of a sensor error | As per NE 43 or can be freely defined |
| Typical deviation from the measuring range final value | 1 % |
Technical specifications and performance data
Installation and operation guide