| Parameter | Value |
|---|---|
| GTIN | 4055626043906 |
| Orderkey | 2906170 |
| (Drawings) | |
| Catalog page | Page 140 (C-5-2019) |
| Packing unit | 1 |
| (Input data) | ≤ 0.2 A DC (ohmic load, 120 V DC) |
| ATEX (General) | II 3 G Ex ec nC IIC T4 Gc |
| (Power supply) | 2.5 kV (50 Hz, 1 min., test voltage) |
| IECEx (General) | Ex ec nC IIC T4 Gc |
| Depth (Drawings) | 114.5 mm |
| Width (Drawings) | 12.5 mm |
| ETIM 4.0 (eCl@ss) | EC002653 |
| ETIM 5.0 (eCl@ss) | EC002653 |
| ETIM 6.0 (eCl@ss) | EC002653 |
| ETIM 7.0 (eCl@ss) | EC002653 |
| Height (Drawings) | 99 mm |
| SIL (Power supply) | 2 |
| ATEX (Power supply) | II 3 G Ex ec nC IIC T4 Gc |
| Custom tariff number | 85437090 |
| IECEx (Power supply) | Ex ec nC IIC T4 Gc |
| (Ambient conditions) | Short circuit U > 10.8 V, I > 21.1 mA |
| Conformance (General) | CE-compliant, additionally EN 61326 |
| Block diagram (Drawings) | |
| Noise emission (General) | EN 61000-6-4 |
| Output name (Input data) | Relay output |
| UL, USA/Canada (General) | UL applied for |
| Contact type (Input data) | 1 PDT |
| Conformance (Power supply) | CE-compliant, additionally EN 61326 |
| Designation (Power supply) | Input/supply, DIN rail connector |
| Noise immunity (Dimensions) | EN 61000-6-2 When being exposed to interference, there may be minimal deviations. |
| (Standards and Regulations) | For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |
| eCl@ss 4.0 (Classifications) | 27210100 |
| eCl@ss 4.1 (Classifications) | 27210100 |
| eCl@ss 5.0 (Classifications) | 27210100 |
| eCl@ss 5.1 (Classifications) | 27210100 |
| eCl@ss 6.0 (Classifications) | 27210100 |
| eCl@ss 7.0 (Classifications) | 27210120 |
| eCl@ss 8.0 (Classifications) | 27210120 |
| eCl@ss 9.0 (Classifications) | 27210120 |
| Contact material (Input data) | AgSnO2, hard gold-plated |
| Maximum altitude (Dimensions) | ≤ 2000 m |
| Status display (Power supply) | Green LED (supply voltage, PWR) |
| UL, USA/Canada (Power supply) | UL applied for |
| Housing material (Power supply) | PA 6.6-FR |
| Power consumption (Output data) | ≤ 1.2 W |
| Power dissipation (Output data) | < 0.9 W |
| Degree of pollution (Power supply) | 2 |
| Supply voltage range (Output data) | 9.6 V DC ... 30 V DC (12 V DC ... 24 V DC (-20 % ... +25 %)) |
| Electrical isolation (Power supply) | 375 V (Peak value in accordance with EN 60079-11) |
| Max. switching current (Input data) | ≤ 4 A AC (cos phi = 1) |
| Overvoltage category (Power supply) | II |
| Interference emission (Power supply) | EN 61000-6-4 |
| Mechanical service life (Input data) | ≤ 107cycles |
| Nominal supply voltage (Output data) | 24 V DC |
| China RoHS (Standards and Regulations) | Environmentally Friendly Use Period = 50 |
| Max. current consumption (Output data) | 90 mA (10 V DC) |
| REACh SVHC (Standards and Regulations) | Lead 7439-92-1 |
| Step response (0–99%) (Power supply) | ≤ 22 ms |
| Electromagnetic compatibility (General) | Conformance with EMC directive |
| Current input signal (Ambient conditions) | 0.2 mA ... 20 mA |
| Line fault detection (Ambient conditions) | Break U |
| Maximum transmission error (Power supply) | 0.1 % |
| Switching hysteresis (Ambient conditions) | off: approx. 0.5 %, on: approx. 1 % |
| Typical current consumption (Output data) | 38 mA (24 V DC) |
| Voltage input signal (Ambient conditions) | 0.1 V ... 10 V |
| Ambient temperature (operation) (Dimensions) | -20 °C ... 65 °C (Any mounting position) |
| Electromagnetic compatibility (Power supply) | Conformance with EMC directive |
| Permissible humidity (operation) (Dimensions) | 5 % ... 95 % (non-condensing) |
| Maximum temperature coefficient (Power supply) | 0.01 %/K |
| Input resistance current input (Ambient conditions) | < 28 Ω |
| Ambient temperature (storage/transport) (Dimensions) | -40 °C ... 85 °C |
| Input resistance of voltage input (Ambient conditions) | > 100 kΩ |
Technical specifications and performance data