| Parameter | Value |
|---|---|
| (General) | Class I, Zone 2, Group IIC T6 |
| Depth (Note) | 114.5 mm |
| Width (Note) | 17.5 mm |
| (Input data) | 1 A (30 V DC) |
| Height (Note) | 99 mm |
| ATEX (General) | II 3 G Ex nA nC ic IIC T4 Gc X |
| IECEx (General) | Ex nA nC ic IIC T4 Gc X |
| UNSPSC 11 (ETIM) | 39121008 |
| ETIM 4.0 (eCl@ss) | EC001596 |
| ETIM 5.0 (eCl@ss) | EC002568 |
| (Connection data) | Class I, Zone 2, Group IIC T6 |
| UNSPSC 13.2 (ETIM) | 39121008 |
| UNSPSC 6.01 (ETIM) | 30211506 |
| UNSPSC 12.01 (ETIM) | 39121008 |
| UNSPSC 7.0901 (ETIM) | 39121008 |
| Conformance (General) | CE-compliant |
| ATEX (Connection data) | II 3 G Ex nA nC ic IIC T4 Gc X |
| Color (Connection data) | green |
| IECEx (Connection data) | Ex nA nC ic IIC T4 Gc X |
| Utilization restriction | EMC: class A product, see manufacturer's declaration in the download area |
| Output name (Input data) | Relay output |
| Contact type (Input data) | 1 PDT |
| UL, USA / Canada (General) | UL 508 Listed |
| Noise immunity (Dimensions) | EN 61000-6-2 When being exposed to interference, there may be minimal deviations. |
| Screw thread (Power supply) | M3 |
| Conformance (Connection data) | CE-compliant |
| Contact material (Input data) | AgSnO2, hard gold-plated |
| Designation (Connection data) | Input/switching output |
| Maximum altitude (Dimensions) | ≤ 2000 m |
| Electrical isolation (General) | 4-way, between input/output/power supply/switching output |
| Power consumption (Output data) | < 1.5 W |
| Stripping length (Power supply) | 7 mm |
| Connection method (Power supply) | Screw connection |
| Current output signal (Input data) | 0 mA ... 20 mA ±10 V (in the case of SIL; further free configuration without SIL) |
| Housing material (Connection data) | PA 66-FR |
| Supply voltage range (Output data) | 24 V ... 230 V AC/DC (-20 %/+10 %, 50/60 Hz) |
| UL, USA / Canada (Connection data) | UL 508 Listed |
| Maximum inrush current (Input data) | 0.5 A (30 V AC) |
| Degree of pollution (Connection data) | 2 |
| Electrical isolation (Connection data) | 375 V (Peak value in accordance with EN 60079-11) |
| Maximum switching voltage (Input data) | 30 V AC (30 V DC) |
| Overvoltage category (Connection data) | II |
| eCl@ss 4.0 (Standards and Regulations) | 27210107 |
| eCl@ss 4.1 (Standards and Regulations) | 27210107 |
| eCl@ss 5.0 (Standards and Regulations) | 27210107 |
| eCl@ss 5.1 (Standards and Regulations) | 27210107 |
| eCl@ss 6.0 (Standards and Regulations) | 27210107 |
| eCl@ss 7.0 (Standards and Regulations) | 27210107 |
| eCl@ss 8.0 (Standards and Regulations) | 27371503 |
| Electromagnetic compatibility (General) | Conformance with EMC directive |
| Input signal range (Ambient conditions) | -1000 mV ... 1000 mV |
| Max. current output signal (Input data) | 22 mA |
| Max. voltage output signal (Input data) | ± 11 V |
| Functional Safety (SIL) (Connection data) | SIL 2 |
| Ambient temperature (operation) (Dimensions) | -20 °C ... 65 °C |
| Load/output load current output (Input data) | ≤ 600 Ω (20 mA) |
| Load/output load voltage output (Input data) | ≥ 10 kΩ |
| Permissible humidity (operation) (Dimensions) | typ. 5 % ... 95 % (non-condensing) |
| Conductor cross section AWG max. (Power supply) | 14 |
| Conductor cross section AWG min. (Power supply) | 24 |
| Electromagnetic compatibility (Connection data) | Conformance with EMC directive |
| Flammability rating according to UL 94 (General) | V0 |
| Temperature measuring range (Ambient conditions) | -250 °C ... 2500 °C (Range depending on the sensor type) |
| Conductor cross section solid max. (Power supply) | 2.5 mm² |
| Conductor cross section solid min. (Power supply) | 0.2 mm² |
| Maximum temperature coefficient (Connection data) | 0.01 %/K |
| Potentiometer resistance range (Ambient conditions) | 0 Ω ... 50 kΩ |
| Ambient temperature (storage/transport) (Dimensions) | -40 °C ... 85 °C |
| Behavior in the event of a sensor error (Input data) | according to NE 43 or freely configurable |
| Conductor cross section flexible max. (Power supply) | 2.5 mm² |
| Conductor cross section flexible min. (Power supply) | 0.2 mm² |
| Sensor types that can be used (TC) (Ambient conditions) | B, E, J, K, N, R, S, T, L, U, CA, DA, A1G, A2G, A3G, MG, LG |
| Flammability rating according to UL 94 (Connection data) | V0 |
| Sensor types (RTD) that can be used (Ambient conditions) | Pt, Ni, Cu sensors: 2, 3, 4-wire |