Service time: Monday to Friday 9:00-18:00
MACX MCR-SL-RTD-I-SP-NC - MACX MCR-SL-RTD-I-SP-NC 2924320 PHOENIX CONTACT Temperature measuring transducer
In Stock Hot Product

MACX MCR-SL-RTD-I-SP-NC

MACX MCR-SL-RTD-I-SP-NC 2924320 PHOENIX CONTACT Temperature measuring transducer

$0.00USD
3139 in stock
Key Specifications
:≤ 1100 ms
Note:and EN 61326-1
Type:Signal conditioner
Color:gray (RAL 7042)
Supplier Information
Products: 0
Usually ships within 2-3 business days
Quality Guaranteed
Fast Shipping
Technical Support

Technical Specifications

ParameterValue
≤ 1100 ms
Noteand EN 61326-1
TypeSignal conditioner
Colorgray (RAL 7042)
Depth114.5 mm
Width12.5 mm
Height116 mm
Altitude≤ 2000 m
InsulationSafe isolation in accordance with IEC/EN 61010-1
ApplicationTemperature
CertificateCE-compliant
DesignationElectromagnetic RF field
Input signalTemperature
Product typeTemperature transmitter
Test voltage2.5 kV AC (50 Hz, 60 s)
Mounting typeDIN rail mounting
Alignment span± 5 %
Alignment zero± 5 %
Identification II 3G Ex nA ic IIC T4 Gc X
Noise emissionEN 61000-6-4
Noise immunityEN 61000-6-2
Status displayLED supply voltage, PWR (green)
Housing materialPA 6.6-FR
Number of inputs1
Pollution degree2
Stripping length8 mm
Connection methodPush-in connection
Number of outputs1
Power dissipation< 1 W
Output descriptionCurrent output
Dimensional drawing
Degree of protectionIP20 (not assessed by UL)
Electrical isolation3-way isolation
Overvoltage categoryII
Sensor input current200 µA ... 1 mA
Supply voltage range19.2 V DC ... 30 V DC (24 V DC, -20 % ... +25 %)
Current output signal0 mA ... 20 mA
Standards/regulationsEN 61000-4-3
Nominal supply voltage24 V DC
Output ripple (current)< 50 µAPP
Step response (0–99%)700 ms
Max. current consumption< 40 mA (24 V DC)
Rated insulation voltage300 Vrms
Configurable/programmableno
Conductor cross section AWG24 ... 16
Temperature measuring range-200 °C ... 850 °C (Range depending on the sensor type)
Conductor cross section rigid0.2 mm² ... 1.5 mm²
Ambient temperature (operation)-20 °C ... 60 °C (Any mounting position)
Load/output load current output≤ 500 Ω
Conductor cross section flexible0.2 mm² ... 1.5 mm²
Permissible humidity (operation)5 % ... 95 % (non-condensing)
Temperature coefficient, typical0.01 %/K
Linear resistance measuring range0 Ω ... 2000 Ω
Sensor types (RTD) that can be usedPt, Ni, Cu sensors: 2, 3, 4-wire
Flammability rating according to UL 94V0 (Housing)
Ambient temperature (storage/transport)-40 °C ... 80 °C
Behavior in the event of a sensor errorAs per NE 43 or can be freely defined
Max. permissible overall conductor resistance50 Ω (Per cable)

Product Description

Temperature transducer, converts signals from resistance temperature detectors and resistors into 0/4 - 20 mA analog signals. Freely programmable, 3-way electrical isolation. Replacement item: 1050201
Key Features
  • Industrial grade quality
  • RoHS compliant
  • CE certified
  • 1-year warranty

Product Documents

Datasheet

Technical specifications and performance data

User Manual

Installation and operation guide

Top